Compact-Y SM
THAEY 122÷130Packaged reversible air-cooled heat pumps with axial fans. Range with scroll hermetic compressors and R410A refrigerant gas.
Key features
Plug&Play unit with integrated hydraulic module
Integrated MASTER/SLAVE control
Description
Construction features
• Compressor: hermetic, rotary scroll compressor, complete with thermal protection and casing heater for mod. 127-130.
• Water side heat exchanger: adequately insulated stainless steel plates, complete with antifreeze heater and water flow differential pressure switch.
• Air side heat exchanger: finned coil with copper pipes and aluminium fins, complete with protection grilles.
• Fan: external rotor axial type electric fans equipped with internal thermal protection and accident protection grilles.
• Control: microprocessor electronic control with Adaptive Function Plus logic.
• Structure: in galvanised and painted steel plate, complete with condensate drain pan.
• The unit is also complete with:
- outdoor air temperature probe for compensation of the Set-point;
- display of cooling circuit high and low pressure;
- Master/Slave control up to 4 units in parallel;
- clock board.
Models
• THAEY: heat pump unit.
PUMP set-up
• Pump unit complete with: circulator or electric circulation pump, membrane expansion tank, manual air vent valve, safety valve and pressure gauge.
TANK & PUMP set up
• Pump unit complete with: inertial buffer tank, circulator or electric circulation pump, membrane expansion tank, manual air vent valve, automatic air vent valve, safety valve, and pressure gauge.
Factory fitted accessories
• Soft-start device.
• Silenced set up.
• Condensing control.
• Antifreeze heater on the buffer tank.
• Compressor casing heater (mod. 122).
• Unit base antifreeze heater for operation in heat pump mode at low outdoor air temperatures.
• Digital input for double set-point
• 4-20 mA analogue signal for shifting set-point.
• Low water set-point temperature.
• Pre-painted copper/coils or copper/copper coils.
Separately supplied accessories
• Rubber anti-vibration mounts.
• Condensing control.
• Water filter.
• 3-way valve for the production of domestic hot water.
• Outdoor air temperature probe for set-point compensation.
• Additional electrical resistance for heat pump, managed by regulation.
• Remote keypad with display.
• Interfaces for serial communication with other devices.
• Serial converter (RS485/USB).
• Rhoss supervisors for unit monitoring and remote management.
Technical data
THAEY MODEL | 122 | 127 | 130 | ||||
❶ | Heating capacity | kW | 23,5 | 30,3 | 34 | ||
❶ | Absorbed power | kW | 7,94 | 10,13 | 11,26 | ||
❶ | C.O.P. | 2,96 | 2,99 | 3,02 | |||
❷ | Heating capacity | kW | 24 | 30,9 | 34,5 | ||
❷ | C.O.P. | 3,75 | 3,74 | 3,72 | |||
❸ | Cooling capacity | kW | 22,7 | 26,7 | 29 | ||
❸ | Absorbed power | kW | 7,99 | 10,23 | 11,84 | ||
❸ | E.E.R. | 2,84 | 2,61 | 2,45 | |||
❹ | Sound pressure | dB(A) | 52 | 53 | 53 | ||
❹ | Silenced setup sound pressure | dB(A) | 49 | 50 | 50 | ||
Scroll compressors/steps | n. | 1/1 | 1/1 | 1/1 | |||
Circuits | no. | 1 | 1 | 1 | |||
Buffer tank water content | l | 45 | 45 | 45 | |||
❸ | Circulator/standard electric pump nominal available head | kPa | 65/131 | 64/121 | 55/112 | ||
Electrical supply | V-ph-Hz | 400-3+N-50 | 400-3+N-50 | 400-3+N-50 | |||
DIMENSIONS AND WEIGHT | 122 | 127 | 130 | ||||
L – PUMP width | mm | 1230 | 1535 | 1535 | |||
W – TANK & PUMP width | mm | 1522 | 1822 | 1822 | |||
H – Height | mm | 1280 | 1510 | 1510 | |||
P – Depth | mm | 600 | 695 | 695 | |||
❺ | THAEY weight | kg | 278 | 350 | 380 | ||
SEASONAL ENERGY PERFORMANCE | 122 | 127 | 130 | ||||
THAEY MODEL SEASONAL PERFORMANCE IN HEATING MODE | |||||||
③ | Pdesignh (EN 14825) | kW | 24 | 32 | 36 | ||
③ | SCOP (EN 14825) | 3,21 | 3,21 | 3,2 | |||
④ | ηs | % | 125 | 125 | 125 | ||
④ | Energy class | A+ | A+ | A+ | |||
- Data at the following conditions:
- ❶ Air: 7°C D.B. – 6°C W.B. – Water: 40/45°C.
- ❷ Air: 7°C D.B. – 6°C W.B. – Water: 30/35°C.
- ❸ Air: 35°C – Water: 12/7°C.
- ❹ In open field (Q = 2) at 5 m from the unit.
- ❺ Weight refers to the most complete setup.
- Performance according to EN 14511. Setup with electric pump.
- ③ In Average climatic conditions, low temperature application (35°C)
- ④ Seasonal energy efficiency: low temperature heating in Average climate (EU Regulations No.811/2013 and No.813/2013)
Manuals
To view all the documents, log in to the reserved area
Technical notes
To view all the documents, log in to the reserved area
Documents
To view all the documents, log in to the reserved area
Images
Request information about this product
Find a reseller in your area for a customized offer on Rhoss air conditioning solutions.