Web code: CID01
CHILLERS HEAT PUMPS AIR-cooled CENTRIFUGAL fans

Compact-ID

TCCITY-THCITY 117÷128
Cooling capacity 16,4÷27,5 kW
Heating capacity 17,7÷28,5 kW

Packaged air-cooled water chillers and reversible heat pumps with Plug-Fans with EC motor. Range with scroll hermetic compressors, DC Inverter and R410A refrigerant gas.

Features

Tax incentives*

Key features

PLUG-FANS with low consumption EC motor
Vertically or horizontally ducted delivery.
Hot water up to –15°C outdoor air
Temperature of the produced water up to 60°C
Integrated MASTER/SLAVE control
Inertial buffer tank

Compact-ID

Description

• Compressor: scroll type, rotary, hermetic with Inverter actuation, complete with thermal protection and casing heater.

• Water side heat exchanger: adequately insulated stainless steel plates, complete with antifreeze heater and water flow differential pressure switch.
• Air side heat exchanger: featuring a finned coil with copper pipes and aluminium fins for TCCITY and with hydrophilic treatment for THCITY, complete with protection grilles.
• Fan: Plenum electric fan with directly coupled, low consumption EC motor fitted with internal thermal protection and accident protection grilles. Removable fan unit section for on-site positioning.
• Vertical condensing air delivery, horizontal outlet easily transformed on-site.
• Proportional electronic device for the continuous regulation of the fan rotation speed up to a temperature of outdoor air of -10°C when running as a chiller.
• Control: microprocessor electronic control with Adaptive Function Plus logic.
• Structure: made of galvanised and painted steel plate, complete with condensate drain pan and unit base antifreeze heater for THCITY.
• The unit is also complete with:
- outdoor air temperature probe for set-point compensation;
- electronic expansion valve;
- display of cooling circuit high and low pressure;
- Master/Slave control up to 4 units in parallel;
- clock board.

Version

T - High efficiency.

Models

TCCITY: unit designed for cooling only.
THCITY: heat pump unit.

PUMP set-up

• Pump unit complete with: EC circulator with 3 speed selector or continuous speed regulation or electric pump, membrane expansion tank, manual air vent valve, safety valve and pressure gauge.

TANK&PUMP set up
• Pump unit complete with: inertial buffer tank, circulator or electric circulation pump, membrane expansion tank, manual air vent valve, safety valve, and pressure gauge.

Factory fitted accessories

• Forced Download. Compressor partialisation or switch-off to limit power and current consumption (digital input).
• Antifreeze heater on the tank.
• Circulator/electric pump antifreeze heater.
• Pre-painted copper/coils or copper/copper coils.
• Digital input for double set-point.
• 4-20 mA analogue signal for shifting set-point.
• Low water set-point temperature.

Accessories supplied loose

• 3-way valve for the production of domestic hot water, managed by regulation.
• Additional electrical resistance for heat pump, managed by regulation.
• Remotable outdoor air temperature probe for compensation of the set-point.
• Delivery anti-vibration fitting.
• Suction duct fitting.
• Water filter.
• Rubber anti-vibration mounts.
• Remote keypad with display.
• Interfaces for serial communication with other devices.
• RS485/USB serial converter.
• Rhoss supervisors for unit monitoring and remote management.

Technical data

TCCITY MODEL 117 124 128
Cooling capacity kW 16,4 24,3 27,5
NOM absorbed power kW 5,24 8,15 9,01
E.E.R. 3,13 2,98 3,05
THCITY MODEL 117 124 128
Heating capacity kW 17,7 24,3 28,5
NOM absorbed power kW 5,33 7,48 8,88
C.O.P. 3,32 3,25 3,21
Heating capacity kW 18,8 25 29,1
NOM absorbed power kW 4,59 6,1 7,28
C.O.P. 4,1 4,1 4
Heating capacity kW 12,3 18,1 22,9
NOM absorbed power kW 4,14 6,65 7,46
C.O.P. 2,97 2,72 3,07
MIN/NOM/MAX cooling capacity 16,2 23,8 27
E.E.R. 2,98 2,84 2,91
TCCITY – THCITY MODEL 117 124 128
Fan delivery sound pressure dB(A) 53 53 56
Machine body sound pressure dB(A) 42 42 45
Fan nominal air flow m3/h 7600 7600 8640
Fan available static pressure Pa 80 80 80
P0 circulator available head kPa 89 89 76
Buffer tank water content l 110 110 110
Electrical supply V-ph-Hz 400-3+N-50 400-3+N-50 400-3+N-50
DIMENSIONS AND WEIGHT 117 124 128
L – PUMP width mm 1522 1522 1522
L – TANK&PUMP width mm 1625 1625 1625
H – PUMP height mm 1280 1280 1280
H – TANK&PUMP height mm 1590 1590 1590
P – PUMP Depth mm 815 815 815
P – TANK&PUMP Depth mm 815 815 815
PUMP Weight kg 265 285 295
TANK&PUMP Weight kg 365 385 395
SEASONAL ENERGY PERFORMANCE 117 124 128
TCCITY MODEL SEASONAL PERFORMANCE IN COOLING MODE
Pdesignc (EN 14825) kW 16,4 24,3 27,5
SEER  (EN 14825) 4,54 4,52 4,59
ηs,c % 179 178 181
THCITY MODEL SEASONAL PERFORMANCE IN HEATING MODE – Low temperature application 35°C
Pdesignh (EN 14825) kW 19 28 35
SCOP (EN 14825) 4,14 3,53 3,69
ηs % 162 138 145
Energy class A++ A+ A+
THCITY MODEL SEASONAL PERFORMANCE IN HEATING MODE – Medium temperature application 55°C
Pdesignh (EN 14825) kW 16 - -
SCOP (EN 14825) 3,08 - -
ηs % 120 - -
Energy class A+ - -
  • Data at the following conditions:
  • Air: 35°C D.B. – Water: 12/7°C.
  • Air: 7°C D.B. – 6°C W.B. – Water: 40/45°C.
  • Air: 7°C D.B. – 6°C W.B. – Water: 30/35°C.
  • Air: -7°C D.B. – Water: 30/35°C.
  • In open field (Q = 2) at 5 m from the unit and ducted fan.
  • Weight refers to the most complete setup.
  • Performance according to EN 14511. P0/PI0 setup.
  • Low temperature application (7°C)
  • Seasonal energy efficiency: low temperature cooling (EU Regulation 2016/2281)
  • In Average climatic conditions.
  • Seasonal energy efficiency: ambient heating in Average climate (EU Regulations No.811/2013 and No.813/2013)

Manuals

To view all the documents, log in to the reserved area

Technical notes

To view all the documents, log in to the reserved area

Documents

To view all the documents, log in to the reserved area

Images

Format: TIF
Request information about this product









    Find an agent or a reseller.

    Find a reseller in your area for a customized offer on Rhoss air conditioning solutions.