MidiPACK-PI
THAITP 120-135Reversible heat pumps for high temperature water production, air cooled with axial fans.
Range with scroll hermetic compressors, DC inverter and R290 refrigerant gas.
Key features
Efficient and eco-friendly range in R290
Plug&Play unit with integrated hydraulic module
Full inverter units
Hot water production from -20°C to 40°C outdoor air
Temperature of the produced water up to 80°C
Integrated MASTER/SLAVE control
Description
Construction features
• Compressor: hermetic rotary, scroll type with inverter actuation, complete with thermal protection and casing heater.
• Water side heat exchanger: adequately insulated stainless steel plates, complete with water flow differential pressure switch.
• Air side heat exchanger: finned coil heat exchanger, with copper pipes and aluminium fins with hydrophilic treatment.
• Fan: external rotor helical type electric fan and permanent magnet motor (EC brushless) for electronic speed control, equipped with internal thermal protection.
• Control: microprocessor electronic control with Adaptive Function Plus logic.
• Structure: suitably sound-proofed, galvanised and painted steel plate, complete with antifreeze heater on the condensate drain pan.
• The unit is also complete with:
- electronic expansion valve;
- outdoor air temperature probe for set-point compensation;
- display of cooling circuit high and low pressure;
- clock board;
- automatic management of anti-legionella cycles.
Version
T - High efficiency/temperature version.
PUMP set-up
• Pump unit complete with: EC circulator with continuous speed regulation, manual air vent valve, safety valve and automatic deareator.
Factory fitted accessories
• Forced limit of power consumption.
• Unit with copper/pre-painted aluminium or copper/copper condensation coils.
• Hot wire heaters protecting pump and piping down to -20°C outdoor air.
• Silenced set up (muffled compressors).
• Digital input for double set-point.
• 4-20 mA analogue signal for shifting set-point.
• Contacts for Smart Grid integration and photovoltaic system.
• Energy parameter measuring device.
• Low temperature water production.
• Interfaces for serial communication with other devices.
Separately supplied accessories
• Inertial storage tank, energy class C (class between F and A+).
• Buffer tank antifreeze heater.
• 3-way valve for the production of domestic hot water, managed by the adjustment.
• Remotable outdoor air temperature probe for compensation of the set-point.
• Additional electrical resistance for heat pump, managed by the adjustment.
• Rubber anti-vibration mounts.
• Water filter.
• Thermostat with display.
• Remote keypad with display.
• Interfaces for serial communication with other devices.
• Serial converter (RS485/USB).
• Rhoss supervisors for unit monitoring and remote management.
Technical data
THAITP MODEL | 120 | 125 | 130 | 135 | ||||
❶ | Heating capacity | kW | 20,8 | 25,1 | 30,5 | 34,9 | ||
❶ | Absorbed power | kW | 5,76 | 7,56 | 8,69 | 10,58 | ||
❶ | C.O.P. | 3,61 | 3,32 | 3,51 | 3,3 | |||
❷ | Heating capacity | kW | 21,3 | 25,5 | 31,1 | 35,5 | ||
❷ | Absorbed power | kW | 4,80 | 6,28 | 7,23 | 8,83 | ||
❷ | C.O.P. | 4,44 | 4,06 | 4,3 | 4,02 | |||
❸ | Cooling capacity | kW | 18,7 | 22,3 | 25,8 | 28,9 | ||
❸ | Absorbed power | kW | 5,77 | 7,88 | 8,54 | 10,59 | ||
❸ | E.E.R. | 3,24 | 2,83 | 3,02 | 2,73 | |||
❹ | Cooling capacity | kW | 25,2 | 30,1 | 35,2 | 39,5 | ||
❹ | Absorbed power | kW | 6,10 | 8,50 | 8,87 | 11,06 | ||
❹ | E.E.R. | 4,13 | 3,54 | 3,97 | 3,57 | |||
❺ | Sound pressure | dB(A) | 46,0 | 48,0 | 48,5 | 49,5 | ||
Scroll compressor | no. | 1 inverter | 1 inverter | 1 inverter | 1 inverter | |||
Circuits | no. | 1 | 1 | 1 | 1 | |||
❸ | Available circulator head | kPa | 81 | 60 | 59 | 41 | ||
KAI Buffer tank water content | l | 150 | 150 | 150 | 150 | |||
Electrical supply | V-ph-Hz | 400-3+N-50 | 400-3+N-50 | 400-3+N-50 | 400-3+N-50 | |||
DIMENSIONS AND WEIGHTS | 120 | 125 | 130 | 135 | ||||
L – THAITP width | mm | 1635 | 1635 | 1635 | 1635 | |||
H – THAITP height | mm | 1290 | 1290 | 1670 | 1670 | |||
P – THAITP Depth | mm | 600 | 600 | 600 | 600 | |||
❻ | THAITP weight | kg | 260 | 260 | 330 | 330 | ||
L – THAITP+KAI width | mm | 1740 | 1740 | 1740 | 1740 | |||
H – THAITP+KAI height | mm | 1795 | 1795 | 2175 | 2175 | |||
P – THAITP+KAI Depth | mm | 730 | 730 | 730 | 730 | |||
❻ | THAITP+KAI weight | kg | 360 | 360 | 430 | 430 | ||
SEASONAL ENERGY PERFORMANCE | 120 | 125 | 130 | 135 | ||||
THAITP MODEL SEASONAL PERFORMANCE IN HEATING MODE – Low temperature application 35°C | ||||||||
③ | Pdesignh (EN 14825) | kW | 20 | 23 | 28 | 31 | ||
③ | SCOP (EN 14825) | 4,54 | 4,5 | 4,7 | 4,69 | |||
④ | ηs | % | 178 | 177 | 185 | 185 | ||
④ | Energy class | A+++ | A+++ | A+++ | A+++ | |||
THAITP MODEL SEASONAL PERFORMANCE IN HEATING MODE – Medium temperature application 55°C | ||||||||
③ | Pdesignh (EN 14825) | kW | 20 | 23 | 27 | 30 | ||
③ | SCOP (EN 14825) | 3,67 | 3,61 | 3,8 | 3,78 | |||
④ | ηs | % | 144 | 141 | 149 | 148 | ||
④ | Energy class | A++ | A++ | A++ | A++ | |||
- Data at the following conditions:
- ❶ Air: 7°C D.B. – 6°C W.B. – Water: 40/45°C.
- ❷ Air: 7°C D.B. – 6°C W.B. – Water: 30/35°C.
- ❸ Air: 35°C D.B. – Water: 12/7°C.
- ❹ Air: 35°C D.B. – Water: 23/18°C.
- ❺ In open field (Q = 2) at 5 m from the unit.
- ❻ Weight referred to the unit without load and not accessorised.
- Performance according to EN 14511
- ③ In Average climatic conditions.
- ④ Seasonal energy efficiency: ambient heating in Average climate (EU Regulations No.811/2013 and No.813/2013 – class between D and A+++)
Manuals
To view all the documents, log in to the reserved area
Technical notes
To view all the documents, log in to the reserved area
Documents
To view all the documents, log in to the reserved area
Images

Request information about this product
Find a reseller in your area for a customized offer on Rhoss air conditioning solutions.