New
Web code: PKI07
CHILLERS HEAT PUMPS AIR-cooled AXIAL fans

POKER-PI

THAITP 150
Cooling capacity 41,8÷166,3 kW
Heating capacity 47,5÷190,9 kW

Modular reversible heat pumps for high temperature water production, air cooled with axial fans. Range with scroll hermetic compressors, DC inverter and R290 refrigerant gas.

Features

Key features


Efficient and eco-friendly range in R290

Modular range: up to 4 units may be combined

Total system redundancy with multiple modules installed

Cascade management including DHW with multiple modules installed

Hot water production from -20°C to 40°C outdoor air

Temperature of the produced water up to 80°C


POKER-PI

Description

Construction features

• Compressor: rotary hermetic, scroll type with Inverter actuation, complete with thermal protection and casing heater.
• Water side heat exchanger: adequately insulated stainless steel plates, complete with water flow differential pressure switch.
• Air side heat exchanger: finned coil heat exchanger, with copper pipes and aluminium fins with hydrophilic treatment.
• Fan: external rotor helical type electric fan and permanent magnet motor (EC brushless) for electronic speed control, equipped with internal thermal protection and accident protection grilles.
• Control: microprocessor electronic control with Adaptive Function Plus logic.
• Structure: suitably sound-proofed, galvanised and painted steel plate, complete with antifreeze heater on the condensate drain pan.
• Refrigerant leak detector.
• Metal filters or coil protection nets.
• The unit is also complete with:
- fan circuit breaker switches;
- electronic expansion valve;
- outdoor air temperature probe for set-point compensation;
- display of cooling circuit high and low pressure;
- clock board;
- automatic management of anti-legionella cycles.

Version

T - High efficiency/temperature version.

Set ups

• PUMP P1 - Unit complete with: electric circulation pump and manual air vent valve.
• PUMP P1 V3V - Unit complete with: electric circulation pump, manual air vent valve, 3-way diverter valve for the production of domestic hot water.

Factory fitted accessories

• Forced Download. Compressor partialisation or switch-off to limit power and current consumption (digital input).
• Desuperheater.
• Set up with oversized head pump.
• Condensing control with over-pressure fans
• Forced limit of power consumption.
• Unit with copper/pre-painted aluminium or copper/copper condensation coils.
• Flow switch and hot wire heaters protecting pump and piping down to -20°C outdoor air.
• Silenced set up (muffled compressors).
• Digital input for double set-point.
• 4-20 mA analogue signal for shifting set-point.
• Contacts for Smart Grid integration and photovoltaic system.
• Energy parameter measuring device.
• Double safety valves.
• Control of min/max power supply voltage.
• Low temperature water production.
• Interfaces for serial communication with other devices.
• Rubber anti-vibration mounts.

Separately supplied accessories

• Rubber anti-vibration mounts.
• Water filter and valves.
• 3-way diverter valve to manage the production of domestic hot water complete with protective casing and hoses for machine connection. For downstream installation of the group of machines. Not compatible with PUMP V3V set up.
• Additional electrical resistance for heat pump managed by regulation.
• Interfaces for serial communication with other devices.
• Serial converter (RS485/USB).
• Rhoss supervisors for unit monitoring and remote management.
• Rhoss sequencer for integrated management of multiple chillers.
• Remote keypad with display.
• Thermostat with display.

Technical data

THAITP MODEL 150
1 mod. 2 mod. 3 mod. 4 mod.
Nominal heating capacity kW 47,5 95,3 143,1 190,9
C.O.P. 3,1 3,1 3,1 3,1
Nominal cooling capacity kW 41,8 83,3 124,8 166,3
E.E.R. 2,45 2,45 2,45 2,45
Absorbed power kW 15,3 30,7 46,2 61,6
Sound pressure dB(A) 47,5 50 51,5 53
Sound power dB(A) 79 82 84 85
Scroll compressors/steps n. 1 inverter 2 inverter 3 inverter 4 inverter
Circuits n. 1 2 3 4
Standard electric pump nominal available head kPa 131 131 131 131
Electrical supply V-ph-Hz 400-3-50 400-3-50 400-3-50 400-3-50
DIMENSIONS AND WEIGHTS 1 mod. 2 mod. 3 mod. 4 mod.
L – Width mm 1224 2458 3692 4926
H – Height mm 2335 2335 2335 2335
P – Depth mm 1320 1320 1320 1320
Weight kg 635 1270 1905 2540
SEASONAL ENERGY PERFORMANCE 150
1 mod. 2 mod. 3 mod. 4 mod.
THAITP MODEL SEASONAL PERFORMANCE IN HEATING MODE – Low temperature application 35°C
Pdesignh (EN 14825) kW 39 79 118 158
SCOP (EN 14825) 4,08 4,34 4,46 4,52
ηs % 160 171 176 178
Energy class A++ - - -
THAITP MODEL SEASONAL PERFORMANCE IN HEATING MODE – Medium temperature application 55°C
Pdesignh (EN 14825) kW 38 77 115 154
SCOP (EN 14825) 3,4 3,6 3,69 3,72
ηs % 133 141 144 146
Energy class A++ - - -
  • Data at the following conditions:
  • Air: 35°C – Water: 12/7°C
  • Air: 7°C, D.B. – 6°C W.B.- Water: 40/45°C.
  • In open field (Q = 2) at 10 m from the unit.
  • Total sound power level in dB(A) based on measurements carried out in accordance with regulation UNI EN-ISO 9614.
  • Weight refers to P1 setup.
  • Performance according to EN 14511. P1 setup.
  • In Average climatic conditions
  • Seasonal energy efficiency: heating in Average climate (EU Regulations No.811/2013 and No.813/2013)

Manuals

To view all the documents, log in to the reserved area

Technical notes

To view all the documents, log in to the reserved area

Documents

To view all the documents, log in to the reserved area

Images

Format: TIF
Request information about this product









    Find an agent or a reseller.

    Find a reseller in your area for a customized offer on Rhoss air conditioning solutions.