Web code: CYI12
CHILLERS HEAT PUMPS AIR-cooled AXIAL fans

MidiPACK-I

TCAITY-THAITY 138÷262
Cooling capacity 37,4÷62,6 kW
Heating capacity 40,2÷71 kW

Water chillers and packaged reversible air-cooled heat pumps with axial fans. Range with scroll hermetic compressors, DC Inverter and R410A refrigerant gas.

Features

Tax incentives*

Key features

Hot water up to -15°C outdoor air
Temperature of the produced water up to 60°C
Plug&Play unit with integrated hydraulic module
Optional EC fans and inverter-based circulation pump
Multi-purpose for systems with 2 pipes + DHW (with optional RC100)
Integrated MASTER/SLAVE control

MidiPACK-I

Description

Construction features

• Compressor: scroll type, rotary, hermetic with Inverter actuation, complete with thermal protection and casing heater.
• Water side heat exchanger: adequately insulated stainless steel plates, complete with antifreeze heater and water flow differential pressure switch.
• Air side heat exchanger: finned coil with copper pipes and aluminium fins, complete with protection grilles.
• Fan: external rotor axial type electric fans equipped with internal thermal protection, accident protection grilles and proportional electronic device for continuous fan rotation speed regulation.
• Control: microprocessor electronic control with Adaptive Function Plus logic.
• Structure: made of galvanised and painted steel plate
• The unit is also complete with:
- outdoor air temperature probe for set-point compensation;
- display of cooling circuit high and low pressure;
- electronic expansion valve;
- Master/Slave control up to 4 units in parallel;
- clock board.

Version

T - High efficiency.

Models

TCAITY: unit designed for cooling only.
THAITY: heat pump unit.

PUMP set-up

Pump unit with single or double electric pump, including an automatic actuation pump in standby, complete with expansion tank, air vent valves, safety valve and water side pressure gauge. The pumps are available in low or high pressure head versions, and with INVERTER operation.
TANK&PUMP set up
• Pump unit complete with inertial buffer tank and single or double electric pump, including an automatic actuation pump in standby, complete with expansion tank, air vent valves, safety valve and water side pressure gauge. The pumps are available in low or high pressure head versions, and with INVERTER operation.

Factory fitted accessories

• Pre-painted copper/aluminium coils with hydrophilic treatment or copper/copper.
• Desuperheater.
• 100% heat recovery unit.
• 3-way diverter valve for the production of domestic hot water, managed by regulation.
• Condensing control with fans with EC motor.
• Base antifreeze heater
• Antifreeze heater for buffer tank and electric pumps
• Forced Download. Compressor partialisation or switch-off to limit power and current consumption (digital input).
• Refrigerant leak detector
• Digital input for double set-point.
• 4-20 mA analogue signal for shifting set-point.
• Energy parameters measurement.
• Silenced set up.
• Cooling circuit high and low pressure gauges.
• Low water set-point temperature.

Separately supplied accessories

• 3-way valve for the production of domestic hot water, managed by regulation.
• Remotable outdoor air temperature probe for compensation of the set-point.
• Additional electrical resistance for heat pump, managed by regulation.
• Rubber anti-vibration mounts.
• Water filter.
• Thermostat with display.
• Remote keypad with display.
• Interfaces for serial communication with other devices.
• Serial converter (RS485/USB).
• Rhoss supervisors for unit monitoring and remote management.

Technical data

TCAITY MODEL 138 146 154 262
Cooling capacity kW 37,4 47,7 55,1 62,6
Absorbed power kW 13,6 16,1 18,4 22,8
E.E.R. 2,76 2,97 2,99 2,75
THAITY MODEL 138 146 154 262
Heating capacity kW 40,2 52,1 58,7 71
Absorbed power kW 12,5 16,2 18,2 22,2
C.O.P. 3,21 3,22 3,23 3,2
Heating capacity kW 40,2 54,2 60,4 74
Absorbed power kW 10,3 14,3 15,9 20,2
C.O.P. 3,91 3,8 3,81 3,67
Heating capacity kW 28,3 38,6 42,3 51
Absorbed power kW 9,7 13,4 14,9 19,5
C.O.P. 2,92 2,89 2,83 2,62
Cooling capacity kW 36,7 46,1 54 61,4
E.E.R. 2,69 2,9 2,92 2,7
TCAITY-THAITY MODEL 138 146 154 262
Sound pressure dB(A) 54 55 55 57
Scroll compressor n. 1 inverter 1 inverter 1 inverter 1 inverter + 1
Circuits no. 1 1 1 1
Buffer tank water content (TANK&PUMP) l 80 150 150 150
Standard head pump nominal available head (TCAITY) kPa 124 98 107 111
Electrical supply V-ph-Hz 400-3+N-50 400-3+N-50 400-3+N-50 400-3+N-50
DIMENSIONS AND WEIGHTS 138 146 154 262
L – Width mm 1710 2315 2315 2315
H – Height mm 1570 1570 1570 1570
P – Depth mm 1000 1000 1000 1000
TCAITY weight kg 545 640 690 815
THAITY weight kg 555 660 720 835
SEASONAL ENERGY PERFORMANCE 138 146 154 262
TCAITY MODEL SEASONAL PERFORMANCE IN COOLING MODE
Pdesignc (EN 14825) kW 37,4 47,7 55,1 62,6
SEER  (EN 14825) 4,33 4,31 4,27 4,31
ηs,c % 170 169 168 169
THAITY MODEL SEASONAL PERFORMANCE IN HEATING MODE
Pdesignh (EN 14825) kW 40 54 60 70
SCOP (EN 14825) 3,9 3,85 3,84 4,08
ηs % 153 151 150 160
Energy class A++ A++ A++ A++
  • Data at the following conditions:
  • Air: 35°C D.B. – Water: 12/7°C.
  • Air: 7°C D.B. – 6°C W.B. – Water: 40/45°C.
  • Air: 7°C D.B. – 6°C W.B. – Water: 30/35°C.
  • Air: -7°C D.B. – Water: 30/35°C.
  • In open field (Q = 2) at 5 m from the unit.
  • Weight refers to the most complete setup.
  • Performance according to EN 14511.
  • Low temperature application (7°C)
  • Seasonal energy efficiency: low temperature cooling (EU Regulation 2016/2281)
  • In Average climatic conditions, low temperature application (35°C)
  • Seasonal energy efficiency: low temperature heating in Average climate (EU Regulations No.811/2013 and No.813/2013)

Manuals

To view all the documents, log in to the reserved area

Technical notes

To view all the documents, log in to the reserved area

Documents

To view all the documents, log in to the reserved area

Images

Format: tif
Request information about this product









    Find an agent or a reseller.

    Find a reseller in your area for a customized offer on Rhoss air conditioning solutions.