Y-Flow E
TCEEY 115÷240Cooling only condenserless units. Range with scroll hermetic compressors and R410A refrigerant gas.
Key features
Efficient condenserless unit in R410A
Description
Construction features
• Compressor: hermetic rotary scroll complete with thermal protection and crankcase heater.
• Water side heat exchanger: adequately insulated stainless steel plates, complete with antifreeze heater and water flow differential pressure switch.
• Control: microprocessor electronic control, with Adaptive Function Plus logic.
• Structure: in galvanised and painted steel plate coated with polyester powder, internally lined with soundproof panelling.
Models
TCEEY: unit designed for cooling only.
Factory fitted accessories
• PUMP - Primary side (user): pump unit complete with electric circulation pump, membrane expansion tank, safety valve, water fill/drain valve, manual air vent valve, and pressure gauge.
The electric pumps are available with low or high head.
• Soft start device.
• Silenced set up with double panelling in the compressor compartment.
• Digital input for double set-point.
• 4-20 mA analogue signal for shifting set-point.
• Refrigerant leak detector.
• Forced limit of power consumption.
Separately supplied accessories
• Outdoor air temperature probe for set-point compensation.
• Water filter.
• Rubber anti-vibration mounts.
• Remote keypad with LCD display.
• Interfaces for serial communication with other devices.
• Serial converter (RS485/USB).
Technical data
TCEEY MODEL | 115 | 118 | 122 | 125 | 230 | 240 | ||||
❶ | Nominal cooling capacity | kW | 13,7 | 16,4 | 20,1 | 23,3 | 26,8 | 36,9 | ||
❶ | EER | 3,26 | 4 | 3,65 | 3,76 | 3,12 | 3,69 | |||
❶ | Absorbed power (*) | kW | 4,2 | 4,1 | 5,5 | 6,2 | 8,6 | 10 | ||
❶ | Available head of standard electric pump | kPa | 89 | 80 | 73 | 114 | 107 | 113 | ||
❶ | Available head of high head pump | kPa | 164 | 146 | 163 | 152 | 129 | 135 | ||
❷ | Sound power | dB(A) | 58 | 58 | 62 | 63 | 64 | 67 | ||
❷ | Silenced setup sound power | dB(A) | 53 | 53 | 57 | 58 | 59 | 62 | ||
Scroll/ step compressors | n. | 1/1 | 1/1 | 1/1 | 1/1 | 2/2 | 2/2 | |||
Circuits | n. | 1 | 1 | 1 | 1 | 1 | 1 | |||
Electrical supply | V-ph-Hz | 400-3+N-50 | 400-3+N-50 | 400-3+N-50 | 400-3+N-50 | 400-3+N-50 | 400-3+N-50 | |||
DIMENSIONS AND WEIGHTS | 115 | 118 | 122 | 125 | 230 | 240 | ||||
L – Width | mm | 700 | 700 | 700 | 700 | 700 | 700 | |||
H – Height | mm | 1140 | 1140 | 1140 | 1140 | 1140 | 1140 | |||
P – Depth | mm | 560 | 560 | 780 | 780 | 780 | 780 | |||
❸ | Weight | kg | 166 | 166 | 191 | 214 | 234 | 251 | ||
- Data at the following conditions:
- ❶ Chilled water: 12/7°C – Condensing temperature: 50°C (dew point)
- ❷ Sound power level in dB(A) based on measurements carried out in accordance with regulation UNI EN ISO 9614
- ❸ Weight refers to the most complete setup
- (*) Unit without electric pumps.
Manuals
To view all the documents, log in to the reserved area
Technical notes
To view all the documents, log in to the reserved area
Documents
To view all the documents, log in to the reserved area
Images
Request information about this product
Find a reseller in your area for a customized offer on Rhoss air conditioning solutions.