Web code: PK001
CHILLERS HEAT PUMPS AIR-cooled AXIAL fans

POKER

THAETY 234 H.T.
Cooling capacity 28,8÷115,2 kW
Heating capacity 33,8÷135,2 kW

Modular reversible heat pumps for high temperature water production, air cooled with axial fans. Range with scroll hermetic compressors and R410A refrigerant gas.

Features

Tax incentives*

Key features

Modular range: up to 4 units may be combined
Total system redundancy with multiple modules installed
Cascade management including DHW with multiple modules installed
Hot water production from -20°C to 40°C outdoor air
Temperature of the produced water up to 60°C

POKER

Description

Construction features

• Compressors: hermetic scroll type rotary compressors with steam injection, thermal protection and casing heater.
• Water side heat exchanger: adequately insulated stainless steel plates, complete with antifreeze heater and water flow differential pressure switch.
• Air side heat exchanger: finned coil heat exchanger, with copper pipes and aluminium fins with hydrophilic treatment.
• Fan: external rotor helical type electric fan and permanent magnet motor (EC brushless) for electronic speed control, equipped with internal thermal protection and accident protection grilles.
• Control: microprocessor electronic control with Adaptive Function Plus logic.
• Structure: suitably sound-proofed, galvanised and painted steel plate, complete with antifreeze heater on the condensate drain pan.
• The unit is also complete with:
- outdoor air temperature probe for set-point compensation;
- display of cooling circuit high and low pressure;
- clock board.

Version

T - High efficiency/temperature version.

Set ups

• PUMP P1 - Unit complete with: electric circulation pump and manual air vent valve.
• PUMP P1 V3V - Unit complete with: electric circulation pump, manual air vent valve, 3-way diverter valve for the production of domestic hot water.
• PUMP P1 DS - Unit complete with: electric circulation pump to the main heat exchanger, manual air vent valve and desuperheater complete with antifreeze heater.

Separately sold kits are COMPULSORY

• Remote keypad with back-lit LCD display, which can be wall-mounted or installed on the machine.
• Side buffer panels.

Separately sold kits are MANDATORY
when multiple modules are installed in parallel
• Connection hoses between modules.
• Panels and telephone cables for module connection.

Factory fitted accessories
• Forced Download. Compressor partialisation or switch-off to limit power and current consumption (digital input). When multiple modules are connected in parallel, a KCSC accessory must be purchased in order to enable this signal.
• Set up with oversized head pump.
• Soft-Start device.
• Unit with copper/pre-painted aluminium or copper/copper condensation coils.
• Flow switch and hot wire heaters protecting pump and piping down to -20°C outdoor air.
• Silenced set up (muffled compressors).
• Cooling circuit high and low pressure gauges.
• Digital input for double set-point.
• 4-20 mA analogue signal for shifting set-point.

Separately supplied accessories

• Digital input and output concentrator (KCSC).
• Rubber anti-vibration mounts.
• Water filter.
• Right-hand connection kit.
• 3-way diverter valve to manage the production of domestic hot water complete with protective casing and hoses for machine connection. For downstream installation of the group of machines. Not compatible with PUMP V3V set up.
• Additional electrical resistance for heat pump managed by regulation.
• Interfaces for serial communication with other devices.
• Serial converter (RS485/USB).
• Rhoss supervisors for unit monitoring and remote management.

Technical data

THAETY H.T. MODEL 234
1 mod. 2 mod. 3 mod. 4 mod.
Heating capacity kW 33,8 67,6 101,4 135,2
Absorbed power kW 9,85 19,71 29,56 39,42
C.O.P. 3,42 3,42 3,42 3,42
Heating capacity kW 23,49 46,98 70,47 93,96
Absorbed power kW 9,83 19,66 29,48 39,31
C.O.P. 2,39 2,39 2,39 2,39
Heating capacity kW 33,9 67,88 101,82 135,76
Absorbed power kW 8,11 16,24 24,36 32,48
C.O.P. 4,18 4,18 4,18 4,18
Cooling capacity kW 28,8 57,6 86,4 115,2
E.E.R. 2,93 2,93 2,93 2,93
Sound pressure dB(A) 43 46 47 48
Silenced setup sound pressure dB(A) 41 44 45 46
Scroll compressors/steps no. 2/2 4/4 6/6 8/8
Electric pump nominal available head kPa 137 137 137 137
Electrical supply V-ph-Hz 400-3-50 400-3-50 400-3-50 400-3-50
DIMENSIONS AND WEIGHTS 1 mod. 2 mod. 3 mod. 4 mod.
L – Width mm 1297 2541 3785 5029
H – Height mm 2152 2152 2152 2152
P – Depth mm 1224 1224 1224 1224
Weight kg 510 (1 mod.)
SEASONAL ENERGY PERFORMANCE 234
1 mod. 2 mod. 3 mod. 4 mod.
THAETY H.T. MODEL SEASONAL PERFORMANCE IN HEATING MODE – Low temperature application 35°C
Pdesignh (EN 14825) kW 32 65 98 131
SCOP (EN 14825) 3,94 4 4,05 4,12
ηs % 155 157 159 162
Energy class A++ A++ - -
THAETY H.T. MODEL SEASONAL PERFORMANCE IN HEATING MODE – Medium temperature application 55°C
Pdesignh (EN 14825) kW 33 66 99 131
SCOP (EN 14825) 3,09 3,14 3,21 3,28
ηs % 121 123 125 128
Energy class A+ A+ - -
  • Data at the following conditions:
  • Air: 7°C D.B. – 6°C W.B. – Water: 40/45°C.
  • Air: -7°C D.B. – Water: 40/45°C.
  • Air: 7°C D.B. – 6°C W.B. – Water: 30/35°C.
  • Air: 35°C D.B. – Water: 12/7°C.
  • In open field (Q = 2) at 10 m from the unit.
  • Weight refers to P1 DS setup.
  • Performance according to EN 14511
  • In Average climatic conditions
  • Seasonal energy efficiency: heating in Average climate (EU Regulations No.811/2013 and No.813/2013)

Manuals

To view all the documents, log in to the reserved area

Technical notes

To view all the documents, log in to the reserved area

Documents

To view all the documents, log in to the reserved area

Images

Format: tif
Request information about this product









    Find an agent or a reseller.

    Find a reseller in your area for a customized offer on Rhoss air conditioning solutions.