Web code: TP011
CHILLERS HEAT PUMPS AIR-cooled AXIAL fans

TurboPOWER

TCATBZ-TCATTZ 1300÷31100 / TCATQZ 1300÷3990
Cooling capacity 267,0÷1101 kW

Air cooled water chillers with axial fans. Range with oil-free centrifugal compressors and R134a refrigerant gas.

Features

Key features

Efficient, quiet and low start-up current oil-free compressor
High energy efficiency chillers.
Wide range of accessories
Integrated MASTER/SLAVE control

TurboPOWER

Description

Construction features

• Compressor: high energy efficiency, oil free, centrifugal compressor with limited start, equipped with magnetic levitation bearings and complete with integral protection and intake and delivery shut-off valves.
• Water side heat exchanger: flooded type shell and tube, complete with closed cell polyurethane foam rubber insulation, water flow differential pressure switch and Victaulic fittings.
• Air side heat exchanger: with micro-channels.
• Fan: external rotor axial type electric fans with internal thermal protection, accident protection grilles. Version B is equipped with a proportional electronic device for continuous fan rotation speed regulation, while versions T-Q are equipped with EC motor fans.
• Control: microprocessor electronic control.
• Structure: made of galvanised and painted steel plate with polyester powder coating.
• The unit is also complete with:
- display of cooling circuit high/low pressure;
- electronic expansion valve;
- double safety valve;
- clock board;
- Master/Slave control up to 4 units in parallel;
- control of Variable Primary Flow (VPF_R).

Versions

• B - Basic version, soundproofed technical compressor compartment (TCATBZ).
• T - High-efficiency version, soundproofed technical compressor compartment (TCATTZ).
• Q - Super silenced version, super-soundproofed technical compartment, reduced speed fans (TCATQZ).

Models

• TCATBZ: standard unit designed for cooling only.
• TCATTZ: high efficiency unit designed for cooling only.
• TCATQZ: super silenced unit designed for cooling only.

Factory fitted accessories

• PUMP with single or double electric pump, one of which automatic in standby. The electric pumps are available in the low or high head versions.
• Inverter pump control for unit start-up.
• Condensing control with fans with EC motor (standard in T-Q versions).
• Condensing control with over-pressure fans.
• Power factor correction capacitors (cosφ > 0.94).
• Compressor circuit breaker switches.
• Electro-mechanical flow switch.
• Forced limit of power consumption.
• Forced noise limit.
• Energy parameter measuring device.
• Soundproofed compressor box.
• Refrigerant leak detector.
• Cooling circuit high and low pressure gauges.
• Coil protection nets.
• Micro-channel coils with E-coating treatment.
• Control of min/max power supply voltage.
• Digital input for double set-point.
• 4-20 mA analogue signal for shifting set-point.
• Evaporator antifreeze heater, electrical panel, electric pumps, if applicable.
• Interfaces for serial communication with other devices.
• Anti-vibration mounts.

Separately supplied accessories

• Remote keypad with display.
• Rhoss supervisors for unit monitoring and remote management.
• Rhoss sequencer for integrated management of multiple chillers.

Technical data

TCATBZ-TCATTZ-TCATQZ MODEL 1300 1400 2500 2590 2680 2760 2820 2880 3990 31100
TCATBZ nominal cooling capacity kW 284,9 376,6 489,2 577,8 675,1 749,2 808,9 874,4 982,2 1089,1
TCATTZ nominal cooling capacity kW 298,8 402,3 498,1 593,6 685 760 820,8 882,3 993,1 1101
TCATQZ nominal cooling capacity kW 267,1 369,7 463,4 541,2 639,5 721,5 792,1 871,6 970,4 -
E.E.R. TCATBZ 3,2 3,18 3,26 3,22 3,2 3,2 3,22 3,14 3,25 3,22
E.E.R. TCATTZ 3,46 3,42 3,46 3,48 3,37 3,52 3,5 3,33 3,47 3,45
E.E.R. TCATQZ 3,22 3,32 3,25 3,28 3,21 3,24 3,36 3,31 3,27 -
TCATBZ absorbed power kW 89 118,4 150,1 179,4 211 234,1 251,2 278,5 302,2 338,2
TCATTZ absorbed power kW 86,4 117,6 144 170,6 203,3 215,9 234,5 265 286,2 319,1
TCATQZ absorbed power kW 83 111,4 142,6 165 199,2 222,7 235,7 263,3 296,8 -
TCATBZ-TCATTZ-TCATQZ MODEL 1300 1400 2500 2590 2680 2760 2820 2880 3990 31100
TCATBZ sound pressure dB(A) 60 62 62,5 62,5 63 64 64 64 64 65
TCATTZ sound pressure dB(A) 60 62 62,5 62,5 63 64 64 64 64 65
TCATQZ sound pressure dB(A) 55 56 56,5 57 58 58 58 59 59 -
TCATBZ sound power dB(A) 92 94 95 95 96 97 97 97 97 98
TCATTZ sound power dB(A) 92 94 95 95 96 97 97 97 97 98
TCATQZ sound power dB(A) 87 88 89 90 91 91 91 92 92 -
Compressor n. 1 1 2 2 2 2 2 2 3 3
Circuits n. 1 1 1 1 1 1 1 1 2 2
Electrical supply V-ph-Hz 400-3-50 400-3-50 400-3-50 400-3-50 400-3-50 400-3-50 400-3-50 400-3-50 400-3-50 400-3-50
DIMENSIONS AND WEIGHT 1300 1400 2500 2590 2680 2760 2820 2880 3990 31100
W – Width of version B mm 3840 4940 6090 7250 8350 9450 9450 10550 11650 12810
W – Width of version T mm 3840 4940 6090 7250 8350 9450 10550 11650 11650 12810
W – Width of version Q mm 3840 4940 6090 7250 8350 9450 10550 11650 12810 -
H – Height mm 2450 2450 2450 2450 2450 2450 2450 2450 2450 2450
P – Depth mm 2260 2260 2260 2260 2260 2260 2260 2260 2260 2260
TCATBZ weight kg 2390 2740 3490 3950 4350 4800 4910 5210 6040 6560
TCATTZ weight kg 2410 2760 3470 3980 4320 4840 5140 5440 6000 6520
TCATQZ weight kg 2390 2730 3500 3960 4350 4800 5160 5460 6500 -
SEASONAL ENERGY PERFORMANCE 1300 1400 2500 2590 2680 2760 2820 2880 3990 31100
TCATBZ MODEL SEASONAL PERFORMANCE IN COOLING MODE
Pdesignc (EN 14825) kW 284,9 376,6 489,2 577,8 675,1 749,2 808,8 874,4 982,1 1088,9
SEER  (EN 14825) 5,3 5,18 5,34 5,26 5,35 5,21 5,26 5,21 5,35 5,31
ηs,c % 209 204 211 207 211 205 207 205 211 210
TCATTZ MODEL SEASONAL PERFORMANCE IN COOLING MODE
Pdesignc (EN 14825) kW 298,8 402,3 498,1 593,6 685 760,1 820,8 882,3 993,1 1100,9
SEER  (EN 14825) 5,63 5,75 5,85 5,83 5,91 6,03 5,97 5,94 5,99 5,94
ηs,c % 222 227 231 230 234 238 236 235 237 234
TCATQZ MODEL SEASONAL PERFORMANCE IN COOLING MODE
Pdesignc (EN 14825) kW 267,1 369,7 463,4 541,2 639,5 721,5 792,1 871,6 970,3 -
SEER  (EN 14825) 5,65 5,76 5,88 5,81 5,9 5,96 5,98 5,98 6,02 -
ηs,c % 223 227 232 230 233 235 236 236 238 -
  • Data at the following conditions:
  • Air: 35°C – Water: 12/7°C
  • In open field (Q = 2) at 10 m from the unit.
  • Total sound power level in dB(A) based on measurements carried out in accordance with regulation UNI EN-ISO 9614.
  • Weight referred to the unit without load and not accessorised.
  • TCATQZ super silenced versions
  • Performance according to EN 14511.
  • Low temperature application (7°C)
  • Seasonal energy efficiency: low temperature cooling (EU Regulation 2016/2281)

Manuals

To view all the documents, log in to the reserved area

Technical notes

To view all the documents, log in to the reserved area

Documents

To view all the documents, log in to the reserved area

Images

Format: TIF
Request information about this product









    Find an agent or a reseller.

    Find a reseller in your area for a customized offer on Rhoss air conditioning solutions.