FullFLOW VFD (1+i)
TCHITL 1390÷21700Water-cooled water chillers. Range with semi-hermetic screw compressors with variable Vi, inverter regulation and R513A refrigerant gas.
Key features
Non-flammable reduced GWP gas
High efficiency levels
Continuous power regulation
Various soundproofing options
Touch interface (optional)
Free-Cooling management
Integrated MASTER/SLAVE control
Description
Construction features
• Compressor: high energy efficiency semi-hermetic screw driven by fixed speed motor with linear capacity control and/or variable Vi regulated by inverter (25%-100% single-compressor sizes, 12.5-100% bi-compressor sizes), limited start, complete with integral protection, casing heater, oil level sensor and shut-off valves on delivery and intake piping.
• Water side heat exchanger (evaporator): low refrigerant charge spray flooded type shell and tube exchanger, complete with closed cell polyurethane foam rubber insulation, water flow differential pressure switch and Victaulic fittings.
• Water side heat exchanger (condenser): tube and shell complete with safety valve, service valve on the high-pressure refrigerant gas circuit, and a water flow differential pressure switch and Victaulic fittings.
• Control: microprocessor electronic control.
• Structure: made of galvanised and painted steel plate with polyester powder coating.
• The unit is also complete with:
- clock board;
- electronic expansion valve;
- display of cooling circuit high/low pressure;
- Master/Slave control up to 4 units in parallel;
- 0-10V analogue signal for condensing control from external device;
- control of Variable Primary Flow (VPF_R).
Versions
• T - High efficiency version
Models
• TCHITL: unit designed for cooling only.
Factory fitted accessories
• Free-Cooling management
• Dry-Cooler management
• 100% heat recovery unit.
• Set up for heat pump operation.
• Power factor correction capacitors (cosφ > 0.94).
• Circuit breaker switches.
• Forced limit of power consumption.
• Soft starter.
• Electro-mechanical flow switch.
• EMC anti-disturbance filters.
• Energy parameter measuring device.
• Compressor soundproof enclosures.
• Full acoustic casing.
• Refrigerant leak detector.
• Double safety valves.
• Digital input for double set-point.
• 4-20 mA analogue signal for shifting set-point.
• Evaporator antifreeze heater.
• Control of min/max power supply voltage.
• Interfaces for serial communication with other devices.
• Colour touch user keypad (fitted on the machine or remotely) with 7” display.
• Anti-vibration mounts.
Separately supplied accessories
• Remote keypad with display.
• Outdoor air temperature probe for set-point compensation
• Thermostat with display.
• Rhoss supervisors for unit monitoring and remote management.
• Rhoss sequencer for integrated management of multiple chillers.
Technical data
TCHITL MODEL | 1390 | 1490 | 1600 | 2720 | 2810 | 2900 | 21000 | 21110 | 21260 | 21360 | 21520 (*) | 21700 (*) | ||||
❶ | Nominal cooling capacity | kW | 389,5 | 486,5 | 610,4 | 727,4 | 816,3 | 920,3 | 1001,3 | 1117,2 | 1260,2 | 1361,1 | 1524,2 | 1701,1 | ||
❶ | E.E.R. | 5,18 | 5,16 | 5,11 | 5,5 | 5,41 | 5,5 | 5,45 | 5,32 | 5,36 | 5,4 | 5,57 | 5,55 | |||
❶ | Absorbed power | kW | 75,2 | 94,3 | 119,5 | 132,3 | 150,9 | 167,3 | 183,7 | 210 | 235,1 | 252,1 | 273,6 | 306,5 | ||
❷ | Sound power | dB(A) | 97 | 99 | 101 | 98 | 98 | 100 | 100 | 102 | 103 | 103 | 102 | 103 | ||
❷ | Sound power with enclosure accessory | dB(A) | 93 | 95 | 97 | 94 | 94 | 96 | 96 | 98 | 99 | 99 | 98 | 99 | ||
Screw compressors | n. | 1 | 1 | 1 | 2 | 2 | 2 | 2 | 2 | 2 | 2 | 2 | 2 | |||
Circuits | n. | 1 | 1 | 1 | 2 | 2 | 2 | 2 | 2 | 2 | 2 | 2 | 2 | |||
Electrical supply | V-ph-Hz | 400-3-50 | 400-3-50 | 400-3-50 | 400-3-50 | 400-3-50 | 400-3-50 | 400-3-50 | 400-3-50 | 400-3-50 | 400-3-50 | 400-3-50 | 400-3-50 | |||
DIMENSIONS AND WEIGHTS | 1390 | 1490 | 1600 | 2720 | 2810 | 2900 | 21000 | 21110 | 21260 | 21360 | 21520 | 21700 | ||||
L – Width | mm | 3859 | 3859 | 3859 | 3990 | 3990 | 3990 | 4329 | 4407 | 4407 | 4407 | 4501 | 4586 | |||
H – Height | mm | 1830 | 1830 | 1830 | 2040 | 2040 | 2040 | 2040 | 2040 | 2080 | 2080 | 2090 | 2090 | |||
P – Depth | mm | 1531 | 1531 | 1591 | 1676 | 1676 | 1676 | 1676 | 1814 | 1844 | 1844 | 1979 | 2024 | |||
❸ | TCHITL weight | kg | 2460 | 2530 | 2605 | 4700 | 4830 | 4915 | 5385 | 5600 | 6325 | 6455 | 7765 | 8115 | ||
SEASONAL ENERGY PERFORMANCE | 1390 | 1490 | 1600 | 2720 | 2810 | 2900 | 21000 | 21110 | 21260 | 21360 | 21520 (*) | 21700 (*) | ||||
TCHITL MODEL SEASONAL PERFORMANCE IN COOLING MODE | ||||||||||||||||
① | Pdesignc (EN 14825) | kW | 389,5 | 486,5 | 610,4 | 727,4 | 816,3 | 920,3 | 1001,3 | 1117,2 | 1260,2 | 1361,1 | 1524,2 | 1701,1 | ||
① | SEER (EN 14825) | 8,52 | 8,22 | 8,16 | 8,18 | 8,43 | 8,34 | 8,1 | 8,04 | 8 | 8,03 | 8,1 | 7,96 | |||
② | ηs,c | % | 338 | 326 | 323 | 324 | 334 | 331 | 321 | 319 | 317 | 318 | 321 | 316 | ||
- Data at the following conditions:
- ❶ Chilled water: 7/12°C. – Condenser inlet water: 30/35°C.
- ❷ Total sound power level in dB(A) based on measurements carried out in accordance with regulation UNI EN-ISO 9614.
- ❸ Empty weight.
- Performance according to EN 14511.
- (*) Unit not Eurovent certified.
- ① Low temperature application (7°C)
- ② Seasonal energy efficiency: low temperature cooling (EU Regulation 2016/2281)
Manuals
To view all the documents, log in to the reserved area
Technical notes
To view all the documents, log in to the reserved area
Documents
To view all the documents, log in to the reserved area
Images