New
Web code (TCEETU): WFC05 Web code (TCEETY): WFC01
CHILLERS HEAT PUMPS WATER-cooled CONDENSERLESS UNITS

WinFLOW ECO E WinFLOW E

TCEET 4185÷4395
Cooling capacity 166,5÷360,2 kW

Cooling only condenserless units to couple with a remote condenser. Series with scroll hermetic compressors and R454B or R410A refrigerant gas.

Features

Key features


Condenserless units

Efficient and eco-friendly range in R454B

Extended operating limits

Touch interface (optional)

Integrated MASTER/SLAVE control


WinFLOW ECO E WinFLOW E

Description

Construction features

• Compressor: hermetic rotary scroll complete with thermal protection and crankcase heater.
• Water side heat exchanger: with stainless steel plates, complete with closed cell polyurethane foam rubber insulation and water flow differential pressure switch.
• Control: microprocessor electronic control with Adaptive Function Plus logic.
• Structure: made of galvanised and painted steel plate with polyester powder coating.
• The unit is also complete with:
- compressor circuit breaker switches;
- electronic expansion valve;
- display of cooling circuit high and low pressure;
- Master/Slave control up to 4 units in parallel;
- clock board;
- 0-10V analogue signal for condensing control from external device.

Versions

• T - High efficiency version

Models

• TCEETU: unit designed for cooling only with R454B gas.
• TCEETY: unit designed for cooling only with R410A gas.

Factory fitted accessories

• VPF control.
• Primary side (user) PUMP: with single or double electric pump, one of which automatic in standby. The electric pumps are available in the low or high pressure head versions.
• Desuperheater.
• Primary side (user) inverter pump management.
• Power factor correction capacitors (cosφ > 0.94).
• Soft-starter.
• Energy parameter measuring device.
• Cooling circuit intake valves.
• Refrigerant leak detector.
• Forced limit of power consumption.
• Cooling circuit high and low pressure gauges.
• Double safety valves.
• Technical compartment soundproofing.
• Compressor soundproof enclosures
• Control of min/max power supply voltage and backup battery.
• Low temperature water production.
• Digital input for double set-point.
• 4-20mA analogue signal for shifting set-point.
• Evaporator antifreeze heaters, electrical panel, electric pumps and heat exchangers for heat recovery if applicable.
• Interfaces for serial communication with other devices.
• Colour touch user keypad (fitted on the machine or remotely) with 7'' display.
• Set-up for outdoor installation.
• Anti-vibration mounts.

Separately supplied accessories

• Outdoor air temperature probe for set-point compensation.
• Water filter.
• Remote keypad with display.
• Thermostat with display.
• Rhoss supervisors for unit monitoring and remote management.
• Rhoss sequencer for integrated management of multiple chillers.

Technical data

TCEETU MODEL 4185 4210 4240 4275 4305 4350 4395
Cooling capacity kW 166,5 191 215,1 242,4 269,6 309,9 351,8
Absorbed power kW 47,4 55,4 62,7 72,6 82,2 94,5 107,3
E.E.R. 3,51 3,45 3,43 3,34 3,28 3,28 3,28
TCEETU MODEL 4185 4210 4240 4275 4305 4350 4395
Sound pressure dB(A) 47 47 48 49 51 52 53
Sound power dB(A) 79 79 80 81 83 84 85
Sound power with soundproofing set-up dB(A) 76,5 76,5 77,5 78,5 80,5 81,5 82,5
Scroll compressor/steps no. 4/4 4/4 4/4 4/4 4/4 4/4 4/4
Circuits no. 2 2 2 2 2 2 2
Electrical supply V-ph-Hz 400-3-50 400-3-50 400-3-50 400-3-50 400-3-50 400-3-50 400-3-50
DIMENSIONS AND WEIGHTS 4185 4210 4240 4275 4305 4350 4395
L – Width mm 2510 2510 2510 2510 2510 2510 2510
L – Width mm 3740 3740 3740 3740 3740 3740 3740
H – Height mm 1860 1860 1860 1860 1860 1860 1860
P – Depth mm 870 870 870 870 870 870 870
TCEETU weight kg 1040 1050 1070 1245 1390 1430 1445
TCEETY MODEL 4185 4210 4240 4275 4305 4350 4395
Cooling capacity kW 170,7 195,4 220,5 248,8 276,7 317,7 360,2
Absorbed power kW 49,6 57,8 65,6 75,9 85,7 99 112,6
E.E.R. 3,44 3,38 3,36 3,28 3,23 3,21 3,2
TCEETY MODEL 4185 4210 4240 4275 4305 4350 4395
Sound pressure dB(A) 100 100 100 100 100 100 100
Sound power dB(A) 100 100 100 100 100 100 100
Sound power with soundproofing set-up dB(A) 100 100 100 100 100 100 100
Scroll compressor/steps no. 4/4 4/4 4/4 4/4 4/4 4/4 4/4
Circuits no. 2 2 2 2 2 2 2
Electrical supply V-ph-Hz 400-3-50 400-3-50 400-3-50 400-3-50 400-3-50 400-3-50 400-3-50
DIMENSIONS AND WEIGHTS 4185 4210 4240 4275 4305 4350 4395
L – Width mm 2510 2510 2510 2510 2510 2510 2510
L – Width mm 3740 3740 3740 3740 3740 3740 3740
H – Height mm 1860 1860 1860 1860 1860 1860 1860
P – Depth mm 870 870 870 870 870 870 870
TCEETY weight kg 1040 1050 1070 1245 1390 1430 1445
  • Data at the following conditions:
  • Chilled water: 12/7°C – Condensing temperature: 50°C (dew point)
  • In open field (Q = 2) at 10 m from the unit.
  • Total sound power level in dB(A) based on measurements carried out in accordance with regulation UNI EN-ISO 9614.
  • Width referred to a unit with standard set up.
  • Width referring to the PUMP setup, up to a maximum of 2 pumps.
  • Weight refers to the unit empty with soundproofing.

Manuals

To view all the documents, log in to the reserved area

Technical notes

To view all the documents, log in to the reserved area

Documents

To view all the documents, log in to the reserved area

Images

Format: TIF
Request information about this product









    Find an agent or a reseller.

    Find a reseller in your area for a customized offer on Rhoss air conditioning solutions.