MidiPACK-I
TCAITY-THAITY 120÷130Water chillers and packaged reversible air-cooled heat pumps with axial fans. Range with scroll hermetic compressors, DC Inverter and R410A refrigerant gas.
Key features
Hot water up to -15°C outdoor air
Temperature of the produced water up to 60°C
Version with pump or with pump and storage tank
Integrated MASTER/SLAVE control
Description
Construction features
• Compressor: scroll type, rotary, hermetic with Inverter actuation, complete with thermal protection and casing heater.
• Water side heat exchanger: adequately insulated stainless steel plates, complete with antifreeze heater and water flow differential pressure switch.
• Air side heat exchanger: featuring finned coil with copper pipes and aluminium fins for TCAITY with hydrophilic treatment for THAITY, complete with protection grilles.
• Fan: external rotor axial type electric fans equipped with internal thermal protection, accident protection grilles and proportional electronic device for continuous fan rotation speed regulation.
• Control: microprocessor electronic control with Adaptive Function Plus logic.
• Structure: made of galvanised and painted steel plate, complete with condensate drain pan and unit base antifreeze heater for THAITY.
• The unit is also complete with:
- outdoor air temperature probe for set-point compensation;
- electronic expansion valve;
- display of cooling circuit high and low pressure;
- Master/Slave control up to 4 units in parallel;
- clock board.
Version
T - High efficiency.
Models
TCAITY: unit designed for cooling only.
THAITY: heat pump unit.
PUMP set-up
• Pump unit complete with: EC circulator with 3 speed selector or continuous speed regulation or electric pump, membrane expansion tank, manual air vent valve, safety valve and pressure gauge.
TANK&PUMP set up
• Pump unit complete with: inertial buffer tank, circulator or electric circulation pump, membrane expansion tank, manual air vent valve, safety valve, and pressure gauge.
Factory fitted accessories
• Forced Download. Compressor partialisation or switch-off to limit power and current consumption (digital input).
• Condensing control with fans with EC motor.
• Silenced set up.
• Antifreeze heater on the tank.
• Circulator/electric pump antifreeze heater.
• Pre-painted copper/coils or copper/copper coils.
• Digital input for double set-point.
• 4-20 mA analogue signal for shifting set-point.
• Low water set-point temperature.
Separately supplied accessories
• 3-way valve for the production of domestic hot water, managed by regulation.
• Additional electrical resistance for heat pump, managed by regulation.
• Remotable outdoor air temperature probe for compensation of the set-point.
• Water filter.
• Rubber anti-vibration mounts.
• Remote keypad with display.
• Interfaces for serial communication with other devices.
• RS485/USB serial converter.
• Rhoss supervisors for unit monitoring and remote management.
Technical data
TCAITY MODEL | 120 | 125 | 130 | ||||
❶ | Cooling capacity | kW | 18,8 | 25,2 | 29,3 | ||
❶ | Absorbed power | kW | 6,53 | 8,72 | 10,17 | ||
❶ | E.E.R. | 2,88 | 2,89 | 2,88 | |||
THAITY MODEL | 120 | 125 | 130 | ||||
❷ | Heating capacity | kW | 20 | 25,6 | 30,4 | ||
❷ | Absorbed power | kW | 6,15 | 7,83 | 9,5 | ||
❷ | C.O.P. NOM | 3,25 | 3,27 | 3,2 | |||
❸ | Heating capacity | kW | 21,1 | 26,1 | 30,7 | ||
❸ | Absorbed power | kW | 5,2 | 6,41 | 7,62 | ||
❸ | C.O.P. | 4,06 | 4,07 | 4,03 | |||
❹ | Heating capacity | kW | 14,8 | 18,1 | 21,3 | ||
❹ | Absorbed power | kW | 4,92 | 6,51 | 7,61 | ||
❹ | C.O.P. | 3,01 | 2,78 | 2,8 | |||
❶ | Cooling capacity | kW | 18,5 | 24,1 | 28,3 | ||
❶ | E.E.R. | 2,7 | 2,75 | 2,71 | |||
TCAITY-THAITY MODEL | 120 | 125 | 130 | ||||
❺ | Sound pressure | dB(A) | 47 | 50 | 51 | ||
❶ | P0 circulator available head | kPa | 77 | 80 | 67 | ||
Buffer tank water content | l | 110 | 110 | 110 | |||
Electrical supply | V-ph-Hz | 400-3+N-50 | 400-3+N-50 | 400-3+N-50 | |||
DIMENSIONS AND WEIGHT | 120 | 125 | 130 | ||||
L – PUMP width | mm | 1522 | 1522 | 1522 | |||
L – TANK&PUMP width | mm | 1625 | 1625 | 1625 | |||
H – PUMP height | mm | 1280 | 1280 | 1280 | |||
H – TANK&PUMP height | mm | 1590 | 1590 | 1590 | |||
P – PUMP Depth | mm | 600 | 600 | 600 | |||
P – TANK&PUMP Depth | mm | 600 | 600 | 600 | |||
❻ | PUMP Weight | kg | 245 | 265 | 275 | ||
❻ | TANK&PUMP Weight | kg | 345 | 365 | 375 | ||
SEASONAL ENERGY PERFORMANCE | 120 | 125 | 130 | ||||
TCAITY MODEL SEASONAL PERFORMANCE IN COOLING MODE | |||||||
① | Pdesignc (EN 14825) | kW | 18,8 | 25,2 | 29,3 | ||
① | SEER (EN 14825) | 4,31 | 4,36 | 4,32 | |||
② | ηs,c | % | 169 | 171 | 170 | ||
THAITY MODEL SEASONAL PERFORMANCE IN HEATING MODE – Low temperature application 35°C | |||||||
③ | Pdesignh (EN 14825) | kW | 21 | 26 | 30 | ||
③ | SCOP (EN 14825) | 4,17 | 3,63 | 3,88 | |||
④ | ηs | % | 164 | 142 | 152 | ||
④ | Energy class | A++ | A+ | A++ | |||
THAITY MODEL SEASONAL PERFORMANCE IN HEATING MODE – Medium temperature application 55°C | |||||||
③ | Pdesignh (EN 14825) | kW | 19 | - | - | ||
③ | SCOP (EN 14825) | 3,41 | - | - | |||
④ | ηs | % | 133 | - | - | ||
④ | Energy class | A++ | - | - | |||
- Data at the following conditions:
- ❶ Air: 35°C D.B. – Water: 12/7°C.
- ❷ Air: 7°C D.B. – 6°C W.B. – Water: 40/45°C.
- ❸ Air: 7°C D.B. – 6°C W.B. – Water: 30/35°C.
- ❹ Air: -7°C D.B. – Water: 30/35°C.
- ❺ In open field (Q = 2) at 5 m from the unit.
- ❻ Weight refers to the most complete setup.
- Performance according to EN 14511. P0 setup.
- ① Low temperature application (7°C)
- ② Seasonal energy efficiency: low temperature cooling (EU Regulation 2016/2281)
- ③ In Average climatic conditions.
- ④ Seasonal energy efficiency: ambient heating in Average climate (EU Regulations No.811/2013 and No.813/2013)
Manuals
To view all the documents, log in to the reserved area
Technical notes
To view all the documents, log in to the reserved area
Documents
To view all the documents, log in to the reserved area
Images
Request information about this product