New
Web code (TXHETU): WFX05 Web code (TXHETY): WFX01
EXP Multi-purpose Systems

WinFLOW ECO EXP WinFLOW EXP

TXHET 4185÷4395
Cooling capacity 180÷373,8 kW
Heating capacity 200,1÷435,7 kW

EXPsystems - Polyvalent ecological water-cooled system. Series with scroll hermetic compressors and R454B or R410A refrigerant gas.

Features

Key features


Multi-purpose units with TER up to 7,5

Efficient and eco-friendly range in R454B

Applications with well water, water mains, geothermal probes or dry cooler

Extended operating limits

Touch interface (optional)

Integrated MASTER/SLAVE control


WinFLOW ECO EXP WinFLOW EXP

Description

Construction features

• Compressor: hermetic rotary scroll complete with thermal protection and crankcase heater.
• Primary side (user), secondary (recovery) and disposal side heat exchanger (well, mains, geothermal probes or dry cooler): with stainless steel plates, complete with closed cell polyurethane foam rubber insulation and water flow differential pressure switch.
• Control: microprocessor electronic control with Adaptive Function Plus logic.
• Structure: made of galvanised and painted steel plate with polyester powder coating.
• The unit is also complete with:
- compressor circuit breaker switches;
- electronic expansion valve;
- display of cooling circuit high and low pressure;
- Master/Slave control up to 4 units in parallel;
- clock board;
- 0-10V analogue signal for condensing/evaporating control performed by external device;
- control of Variable Primary Flow (VPF_R).

Versions

• T - High efficiency version

Models

- TXHETU: EXPsystems units with R454B gas.
- TXHETY: EXPsystems units with R410A gas.

Factory fitted accessories

• Recovery side VPF_R control.
• Power factor correction capacitors (cosφ > 0.94).
• Soft-starter.
• Energy parameter measuring device.
• Cooling circuit outlet and intake valves (TXHETY)
• Cooling circuit outlet valves (TXHETU).
• Refrigerant leak detector.
• Forced limit of power consumption.
• Cooling circuit high and low pressure gauges.
• Double safety valves.
• Technical compartment soundproofing.
• Compressor soundproof enclosures
• Control of min/max power supply voltage.
• Low temperature water production.
• Digital input for double set-point.
• 4-20mA analogue signal for shifting set-point.
• Antifreeze heaters for heat exchangers and electrical panel.
• Interfaces for serial communication with other devices.
• Colour touch user keypad (fitted on the machine or remotely) with 7'' display.
• Set-up for outdoor installation.
• Anti-vibration mounts.

Separately supplied accessories

• 3-way modulating condensing control valve.
• 2-way modulating condensing control valve.
• Outdoor air temperature probe for set-point compensation.
• Water filter.
• Remote keypad with display.
• Thermostat with display.
• Rhoss supervisors for unit monitoring and remote management.
• Rhoss sequencer for integrated management of multiple chillers.

Technical data

TXHETU MODEL 4185 4210 4240 4275 4305 4350 4395
COOLING OPERATIONS (AUTOMATIC 1 MODE)
Nominal cooling capacity kW 180 206,7 232,4 259,3 286,4 324,8 365,2
Absorbed power kW 40,3 48,3 55,2 61,2 67,2 76,2 86,5
E.E.R. 4,47 4,28 4,21 4,24 4,26 4,26 4,22
COOLING OPERATIONS + TOTAL RECOVERY (AUTOMATIC 2 MODE)
Nominal cooling capacity kW 156,5 181,9 206,8 232,4 259,1 298,2 330,7
Recovery heating capacity kW 202,7 237,2 270,6 302,2 335,5 384,7 428,9
T.E.R. 7,45 7,23 7,16 7,29 7,38 7,5 7,32
HEATING OPERATIONS (MODE SELECT 1-2 AUTOMATIC 3)
Nominal heating capacity kW 200,1 234,6 267,2 299 332,3 380,2 424,8
Total absorbed power kW 49,8 60 68,9 76,1 83,9 94,8 108,4
C.O.P. 4,02 3,91 3,88 3,93 3,96 4,01 3,92
TXHETU MODEL 4185 4210 4240 4275 4305 4350 4395
Sound pressure dB(A) 47 47 48 49 51 52 53
Sound power dB(A) 79 79 80 81 83 84 85
Sound power with soundproofing set-up dB(A) 76,5 76,5 77,5 78,5 80,5 81,5 82,5
Scroll compressor/steps no. 4/4 4/4 4/4 4/4 4/4 4/4 4/4
Circuits no. 2 2 2 2 2 2 2
Electrical supply V-ph-Hz 400-3-50 400-3-50 400-3-50 400-3-50 400-3-50 400-3-50 400-3-50
DIMENSIONS AND WEIGHTS 4185 4210 4240 4275 4305 4350 4395
L – Width mm 2510 2510 2510 2510 2510 2510 2510
H – Height mm 1860 1860 1860 1860 1860 1860 1860
P – Depth mm 870 870 870 870 870 870 870
Weight kg 1205 1315 1455 1500 1520 1675 1770
SEASONAL ENERGY PERFORMANCE 4185 4210 4240 4275 4305 4350 4395
TXHETU MODEL SEASONAL PERFORMANCE IN COOLING MODE
Pdesignc (EN 14825) kW - - - - - 324,8 365,2
SEER  (EN 14825) - - - - - 6,29 6,3
ηs,c % - - - - - 249 249
TXHETU MODEL SEASONAL PERFORMANCE IN HEATING MODE
Pdesignh (EN 14825) kW 239 280 318 356 396 - -
SCOP (EN 14825) 6,79 6,66 6,54 6,47 6,48 - -
ηs % 263 258 254 251 251 - -
TXHETY MODEL 4185 4210 4240 4275 4305 4350 4395
COOLING OPERATIONS (AUTOMATIC 1 MODE)
Nominal cooling capacity kW 184,6 211,6 238,4 266,2 293,9 333,1 373,8
Absorbed power kW 42,1 50,6 57,7 64,1 70,5 79,9 90,5
E.E.R. 4,38 4,18 4,13 4,15 4,17 4,17 4,13
COOLING OPERATIONS + TOTAL RECOVERY (AUTOMATIC 2 MODE)
Nominal cooling capacity kW 159,7 185,4 211 236,8 263,5 303,7 337,1
Recovery heating capacity kW 208,2 243,2 277,7 310 343,4 394,3 439,9
T.E.R. 7,27 7,07 7 7,11 7,19 7,32 7,15
HEATING OPERATIONS (MODE SELECT 1-2 AUTOMATIC 3)
Nominal heating capacity kW 205,5 240,6 274,3 306,7 340,2 389,7 435,7
Total absorbed power kW 52,2 62,8 72,2 79,7 87,9 99,2 113,5
C.O.P. 3,94 3,83 3,8 3,85 3,87 3,93 3,84
TXHETY MODEL 4185 4210 4240 4275 4305 4350 4395
Sound pressure dB(A) 47 47 48 49 51 52 53
Sound power dB(A) 79 79 80 81 83 84 85
Sound power with soundproofing set-up dB(A) 76,5 76,5 77,5 78,5 80,5 81,5 82,5
Scroll compressor/steps no. 4/4 4/4 4/4 4/4 4/4 4/4 4/4
Circuits no. 2 2 2 2 2 2 2
Electrical supply V-ph-Hz 400-3-50 400-3-50 400-3-50 400-3-50 400-3-50 400-3-50 400-3-50
DIMENSIONS AND WEIGHTS 4185 4210 4240 4275 4305 4350 4395
L – Width mm 2510 2510 2510 2510 2510 2510 2510
H – Height mm 1860 1860 1860 1860 1860 1860 1860
P – Depth mm 870 870 870 870 870 870 870
Weight kg 1205 1315 1455 1500 1520 1675 1770
SEASONAL ENERGY PERFORMANCE 4185 4210 4240 4275 4305 4350 4395
TXHETY MODEL SEASONAL PERFORMANCE IN COOLING MODE
Pdesignc (EN 14825) kW - - - - 293,9 333,1 373,8
SEER  (EN 14825) - - - - 6,21 6,2 6,23
ηs,c % - - - - 245 245 246
TXHETY MODEL SEASONAL PERFORMANCE IN HEATING MODE
Pdesignh (EN 14825) kW 246 287 327 365 - - -
SCOP (EN 14825) 6,74 6,58 6,47 6,44 - - -
ηs % 262 255 251 249 - - -
  • Data at the following conditions:
  • Chilled water (user): 12/7℃ – Condenser water (disposal unit-source): 30/35℃
  • Chilled water (user) outlet: 7℃, nominal flow rate – Condenser water outlet (recovery unit): 45℃, nominal flow rate.
  • Evaporator water (disposal-source): 10/7℃ – Hot water (utility): 40/45℃.
  • In open field (Q = 2) at 10 m from the unit.
  • Total sound power level in dB(A) based on measurements carried out in accordance with regulation UNI EN-ISO 9614.
  • Weight refers to the unit empty with soundproofing.
  • Performance according to EN 14511.
  • T.E.R.: Total efficiency ratio
  • Low temperature application (7°C)
  • Seasonal energy efficiency: low temperature cooling (EU Regulation 2016/2281)
  • In Average climatic conditions, low temperature application (35℃)
  • Seasonal energy efficiency: low temperature heating in Average climate (EU Regulations No.811/2013 and No.813/2013)

Manuals

To view all the documents, log in to the reserved area

Technical notes

To view all the documents, log in to the reserved area

Documents

To view all the documents, log in to the reserved area

Images

Format: TIF
Request information about this product









    Find an agent or a reseller.

    Find a reseller in your area for a customized offer on Rhoss air conditioning solutions.