Heat recovery unit
UTNR-T FRESHFresh air units with counterflow static heat recovery. Class A1 mineral wool insulation.
Key features
High efficiency heat recovery
Low-noise Brushless EC fans
F7 and M5 high efficiency filters
Sandwich panels – thickness 40 mm
Mineral wool insulation class A1 fire reaction
Compact size
Competitive solution
Description
Construction features
• Recovery unit: very high efficiency static heat recovery, with aluminum plates with counter-current flows.
• Fans: supply and exhaust fans with highly efficient EC Brushless electric motors with 6 speeds.
• Structure: insulating sandwich panels 40mm thick. Coated externally in corrosion-resistant pre-painted galvanised steel and internally in galvanised steel. Insulation in mineral wool with high thermal and acoustic properties. Fire reaction class A1.
• Air tightness: EPDM gaskets on the panels and balloon gaskets on the inspection doors to ensure full air tightness.
• Stainless steel condensate drain pan, fully integrated in the panel. Side connection drain.
• Filters: compact cell filters with low pressure drop polypropylene media, removable from the side, with ISO ePM10 50%(M5) + ISO ePM1 50% (F7) class efficiency on supply side and ISO ePM10 50% (M5) on exhaust side.
• Factory-installed dirty filter differential pressure switches.
• Integrated defrosting / free-cooling by-pass system. Thanks to the presence of a motorised damper on the heat recovery side, a bypass system can be created to manage freecooling or defrosting depending on thermo-hygrometric requests.
• Integrated control system with electrical box, regulator and user panel that can be remote-controlled up to 100m. No additional power and protection components required.
Separately supplied accessories
• KBEP - Single stage electric heater with antifreeze/pre-heating function, complete with safety thermostat.
• KBER - 3-stage post-heating electric heater, complete with safety thermostat.
• KBA - 2 rows hot water post-heating coil.
• KC5H1 - 5-rows water cooling coil and 1-row water post-heating coil.
• KSRE - Damper with ON/OFF servo control.
Controls
• Mode selection (Auto Heat, Auto Cool, Man. Heat, Man. Cool, Fan Mode).
• Room temperature measurement thanks to the probe integrated in the user panel.
• Fans speed control with 0-10V signal at 6 speed steps.
• Heat recovery bypass management in antifreeze/freecooling/freeheating mode.
• Weekly and daily programming.
• Modbus RTU serial interface via RS485 connection.
• Dirty filter monitoring.
• Automatic restart after power failure.
• Automatic fans speed control based on air quality probe (optional).
• Automatic electrical coil management by steps (optional).
• Management of heating/cooling/summer dehumidification functions (optional).
• Management of ON/OFF or modulating water coils valves (optional).
• Management of ON/OFF dampers (optional).
Technical data
MODEL UTNR-T FRESH | 40 | 60 | 80 | 100 | 150 | 205 | 260 | 330 | ||||
Supply filters | M5 + F7 | M5 + F7 | M5 + F7 | M5 + F7 | M5 + F7 | M5 + F7 | M5 + F7 | M5 + F7 | ||||
Return filters | M5 | M5 | M5 | M5 | M5 | M5 | M5 | M5 | ||||
TECHNICAL SPECIFICATIONS | ||||||||||||
Nominal air flow rate | m³/h | 400 | 600 | 800 | 1000 | 1500 | 2050 | 2600 | 3300 | |||
STANDARD FANS | ||||||||||||
Motor type | EC | EC | EC | EC | EC | EC | EC | EC | ||||
❶ | Supply available static pressure | Pa | 75 | 75 | 100 | 100 | 100 | 125 | 125 | 150 | ||
❷ | Specific fan power (SFP) | W/(m³/s) | 570 | 611,2 | 578,6 | 576,1 | 844,8 | 586,2 | 589,8 | 628,5 | ||
❸ | Sound pressure level | dB(A) | 35 | 43 | 35 | 41 | 52 | 46 | 51 | 53 | ||
Speed No./Control Type | 6 / 0-10V | 6 / 0-10V | 6 / 0-10V | 6 / 0-10V | 6 / 0-10V | 6 / 0-10V | 6 / 0-10V | 6 / 0-10V | ||||
Power supply | V-ph-Hz | 230-1-50 | 230-1-50 | 230-1-50 | 230-1-50 | 230-1-50 | 230-1-50 | 230-1-50 | 230-1-50 | |||
COUNTERFLOW HEAT RECOVERY | ||||||||||||
❹ | Winter Efficiency | % | 88,5 | 88,5 | 87,4 | 87,6 | 88,6 | 88,7 | 89,2 | 88,6 | ||
❺ | Summer Efficiency | % | 82,8 | 82,8 | 80,9 | 81,3 | 83,4 | 83,6 | 84,2 | 83,5 | ||
❻ | Efficiency EcoDesign CE 1253/2014 | % | 82,9 | 82,9 | 81 | 81,4 | 83,5 | 83,7 | 84,3 | 83,6 | ||
OPERATING LIMITS | ||||||||||||
Outdoor air inlet temperature limit | °C | -24<T<46 | -24<T<46 | -24<T<46 | -24<T<46 | -24<T<46 | -24<T<46 | -24<T<46 | -24<T<46 | |||
DIMENSIONS AND WEIGHTS | 40 | 60 | 80 | 100 | 150 | 205 | 260 | 330 | ||||
Length | mm | 721 | 845 | 915 | 965 | 1015 | 1290 | 1720 | 1780 | |||
Height | mm | 397 | 397 | 479 | 479 | 618 | 618 | 618 | 759 | |||
Depth | mm | 1346 | 1346 | 1638 | 1638 | 1937 | 1937 | 1937 | 2219 | |||
❼ | Weight | kg | 92,3 | 104,2 | 137,3 | 144,5 | 193,9 | 233,1 | 291 | 368,3 | ||
Connections drain pan | inch | 3/4″ | 3/4″ | 3/4″ | 3/4″ | 3/4″ | 3/4″ | 3/4″ | 3/4″ |
- Data at the following conditions:
- ❶ Values refer to the nominal air flow rate considering the pressure drops of the unit without accessories.
- ❷ Data according to CE 1253/2014 at nominal air flow rate and available static pressure without accessories.
- ❸ Sound pressure level at 1 m distance in open field.
- ❹ Winter conditions: outdoor air -5ºC, 80% RH and room air 22ºC, 50% RH.
- ❺ Summer conditions: outdoor air 35ºC, 40% RH and room air 24ºC, 50% RH.
- ❻ Values refer to CE 1253/2014 at balanced air flow rates.
- ❼ Unit weight without accessories.
Manuals
To view all the documents, log in to the reserved area
Technical notes
To view all the documents, log in to the reserved area
Documents
To view all the documents, log in to the reserved area
Images
Request information about this product
Find a reseller in your area for a customized offer on Rhoss air conditioning solutions.