EasyPACK-I
TCAIY-THAIY 270÷2130Water chillers and packaged reversible air-cooled heat pumps with axial fans. Range with scroll hermetic compressors, DC Inverter and R410A refrigerant.
Key features
Chillers and heat pumps with inverter compressors
Precise and efficient power modulation
Plug&Play unit with integrated hydronic module and heat recovery
Integrated MASTER/SLAVE control
Description
Construction features
• Compressor: scroll type, rotary, hermetic and with Inverter actuation (1+i) complete with thermal protection and casing heater.
• Continuous regulation with high efficiency at partial loads.
• Water side heat exchanger: with stainless steel plates, complete with closed cell polyurethane foam rubber insulation and water flow differential pressure switch.
• Air side heat exchanger: featuring micro-channels (TCAIY) or finned coil with copper pipes and aluminium fins (THAIY).
• Fan: external rotor axial type electric fans with internal thermal protection, accident protection grilles. The electric fans, based on the sizes, are EC fans or fitted with a proportional electronic device for continuous regulation of the rotation speed of the fans.
• Control: microprocessor electronic control with Adaptive Function Plus logic.
• Structure: load-bearing structure made of galvanised and painted steel plate with polyester powder coating.
• The unit is also complete with:
- compressor and fan circuit breaker switches;
- electronic expansion valve;
- display of cooling circuit high and low pressure;
- Master/Slave control up to 4 units in parallel;
- clock board;
- control of Variable Primary Flow (VPF_R).
Versions
• T - High efficiency version with oversized condensing section (TCAITY-THAITY).
• Q - Super-silenced version complete with compressor technical compartment soundproofing, reduced speed fans and oversized condensing section (TCAIQY-THAIQY).
Models
• TCAITY: high efficiency unit designed for cooling only.
• TCAIQY: super silenced unit designed for cooling only.
• THAITY: high efficiency heat pump unit.
• THAIQY: super silenced heat pump unit.
Factory fitted accessories
• PUMP with single or double electric pump, one of which automatic in standby. The electric pumps are available in the low or high head versions.
• TANK&PUMP with 230 - 440 litre integrated buffer tank (depending on the sizes) and single or double electric pump, complete with expansion tank, air vent valves, safety valve and water side pressure gauge.
• Inverter pump control for unit start-up.
• Desuperheater.
• 100% heat recovery unit
• Condensing control with fans with EC motor (standard in sizes 270-2100).
• Condensing control with over-pressure fans (T version only)
• Power factor correction capacitors (cosφ > 0.94).
• Forced limit of power consumption.
• Forced noise limit.
• Energy parameter measuring device.
• Optimised energy efficiency.
• Soft starter.
• Technical compressor compartment soundproofing.
• Compressor soundproof enclosures.
• Cooling circuit outlet and inlet valves.
• Refrigerant leak detector.
• Cooling circuit high and low pressure gauges.
• Double safety valves.
• Metal filters or coil protection nets.
• Microchannel coils with E-coating treatment, copper/copper, copper/aluminium or pre-painted copper/aluminium depending on the versions.
• Control of min/max power supply voltage.
• Digital input for double set-point.
• 4-20 mA analogue signal for shifting set-point.
• Evaporator antifreeze heater, electrical panel, buffer tank, electric pumps and heat exchangers for heat recovery, if applicable.
• Interfaces for serial communication with other devices.
• Rubber anti-vibration mounts.
Separately supplied accessories
• Remote keypad with display.
• Thermostat with display.
• Rhoss supervisors for unit monitoring and remote management.
• Rhoss sequencer for integrated management of multiple chillers.
Technical data
TCAITY-TCAIQY MODEL | 270 | 280 | 290 | 2100 | 2115 | 1 inverter + 1 | ||||
❶ | Nominal cooling capacity | kW | 69,8 | 82,6 | 90,3 | 97,9 | 117 | 130,4 | ||
❶ | Nominal cooling capacity | kW | 67,8 | 80,8 | 87,7 | 93,4 | 111,4 | 125,5 | ||
❶ | E.E.R. | 3,16 | 3,17 | 3,15 | 3,02 | 3,1 | 3,14 | |||
❶ | E.E.R. | 3,01 | 3,06 | 3 | 2,84 | 2,9 | 3,01 | |||
❶ | Absorbed power | kW | 22,09 | 26,06 | 28,67 | 32,42 | 37,74 | 41,53 | ||
❶ | Absorbed power | kW | 22,52 | 26,41 | 29,23 | 32,89 | 38,41 | 41,69 | ||
THAITY-THAIQY MODEL | 270 | 280 | 290 | 2100 | 2115 | 2130 | ||||
❷ | Nominal heating capacity | kW | 73,4 | 85,4 | 92,5 | 100,6 | 121,5 | 134,6 | ||
❷ | Nominal heating capacity | kW | 71,2 | 83,4 | 90,4 | 98,7 | 117,4 | 130,6 | ||
❷ | C.O.P. | 3,37 | 3,34 | 3,36 | 3,34 | 3,37 | 3,32 | |||
❷ | C.O.P. | 3,31 | 3,33 | 3,32 | 3,3 | 3,34 | 3,36 | |||
❶ | Nominal cooling capacity | kW | 67,1 | 79,3 | 86,8 | 93,5 | 112,6 | 126,5 | ||
❶ | Nominal cooling capacity | kW | 65 | 77,9 | 84,7 | 90,3 | 108,6 | 123,5 | ||
❷ | Absorbed power | kW | 21,78 | 25,57 | 27,53 | 30,12 | 36,05 | 40,54 | ||
❷ | Absorbed power | kW | 21,51 | 25,05 | 27,23 | 29,91 | 35,15 | 38,87 | ||
TCAIY-THAIY MODEL | 270 | 280 | 290 | 2100 | 2115 | 2130 | ||||
❸ | TCAITY-THAITY sound pressure | dB(A) | 52 | 53 | 53 | 53 | 55 | 56 | ||
❸ | TCAIQY-THAIQY sound pressure | dB(A) | 45 | 46 | 46 | 46 | 49 | 50 | ||
❹ | TCAITY-THAITY sound power | dB(A) | 84 | 85 | 85 | 85 | 87 | 88 | ||
❹ | TCAIQY-THAIQY sound power | dB(A) | 77 | 77,5 | 77,5 | 77,5 | 81 | 82 | ||
Scroll compressors | n. | 1 inverter + 1 | 1 inverter + 1 | 1 inverter + 1 | 1 inverter + 1 | 1 inverter + 1 | 1 inverter + 1 | |||
Circuits | n. | 1 | 1 | 1 | 1 | 2 | 2 | |||
Electrical supply | V-ph-Hz | 400-3+N-50 | 400-3+N-50 | 400-3+N-50 | 400-3+N-50 | 400-3+N-50 | 400-3+N-50 | |||
DIMENSIONS AND WEIGHTS | 270 | 280 | 290 | 2100 | 2115 | 2130 | ||||
L – Width | mm | 3250 | 3250 | 3250 | 3250 | 3450 | 3450 | |||
H – Height | mm | 1540 | 1540 | 1540 | 1540 | 2000 | 2000 | |||
P – Depth | mm | 1210 | 1210 | 1210 | 1210 | 1520 | 1520 | |||
❺ | TCAITY weight | kg | 765 | 790 | 795 | 800 | 1125 | 1145 | ||
❺ | THAITY weight | kg | 880 | 915 | 920 | 925 | 1325 | 1345 | ||
SEASONAL ENERGY PERFORMANCE | 270 | 280 | 290 | 2100 | 2115 | 2130 | ||||
TCAITY MODEL SEASONAL PERFORMANCE IN COOLING MODE | ||||||||||
① | Pdesignc (EN 14825) | kW | 69,8 | 82,6 | 90,3 | 97,9 | 117 | 130,4 | ||
① | SEER (EN 14825) | 4,59 | 4,69 | 4,65 | 4,6 | 4,27 | 4,27 | |||
② | ηs,c | % | 181 | 184 | 183 | 181 | 168 | 168 | ||
TCAIQY MODEL SEASONAL PERFORMANCE IN COOLING MODE | ||||||||||
① | Pdesignc (EN 14825) | kW | 67,8 | 80,8 | 87,7 | 93,4 | 111,4 | 125,5 | ||
① | SEER (EN 14825) | 4,49 | 4,58 | 4,49 | 4,45 | 4,11 | 4,12 | |||
② | ηs,c | % | 176 | 180 | 177 | 175 | 161 | 162 | ||
THAITY MODEL SEASONAL ENERGY PERFORMANCE IN HEATING MODE | ||||||||||
③ | Pdesignh (EN 14825) | kW | 57 | 65 | 70 | 95 | 121 | 126 | ||
③ | SCOP (EN 14825) | 4,19 | 4,27 | 4,26 | 4,15 | 3,99 | 4,03 | |||
④ | ηs | % | 165 | 168 | 167 | 163 | 156 | 158 | ||
④ | Energy class | A++ | A++ | A++ | - | - | - | |||
THAIQY MODEL SEASONAL ENERGY PERFORMANCE IN HEATING MODE | ||||||||||
③ | Pdesignh (EN 14825) | kW | 54 | 63 | 69 | 93 | 111 | 133 | ||
③ | SCOP (EN 14825) | 4,04 | 4,17 | 4,11 | 4,06 | 3,88 | 3,96 | |||
④ | ηs | % | 159 | 164 | 162 | 160 | 152 | 155 | ||
④ | Energy class | A++ | A++ | A++ | - | - | - | |||
- Data at the following conditions:
- ❶ Air: 35°C – Water: 12/7°C
- ❷ Air: 7°C, D.B. – 6°C W.B.- Water: 40/45°C.
- ❸ In open field (Q = 2) at 10 m from the unit.
- ❹ Total sound power level in dB(A) based on measurements carried out in accordance with regulation UNI EN-ISO 9614.
- ❺ Weight referred to the unit without load and not accessorised.
- ■ TCAIQY-THAIQY super-silenced versions.
- Performance according to EN 14511.
- ① Low temperature application (7°C)
- ② Seasonal energy efficiency: low temperature cooling (EU Regulation 2016/2281)
- ③ In Average climatic conditions, low temperature application (35°C)
- ④ Seasonal energy efficiency: low temperature heating in Average climate (EU Regulations No.811/2013 and No.813/2013)
Manuals
To view all the documents, log in to the reserved area
Technical notes
To view all the documents, log in to the reserved area
Documents
To view all the documents, log in to the reserved area
Images
Request information about this product
Find a reseller in your area for a customized offer on Rhoss air conditioning solutions.