WinPACK EXP
TXAEY 4150÷4340EXPsystems - Air cooled multi-purpose ecological system with axial fans. Range with scroll hermetic compressors and R410A refrigerant gas.
Key features
Multi-purpose units with TER up to 7,9
Integrated MASTER/SLAVE control
Description
Construction features
• Compressor: scroll type, rotary, hermetic complete with thermal protection and casing heater.
• 4 capacity steps with high efficiency at partial loads.
• Main and secondary heat exchangers: crossed flow stainless steel plate exchangers, complete with antifreeze heater, closed cell polyurethane foam rubber insulation and water flow differential pressure switch.
• Air side heat exchanger: finned coil with copper pipes and aluminium fins.
• Fan: external rotor axial type electric fans equipped with internal thermal protection and accident protection grilles. The electric fans are fitted with a proportional electronic device for continuous regulation of the rotation speed.
• Control: microprocessor electronic control with Adaptive Function Plus logic.
• Structure: made of galvanised and painted steel plate with polyester powder coating.
• The unit is also complete with:
- compressor and fan circuit breaker switches;
- electronic expansion valve;
- display of cooling circuit high/low pressure;
- master/slave control up to 4 units in parallel;
- clock board;
- control of Variable Primary Flow (VPF_R).
Versions
• T - High efficiency version.
• Q - Super silenced version complete with compressor technical compartment soundproofing and reduced speed fans.
Models
• TXAETY: EXPsystems unit.
• TXAEQY: super silenced EXPsystems unit.
• PUMP with single or double electric pump, one of which automatic in standby. The electric pumps are available in the low or high head versions.
• TANK&PUMP with 440 - 700 litre integrated buffer tank (depending on the sizes) and single or double electric pump, complete with expansion tank, air vent valves, safety valve and water side pressure gauge.
• Inverter pump control for unit start-up.
• Recovery side VPF_R control.
• Condensing control with fans with EC motor.
• Condensing control with over-pressure fans (T version only)
• Power factor correction capacitors (cosf > 0.94).
• Forced limit of power consumption.
• Forced noise limit.
• Energy parameter measuring device.
• Optimised energy efficiency.
• Soft starter.
• Technical compressor compartment soundproofing.
• Compressor soundproof enclosures.
• Cooling circuit outlet and inlet valves.
• Refrigerant leak detector.
• Cooling circuit high and low pressure gauges.
• Double safety valves.
• Metal filters or coil protection nets.
• Copper/copper or copper/pre-painted aluminium coils.
• Control of min/max power supply voltage.
• Digital input for double set-point.
• 4-20 mA analogue signal for shifting set-point.
• Electrical panel resistance, buffer tank, electric pumps, if present.
• Interfaces for serial communication with other devices.
• Anti-vibration mounts.
Separately supplied accessories
• Remote keypad with display.
• Rhoss supervisors for unit monitoring and remote management.
• Rhoss sequencer for integrated management of multiple chillers.
Technical data
TXAETY MODEL | 4150 | 4160 | 4190 | 4220 | 4240 | 4270 | 4300 | 4340 | ||||
COOLING OPERATIONS (AUTOMATIC 1 MODE) | ||||||||||||
❶ | Nominal cooling capacity | kW | 145,7 | 162,7 | 193,7 | 219,7 | 237,7 | 268,7 | 303,6 | 339,6 | ||
❶ | Absorbed power | kW | 49,4 | 56,5 | 65,9 | 77,4 | 85,8 | 94 | 105,4 | 120,4 | ||
❶ | E.E.R. | 2,95 | 2,88 | 2,94 | 2,84 | 2,77 | 2,86 | 2,88 | 2,82 | |||
COOLING OPERATIONS + TOTAL RECOVERY (AUTOMATIC 2 MODE) | ||||||||||||
❸ | Nominal cooling capacity | kW | 149,8 | 169,5 | 201,7 | 230,1 | 251,7 | 279,5 | 314,7 | 351,5 | ||
❸ | Recovery heating capacity | kW | 192,1 | 217,5 | 257,5 | 296,2 | 324,4 | 358,4 | 404,5 | 452,6 | ||
❸ | T.E.R. | 7,75 | 7,7 | 7,84 | 7,61 | 7,57 | 7,74 | 7,63 | 7,59 | |||
HEATING OPERATIONS (MODE SELECT 1-2 AUTOMATIC 3) | ||||||||||||
❷ | Nominal heating capacity | kW | 155,4 | 171,3 | 211,3 | 241,3 | 261,4 | 292,4 | 329,4 | 372,4 | ||
❷ | Absorbed power | kW | 48,1 | 53,4 | 66 | 74,9 | 81,4 | 91,4 | 102,3 | 116,4 | ||
❷ | C.O.P. | 3,23 | 3,21 | 3,2 | 3,22 | 3,21 | 3,2 | 3,22 | 3,2 | |||
TXAEQY MODEL | 4150 | 4160 | 4190 | 4220 | 4240 | 4270 | 4300 | 4340 | ||||
COOLING OPERATIONS (AUTOMATIC 1 MODE) | ||||||||||||
❶ | Nominal cooling capacity | kW | 137,7 | 152,7 | 183,7 | 206,7 | 225,7 | 258,7 | 288,6 | 327,6 | ||
❶ | Absorbed power | kW | 52,2 | 59 | 66,8 | 79,2 | 89,6 | 92,7 | 104,6 | 115,4 | ||
❶ | E.E.R. | 2,64 | 2,59 | 2,75 | 2,61 | 2,52 | 2,79 | 2,76 | 2,84 | |||
COOLING OPERATIONS + TOTAL RECOVERY (AUTOMATIC 2 MODE) | ||||||||||||
❸ | Nominal cooling capacity | kW | 150,3 | 169,9 | 202,3 | 230,7 | 252,3 | 280,2 | 315,4 | 352,3 | ||
❸ | Recovery heating capacity | kW | 192,5 | 217,9 | 258 | 296,8 | 324,9 | 358,9 | 405,1 | 453,2 | ||
❸ | T.E.R. | 7,81 | 7,74 | 7,9 | 7,65 | 7,6 | 7,77 | 7,68 | 7,63 | |||
HEATING OPERATIONS (MODE SELECT 1-2 AUTOMATIC 3) | ||||||||||||
❷ | Nominal heating capacity | kW | 150,3 | 167,3 | 202,3 | 231,3 | 251,3 | 279,4 | 316,4 | 357,4 | ||
❷ | Absorbed power | kW | 46,5 | 52,1 | 62,6 | 71,4 | 78 | 86,5 | 97,4 | 110 | ||
❷ | C.O.P. | 3,23 | 3,21 | 3,23 | 3,24 | 3,22 | 3,23 | 3,25 | 3,25 | |||
TXAETY-TXAEQY MODEL | 4150 | 4160 | 4190 | 4220 | 4240 | 4270 | 4300 | 4340 | ||||
❹ | TXAETY sound pressure | dB(A) | 54 | 55 | 57 | 57 | 58 | 60 | 61 | 62 | ||
❹ | TXAEQY sound pressure | dB(A) | 48 | 49 | 51 | 51 | 52 | 54 | 55 | 56 | ||
❺ | TXAETY sound power | dB(A) | 86 | 87 | 89 | 89 | 90 | 92 | 93 | 94 | ||
❺ | TXAEQY sound power | dB(A) | 80 | 81 | 83 | 83 | 84 | 86 | 87 | 88 | ||
Scroll compressors/steps | n. | 4/4 | 4/4 | 4/4 | 4/4 | 4/4 | 4/4 | 4/4 | 4/4 | |||
Circuits | n. | 2 | 2 | 2 | 2 | 2 | 2 | 2 | 2 | |||
Electrical supply | V-ph-Hz | 400-3-50 | 400-3-50 | 400-3-50 | 400-3-50 | 400-3-50 | 400-3-50 | 400-3-50 | 400-3-50 | |||
DIMENSIONS AND WEIGHTS | 4150 | 4160 | 4190 | 4220 | 4240 | 4270 | 4300 | 4340 | ||||
L – Width | mm | 3450 | 3450 | 4800 | 4800 | 4800 | 4800 | 5300 | 5300 | |||
H – Height | mm | 2000 | 2000 | 2030 | 2030 | 2030 | 2030 | 2030 | 2030 | |||
P – Depth | mm | 1520 | 1520 | 2090 | 2090 | 2090 | 2090 | 2090 | 2090 | |||
❻ | TXAETY weight | kg | 1670 | 1685 | 2405 | 2550 | 2610 | 2750 | 3030 | 3250 | ||
❻ | TXAEQY weight | kg | 1735 | 1750 | 2495 | 2640 | 2700 | 2840 | 3120 | 3340 | ||
SEASONAL ENERGY PERFORMANCE | 4150 | 4160 | 4190 | 4220 | 4240 | 4270 | 4300 | 4340 | ||||
TXAETY MODEL SEASONAL PERFORMANCE IN HEATING MODE | ||||||||||||
③ | Pdesignh (EN 14825) | kW | 136 | 152 | 187 | 213 | 232 | 259 | 292 | 331 | ||
③ | SCOP (EN 14825) | 3,61 | 3,59 | 3,57 | 3,59 | 3,55 | 3,53 | 3,57 | 3,49 | |||
④ | ηs | % | 141 | 141 | 140 | 141 | 139 | 138 | 140 | 137 | ||
TXAEQY MODEL SEASONAL PERFORMANCE IN HEATING MODE | ||||||||||||
③ | Pdesignh (EN 14825) | kW | 132 | 148 | 179 | 205 | 223 | 247 | 281 | 318 | ||
③ | SCOP (EN 14825) | 3,62 | 3,6 | 3,67 | 3,66 | 3,59 | 3,68 | 3,66 | 3,62 | |||
④ | ηs | % | 142 | 141 | 144 | 143 | 141 | 144 | 143 | 142 | ||
- Data at the following conditions:
- ❶ Air: 35°C – Water: 12/7°C.
- ❷ Air: 7°C D.B. – 6°C W.B. – Water: 40/45°C.
- ❸ Evaporator output water: 7℃, nominal flow rate. Recovery output water: 45°C, nominal flow rate.
- ❹ In open field (Q = 2) at 10 m from the unit.
- ❺ Total sound power level in dB(A) based on measurements carried out in accordance with regulation UNI EN-ISO 9614.
- ❻ Weight referred to the unit without load and not accessorised.
- Performance according to EN 14511.
- T.E.R.: Total efficiency ratio
- ③ In Average climatic conditions, low temperature application (35°C)
- ④ Seasonal energy efficiency: low temperature heating in Average climate (EU Regulations No.811/2013 and No.813/2013)
Manuals
To view all the documents, log in to the reserved area
Technical notes
To view all the documents, log in to the reserved area
Documents
To view all the documents, log in to the reserved area
Images
Request information about this product
Find a reseller in your area for a customized offer on Rhoss air conditioning solutions.