New
Web code: MDI07
CHILLERS HEAT PUMPS AIR-cooled AXIAL fans

MidiPACK-PI

THAITP 120-135
Cooling capacity 18,7÷28,9 kW
Heating capacity 20,8÷34,8 kW

Reversible heat pumps for high temperature water production, air cooled with axial fans.
Range with scroll hermetic compressors, DC inverter and R290 refrigerant gas.

Features

Key features


Efficient and eco-friendly range in R290

Plug&Play unit with integrated hydraulic module

Full inverter units

Hot water production from -20°C to 40°C outdoor air

Temperature of the produced water up to 80°C

Integrated MASTER/SLAVE control


MidiPACK-PI

Description

Construction features

• Compressor: hermetic rotary, scroll type with inverter actuation, complete with thermal protection and casing heater.
• Water side heat exchanger: adequately insulated stainless steel plates, complete with water flow differential pressure switch.
• Air side heat exchanger: finned coil heat exchanger, with copper pipes and aluminium fins with hydrophilic treatment.
• Fan: external rotor helical type electric fan and permanent magnet motor (EC brushless) for electronic speed control, equipped with internal thermal protection.
• Control: microprocessor electronic control with Adaptive Function Plus logic.
• Structure: suitably sound-proofed, galvanised and painted steel plate, complete with antifreeze heater on the condensate drain pan.
• The unit is also complete with:
- electronic expansion valve;
- outdoor air temperature probe for set-point compensation;
- display of cooling circuit high and low pressure;
- clock board;
- automatic management of anti-legionella cycles.

Version

T - High efficiency/temperature version.

PUMP set-up

• Pump unit complete with: EC circulator with continuous speed regulation, manual air vent valve, safety valve and automatic deareator.

Factory fitted accessories

• Forced limit of power consumption.
• Unit with copper/pre-painted aluminium or copper/copper condensation coils.
• Hot wire heaters protecting pump and piping down to -20°C outdoor air.
• Silenced set up (muffled compressors).
• Digital input for double set-point.
• 4-20 mA analogue signal for shifting set-point.
• Contacts for Smart Grid integration and photovoltaic system.
• Energy parameter measuring device.
• Low temperature water production.
• Interfaces for serial communication with other devices.

Separately supplied accessories

• Inertial storage tank, energy class C (class between F and A+).
• Buffer tank antifreeze heater.
• 3-way valve for the production of domestic hot water, managed by the adjustment.
• Remotable outdoor air temperature probe for compensation of the set-point.
• Additional electrical resistance for heat pump, managed by the adjustment.
• Rubber anti-vibration mounts.
• Water filter.
• Thermostat with display.
• Remote keypad with display.
• Interfaces for serial communication with other devices.
• Serial converter (RS485/USB).
• Rhoss supervisors for unit monitoring and remote management.

Technical data

THAITP MODEL 120 125 130 135
Heating capacity kW 20,8 25,1 30,5 34,9
Absorbed power kW 5,76 7,56 8,69 10,58
C.O.P. 3,61 3,32 3,51 3,3
Heating capacity kW 21,3 25,5 31,1 35,5
Absorbed power kW 4,80 6,28 7,23 8,83
C.O.P. 4,44 4,06 4,3 4,02
Cooling capacity kW 18,7 22,3 25,8 28,9
Absorbed power kW 5,77 7,88 8,54 10,59
E.E.R. 3,24 2,83 3,02 2,73
Cooling capacity kW 25,2 30,1 35,2 39,5
Absorbed power kW 6,10 8,50 8,87 11,06
E.E.R. 4,13 3,54 3,97 3,57
Sound pressure dB(A) 46,0 48,0 48,5 49,5
Scroll compressor no. 1 inverter 1 inverter 1 inverter 1 inverter
Circuits no. 1 1 1 1
Available circulator head kPa 81 60 59 41
KAI Buffer tank water content l 150 150 150 150
Electrical supply V-ph-Hz 400-3+N-50 400-3+N-50 400-3+N-50 400-3+N-50
DIMENSIONS AND WEIGHTS 120 125 130 135
L – THAITP width mm 1635 1635 1635 1635
H – THAITP height mm 1290 1290 1670 1670
P – THAITP Depth mm 600 600 600 600
THAITP weight kg 260 260 330 330
L – THAITP+KAI width mm 1740 1740 1740 1740
H – THAITP+KAI height mm 1795 1795 2175 2175
P – THAITP+KAI Depth mm 730 730 730 730
THAITP+KAI weight kg 360 360 430 430
SEASONAL ENERGY PERFORMANCE 120 125 130 135
THAITP MODEL SEASONAL PERFORMANCE IN HEATING MODE – Low temperature application 35°C
Pdesignh (EN 14825) kW 20 23 28 31
SCOP (EN 14825) 4,54 4,5 4,7 4,69
ηs % 178 177 185 185
Energy class A+++ A+++ A+++ A+++
THAITP MODEL SEASONAL PERFORMANCE IN HEATING MODE – Medium temperature application 55°C
Pdesignh (EN 14825) kW 20 23 27 30
SCOP (EN 14825) 3,67 3,61 3,8 3,78
ηs % 144 141 149 148
Energy class A++ A++ A++ A++
  • Data at the following conditions:
  • Air: 7°C D.B. – 6°C W.B. – Water: 40/45°C.
  • Air: 7°C D.B. – 6°C W.B. – Water: 30/35°C.
  • Air: 35°C D.B. – Water: 12/7°C.
  • Air: 35°C D.B. – Water: 23/18°C.
  • In open field (Q = 2) at 5 m from the unit.
  • Weight referred to the unit without load and not accessorised.
  • Performance according to EN 14511
  • In Average climatic conditions.
  • Seasonal energy efficiency: ambient heating in Average climate (EU Regulations No.811/2013 and No.813/2013 – class between D and A+++)

Manuals

To view all the documents, log in to the reserved area

Technical notes

To view all the documents, log in to the reserved area

Documents

To view all the documents, log in to the reserved area

Images

Format: TIF
Request information about this product









    Find an agent or a reseller.

    Find a reseller in your area for a customized offer on Rhoss air conditioning solutions.