Cooling capacity 841,3÷1283,2 kW
Heating capacity 858,7÷1290,8 kW

EXPsystems - Air cooled multi-purpose ecological system with axial fans. Range with scroll hermetic compressors and R454B refrigerant gas.

Features

Key features


Multi-purpose units with TER up to 8,18

Extended operating limits

SEER up to 5,18 with FIEC accessory (EC fans) and SCOP up to 3,91

R454B eco-friendly gas


WinPOWER ECO EXP TWIN

Description

Construction features

• Compressor: scroll type, rotary, hermetic complete with thermal protection and casing heater.
• Up to 12 capacity steps with high efficiency at partial loads.
• Main and secondary heat exchangers: crossed flow stainless steel plate exchangers, complete with antifreeze heater, closed cell polyurethane foam rubber insulation and water flow differential pressure switch.
• Air side heat exchanger: finned coil with copper pipes and aluminium fins.
• Fan: external rotor axial type electric fans equipped with internal thermal protection, accident protection grilles and proportional electronic device for continuous fan rotation speed adjustment.
• Control: microprocessor electronic control with Adaptive Function Plus logic.
• Structure: load-bearing structure made of galvanised and painted steel plate with polyester powder coating.
• The unit is also complete with:
- fan and compressor thermal magnetic circuit breakers, heat exchanger antifreeze heater;
- display of cooling circuit high and low pressure;
- electronic expansion valve;
- clock board;
- control of Variable Primary Flow (VPF_R).

Versions

• T - High efficiency version.
• Q - Super silenced version complete with compressor technical compartment soundproofing and reduced speed fans.

Models

• TXAETU: EXPsystems unit.
• TXAEQU: super silenced EXPsystems unit.

Factory fitted accessories

• PUMP with single or double electric pump, one of which automatic in standby. The electric pumps are available in the main and secondary/recovery heat exchanger low or high head set-ups.
• Inverter pump control for unit start-up.
• Recovery side VPF_R control.
• Condensing control with fans with EC motor.
• Condensing control with over-pressure fans (T version only).
• Power factor correction capacitors (cosφ > 0.94).
• Forced limit of power consumption.
• Forced noise limit.
• Energy parameter measuring device.
• Soft starter.
• Compressor box and soundproofed cooling circuit.
• Compressor soundproof enclosures.
• Cooling circuit outlet valves.
• Refrigerant leak detector.
• Cooling circuit high and low pressure gauges.
• Double safety valves.
• Coil protection nets or buffer panels.
• Bottom compartment protection nets.
• Pre-painted copper/aluminium coils, copper/copper or with hydrophilic treatment.
• Digital input for double set-point.
• 4-20 mA analogue signal for shifting set-point.
• Electrical panel antifreeze heater, coil tanks and electric pumps, if applicable.
• Interfaces for serial communication with other devices.
• Colour touch user keypad (fitted on the machine or remotely) with 7” display.
• Spring anti-vibration mounts.
• Protective packaging.

Separately supplied accessories

• Remote keypad with display.
• Thermostat with display.
• Rhoss supervisors for unit monitoring and remote management.
• Rhoss sequencer for integrated management of multiple chillers.

Technical data

TXAETU MODEL 8900 10980 101040 101120 121200 121260 121320
COOLING OPERATIONS (AUTOMATIC 1 MODE)
Nominal cooling capacity kW 863,3 949,2 989,2 1085,1 1171,2 1223,2 1283,2
Absorbed power kW 276,7 304,2 320,1 351,2 368,3 387,1 407,4
E.E.R. 3,12 3,12 3,09 3,09 3,18 3,16 3,15
COOLING OPERATIONS + TOTAL RECOVERY (AUTOMATIC 2 MODE)
Nominal cooling capacity kW 861,7 923,9 964,3 1073,8 1150,6 1205,3 1279,1
Recovery heating capacity kW 1092,2 1179,8 1231,8 1363,6 1462,3 1529,2 1617
T.E.R. 8,05 7,79 7,77 7,93 7,95 8,03 8,14
HEATING OPERATIONS (MODE SELECT 1-2 AUTOMATIC 3)
Nominal heating capacity kW 870,7 964,8 1016,8 1088,9 1182,8 1246,8 1290,8
Absorbed power kW 267,9 293,3 310 333 360,6 381,3 394,7
C.O.P. 3,25 3,29 3,28 3,27 3,28 3,27 3,27
TXAEQU MODEL 8900 10980 101040 101120 121200 121260 121320
COOLING OPERATIONS (AUTOMATIC 1 MODE)
Nominal cooling capacity kW 841,3 927,3 965,2 1057,2 1145,2 1191,3 1249,2
Absorbed power kW 281,4 306 322,8 357,2 371,8 390,6 405,6
E.E.R. 2,99 3,03 2,99 2,96 3,08 3,05 3,08
COOLING OPERATIONS + TOTAL RECOVERY (AUTOMATIC 2 MODE)
Nominal cooling capacity kW 864,4 926,7 967,4 1077,1 1154 1209,1 1283,3
Recovery heating capacity kW 1094,7 1182,3 1234,7 1366,6 1465,4 1532,7 1620,8
T.E.R. 8,09 7,82 7,8 7,97 7,98 8,07 8,18
HEATING OPERATIONS (MODE SELECT 1-2 AUTOMATIC 3)
Nominal heating capacity kW 858,7 950,8 1000,8 1074,8 1164,8 1226,8 1272,8
Absorbed power kW 260,2 283,8 300,5 324,7 349,8 369,5 384,5
C.O.P. 3,3 3,35 3,33 3,31 3,33 3,32 3,31
TXAETU-TXAEQU MODEL 8900 10980 101040 101120 121200 121260 121320
TXAETU sound pressure dB(A) 66 67 67 67 68 68 69
TXAEQU sound pressure dB(A) 58 59 59 59 60 60 60
TXAETU sound power dB(A) 99 100 100 100 101 101 102
TXAEQU sound power dB(A) 91 92 92 92 93 93 93
Scroll compressors/steps n. 8/8 10/10 10/10 10/10 12/12 12/12 12/12
Circuits n. 4 4 4 4 4 4 4
Electrical supply V-ph-Hz 400-3-50 400-3-50 400-3-50 400-3-50 400-3-50 400-3-50 400-3-50
DIMENSIONS AND WEIGHTS 8900 10980 101040 101120 121200 121260 121320
L – Width mm 9400 11600 11600 11600 13330 13330 13330
H – Height mm 2480 2480 2480 2480 2530 2530 2530
P – Depth mm 2260 2260 2260 2260 2260 2260 2260
TXAETU weight kg 7640 9070 9210 9270 11070 11220 11280
TXAEQU weight kg 8520 10080 10220 10280 12320 12490 12550
SEASONAL ENERGY PERFORMANCE 8900 10980 101040 101120 121200 121260 121320
TXAETU MODEL SEASONAL PERFORMANCE IN COOLING MODE
Pdesignc (EN 14825) kW 863,3 949,2 989,2 1085,1 1171,2 1223,2 1283,2
SEER  (EN 14825) 4,75 4,84 4,75 4,73 4,9 4,88 4,82
ηs,c % 187 191 187 186 193 192 190
TXAEQU MODEL SEASONAL PERFORMANCE IN COOLING MODE
Pdesignc (EN 14825) kW 841,3 927,3 965,2 1057,2 1145,2 1191,3 1249,2
SEER  (EN 14825) 4,74 4,82 4,71 4,7 4,88 4,85 4,79
ηs,c % 186 190 186 185 192 191 189
  • Data at the following conditions:
  • Air: 35°C – Water: 12/7°C.
  • Air: 7°C D.B. – 6°C W.B. – Water: 40/45°C.
  • Evaporator output water: 7℃, nominal flow rate. Recovery output water: 45°C, nominal flow rate.
  • In open field (Q = 2) at 10 m from the unit.
  • Total sound power level in dB(A) based on measurements carried out in accordance with regulation UNI EN-ISO 9614.
  • Weight refers to the unit without load.
  • Performance according to EN 14511.
  • T.E.R.: Total efficiency ratio
  • Low temperature application (7°C)
  • Seasonal energy efficiency: low temperature cooling (EU Regulation 2016/2281)

Manuals

To view all the documents, log in to the reserved area

Technical notes

To view all the documents, log in to the reserved area

Documents

To view all the documents, log in to the reserved area

Images

Format: TIF
Request information about this product









    Find an agent or a reseller.

    Find a reseller in your area for a customized offer on Rhoss air conditioning solutions.