TurboPOWER ECO
TCATTE-TCATQE 1330÷3950Air cooled water chillers with axial fans. Range with oil-free centrifugal compressors and R1234ze refrigerant gas.
Key features
High energy efficiency chillers
Efficient, quiet and low start-up current oil-free compressor
HFO R1234ze ecological gas
Integrated MASTER/SLAVE control
Description
Construction features
• Compressor: high energy efficiency, oil free, centrifugal compressor with limited start, equipped with magnetic levitation bearings and complete with integral protection and intake and delivery shut-off valves. The compressor was specifically designed for R1234ze gas with zero environmental impact.
• Water side heat exchanger: spray flooded type shell and tube exchanger, complete with closed cell polyurethane foam rubber insulation, water flow differential pressure switch and Victaulic fittings.
• Air side heat exchanger: with micro-channels.
• Fan: external rotor helical type EC motor electric fans with internal thermal protection and accident protection grilles.
• Control: microprocessor electronic control.
• Structure: made of galvanised and painted steel plate with polyester powder coating.
• The unit is also complete with:
- display of cooling circuit high/low pressure;
- electronic expansion valve;
- double safety valve;
- leak detector;
- clock board;
- Master/Slave control up to 4 units in parallel;
- control of Variable Primary Flow (VPF_R).
Versions
• T - High-efficiency version, soundproofed technical compressor compartment (TCATTE).
• Q - Super silenced version, super-soundproofed technical compartment, reduced speed fans (TCATQE).
Models
• TCATTE: high efficiency unit designed for cooling only.
• TCATQE: super silenced unit designed for cooling only.
Factory fitted accessories
• PUMP with single or double electric pump, one of which automatic in standby. The electric pumps are available in the low or high head versions.
• Inverter pump control for unit start-up.
• Condensing control with over-pressure fans.
• Power factor correction capacitors (cosφ > 0.94).
• Compressor circuit breaker switches.
• Electro-mechanical flow switch.
• Forced limit of power consumption.
• Forced noise limit.
• Energy parameter measuring device.
• Soundproofed compressor box.
• Cooling circuit high and low pressure gauges.
• Coil protection nets.
• Micro-channel coils with E-coating treatment.
• Control of min/max power supply voltage.
• Digital input for double set-point.
• 4-20 mA analogue signal for shifting set-point.
• Evaporator antifreeze heater, electrical panel, electric pumps, if applicable.
• Interfaces for serial communication with other devices.
• Anti-vibration mounts.
Separately supplied accessories
• Remote keypad with display.
• Rhoss supervisors for unit monitoring and remote management.
• Rhoss sequencer for integrated management of multiple chillers.
Technical data
TCATTE-TCATQE MODEL | 1330 | 2400 | 2470 | 2550 | 2660 | 3790 | 3950 | ||||
❶ | Nominal cooling capacity | kW | 334,2 | 399,1 | 470 | 548,9 | 660,5 | 792,1 | 948,6 | ||
❶ | Nominal cooling capacity | kW | 323,2 | 386,1 | 450,1 | 536,9 | 639,7 | 767,3 | 916,9 | ||
❶ | E.E.R. | 3,45 | 3,44 | 3,5 | 3,45 | 3,4 | 3,49 | 3,46 | |||
❶ | E.E.R. | 3,45 | 3,39 | 3,46 | 3,37 | 3,38 | 3,45 | 3,43 | |||
❶ | Absorbed power | kW | 96,9 | 116 | 134,3 | 159,1 | 194,3 | 227 | 274,2 | ||
❶ | Absorbed power | kW | 93,7 | 113,9 | 130,1 | 159,3 | 189,3 | 222,4 | 267,3 | ||
TCATTE-TCATQE MODEL | 1330 | 2400 | 2470 | 2550 | 2660 | 3790 | 3950 | ||||
❸ | TCATTE sound pressure | dB(A) | 62 | 62,5 | 62,5 | 63 | 64 | 64 | 65 | ||
❸ | TCATQE sound pressure | dB(A) | 56 | 56,5 | 57 | 58 | 58 | 59 | 60 | ||
❹ | TCATTE sound power | dB(A) | 94 | 95 | 95 | 96 | 97 | 97 | 98 | ||
❹ | TCATQE sound power | dB(A) | 88 | 89 | 90 | 91 | 91 | 92 | 93 | ||
Compressors | n. | 1 | 2 | 2 | 2 | 2 | 3 | 3 | |||
Circuits | n. | 1 | 1 | 1 | 1 | 1 | 2 | 2 | |||
Electrical supply | V-ph-Hz | 400-3-50 | 400-3-50 | 400-3-50 | 400-3-50 | 400-3-50 | 400-3-50 | 400-3-50 | |||
DIMENSIONS AND WEIGHTS | 1330 | 2400 | 2470 | 2550 | 2660 | 3790 | 3950 | ||||
L – Width | mm | 4940 | 6090 | 7250 | 8350 | 9450 | 11650 | 12810 | |||
H – Height | mm | 2450 | 2450 | 2450 | 2450 | 2450 | 2450 | 2450 | |||
P – Depth | mm | 2260 | 2260 | 2260 | 2260 | 2260 | 2260 | 2260 | |||
❺ | TCATTE weight | kg | 2770 | 3410 | 3960 | 4270 | 4880 | 6280 | 6840 | ||
❺ | TCATQE weight | kg | 2790 | 3440 | 3990 | 4300 | 4910 | 6310 | 6880 | ||
SEASONAL ENERGY PERFORMANCE | 1330 | 2400 | 2470 | 2550 | 2660 | 3790 | 3950 | ||||
TCATTE MODEL SEASONAL PERFORMANCE IN COOLING MODE | |||||||||||
① | Pdesignc (EN 14825) | kW | 334,2 | 399,1 | 470 | 548,9 | 660,5 | 792 | 948,6 | ||
① | SEER (EN 14825) | 5,73 | 5,77 | 5,77 | 5,82 | 5,83 | 6,01 | 6 | |||
② | ηs,c | % | 226 | 228 | 228 | 230 | 230 | 238 | 237 | ||
TCATQE MODEL SEASONAL PERFORMANCE IN COOLING MODE | |||||||||||
① | Pdesignc (EN 14825) | kW | 323,2 | 386,1 | 450,1 | 536,9 | 639,7 | 767,2 | 916,8 | ||
① | SEER (EN 14825) | 5,74 | 5,79 | 5,84 | 5,83 | 5,88 | 6,06 | 5,98 | |||
② | ηs,c | % | 226 | 229 | 231 | 230 | 232 | 239 | 236 | ||
- Data at the following conditions:
- ❶ Air: 35°C – Water: 12/7°C
- ❸ In open field (Q = 2) at 10 m from the unit.
- ❹ Total sound power level in dB(A) based on measurements carried out in accordance with regulation UNI EN-ISO 9614.
- ❺ Weight referred to the unit without load and not accessorised.
- ■ TCATQE super silenced versions
- Performance according to EN 14511.
- ① Low temperature application (7°C)
- ② Seasonal energy efficiency: low temperature cooling (EU Regulation 2016/2281)
Manuals
To view all the documents, log in to the reserved area
Technical notes
To view all the documents, log in to the reserved area
Documents
To view all the documents, log in to the reserved area
Images
Request information about this product
Find a reseller in your area for a customized offer on Rhoss air conditioning solutions.