New
Web code: EEM01
CHILLERS HEAT PUMPS AIR-cooled AXIAL fans

ElectaMAXI-ECO

THAITI 118÷130
Cooling capacity 17-29.5 kW
Heating capacity 18-30kW

Packaged reversible air-cooled heat pumps with axial fans. Range with hermetic rotary DC Inverter compressors and R32 refrigerant gas.

Features

Key features


Low GWP R32 refrigerant

Energy class A+++

Temperature of the produced water up to 60°C

Domestic hot water production from –25°C to +43°C outdoor air

Standard control panel

3-way diverter valve management for DHW

Secondary circuit management with 2 zones, high and low temperature

Integrated MASTER/SLAVE management of up to 6 units

Accessory inertial tank under unit


ElectaMAXI-ECO

Description

Construction features

• Compressor: twin rotary type, rotary, hermetic with Inverter actuation, complete with thermal protection and casing heater.
• Electronic expansion valve.
• Water side heat exchanger: adequately insulated stainless steel plates, complete with antifreeze heater and water flow differential pressure switch.
• Air side heat exchanger: finned coil heat exchanger, with copper pipes and aluminium fins with Blue Fin anti-corrosion hydrophilic treatment.
• Fan: axial type electric fans with DC brushless motor, equipped with internal thermal protection, accident protection grilles and continuous fan rotation speed adjustment.
• Structure: made of galvanised and painted steel plate Pantone Warm Grey 2C, complete with condensate drain pan and ducted condensate drains.
• Control: microprocessor electronic control with remote control panel with display (50 m distance max), for integrated management of the heat pump and the heating system, according to the various requirements relating to the use of the energy sources.
- 3-way diverter valve management and electrical resistance for domestic hot water production.
- Rapid heating function for domestic hot water.
- Anti-legionella cycle function, with timer and electric heater.
- Auxiliary or supplementary heat source management.
- Management of water or room air temperature via air temperature probe in the control panel.
- Secondary circuit management with 2 zones, high and low temperature with mixing valve and room thermostats.
- On/off valve management for shutting off a part of the system, in heating or cooling mode.
- Management of one or two booster pumps, DHW recirculation pump and solar pump.
- Management of solar thermal enabling or solar panel probe.
- Master/slave management of up to 6 units in parallel.
- Smart Grid function for photovoltaic panels.
- Operation in silent mode, with two levels, with timer.
- Weekly and daily time bands.
- Holiday mode and system antifreeze function with heating cable.
- Power consumption limiting function.
- Unit activation by external contact (remote ON/OFF), alarm/operation output signal.
- Parental control and start-up menu password.
• The unit is also complete with:
- Outdoor air temperature probe for compensation of the Set-point.
- Supplied water temperature probe (10 m) for domestic hot water storage.
• RS485 interface for serial communication with other devices (Modbus RTU protocol).

Models

• THAITI: heat pump unit.

PUMP set up

• P0 - Pump unit complete with: EC circulator with 3-speed selector switch, membrane expansion tank, automatic air vent valve, safety valve, pressure gauge, water filter, flow switch.

Separately supplied accessories

KAI-110 - Inertial storage tank, with function of thermal flywheel or hydraulic separator, for outdoor installation below ElectaMAXI-ECO unit; 37 W leakage losses, energy class A.
KTAI-110 - Connection pipe between ElectaMAXI-ECO unit and KAI-110 tank.
KSA - Rubber anti-vibration mounts (for ElectaMAXI-ECO without tank KAI-110)
KVDEV - 3-way valve for the production of domestic hot water, managed by the adjustment.
KRIT - Supplementary electrical resistance.
KWTS - Additional water temperature probe (10 m) can be used for: mixed water secondary circuit, hydraulic separator for master/slave function, auxiliary or supplementary heat source, thermal solar.

Technical data

THAITI MODEL 118 122 126 130
Heating capacity kW 18,0 22,0 26,0 30,0
Absorbed power kW 5,14 6,47 8,39 10,34
C.O.P. 3,50 3,40 3,10 2,90
Heating capacity kW 18,0 22,0 26,0 30,1
Absorbed power kW 3,83 5,00 6,37 7,70
C.O.P. 4,70 4,40 4,08 3,91
Cooling capacity kW 17,0 21,0 26,0 29,5
Absorbed power kW 5,57 7,12 9,63 11,57
E.E.R. 3,05 2,95 2,7 2,55
Cooling capacity kW 18,5 23,0 27,0 31,0
Absorbed power kW 3,89 5,00 6,28 7,75
E.E.R. 4,75 4,60 4,30 4,00
Sound pressure dB(A) 56 58 60 62
Available circulator head kPa 102 95 78 61
KAI Buffer tank water content l 118 118 118 118
Electrical supply V-ph-Hz 400-3+N-50 400-3+N-50 400-3+N-50 400-3+N-50
DIMENSIONS AND WEIGHTS 118 122 126 130
L – THAITI width mm 1129 1129 1129 1129
H – THAITI height mm 1558 1558 1558 1558
P – THAITI Depth mm 528 528 528 528
THAITI weight kg 177 177 177 177
L – THAITI+KAI width mm 1333 1333 1333 1333
H – THAITI+KAI height mm 2178 2178 2178 2178
P – THAITI+KAI Depth mm 590 590 590 590
THAITI+KAI weight kg 242 242 242 242
SEASONAL ENERGY PERFORMANCE 118 122 126 130
THAITI MODEL SEASONAL PERFORMANCE IN HEATING MODE – Low temperature application 35°C
Pdesignh (EN 14825) kW 18 22 25 29
SCOP (EN 14825) 4,60 4,53 4,50 4,20
ηs % 181 178 177 165
Energy class A+++ A+++ A+++ A++
THAITI MODEL SEASONAL PERFORMANCE IN HEATING MODE – Medium temperature application 55°C
Pdesignh (EN 14825) kW 18 22 26 30
SCOP (EN 14825) 3,20 3,23 3,15 3,15
ηs % 125 126 123 123
Energy class A++ A++ A+ A+
  • Data at the following conditions:
  • Air: 7°C D.B. – 6°C W.B. – Water: 40/45°C.
  • Air: 7°C D.B. – 6°C W.B. – Water: 30/35°C.
  • Air: 35°C D.B. – Water: 12/7°C.
  • Air: 35°C D.B. – Water: 23/18°C.
  • In open field (Q = 2) at 5 m from the unit.
  • Weight refers to the most complete set up.
  • Performance according to EN 14511
  • In Average climatic conditions.
  • Seasonal energy efficiency: ambient heating in Average climate (EU Regulations No.811/2013 and No.813/2013)

Manuals

To view all the documents, log in to the reserved area

Technical notes

To view all the documents, log in to the reserved area

Documents

To view all the documents, log in to the reserved area

Images

Format: TIF
Request information about this product









    Find an agent or a reseller.