Web code: CYI02
CHILLERS HEAT PUMPS AIR-cooled AXIAL fans

MidiPACK-I

TCAITY-THAITY 120÷130
Cooling capacity 18,8÷29,3 kW
Heating capacity 20÷30,4 kW

Water chillers and packaged reversible air-cooled heat pumps with axial fans. Range with scroll hermetic compressors, DC Inverter and R410A refrigerant gas.

Features

Key features

Hot water up to -15°C outdoor air
Temperature of the produced water up to 60°C
Version with pump or with pump and storage tank
Integrated MASTER/SLAVE control

MidiPACK-I

Description

Construction features

• Compressor: scroll type, rotary, hermetic with Inverter actuation, complete with thermal protection and casing heater.
• Water side heat exchanger: adequately insulated stainless steel plates, complete with antifreeze heater and water flow differential pressure switch.
• Air side heat exchanger: featuring finned coil with copper pipes and aluminium fins for TCAITY with hydrophilic treatment for THAITY, complete with protection grilles.
• Fan: external rotor axial type electric fans equipped with internal thermal protection, accident protection grilles and proportional electronic device for continuous fan rotation speed regulation.
• Control: microprocessor electronic control with Adaptive Function Plus logic.
• Structure: made of galvanised and painted steel plate, complete with condensate drain pan and unit base antifreeze heater for THAITY.
• The unit is also complete with:
- outdoor air temperature probe for set-point compensation;
- electronic expansion valve;
- display of cooling circuit high and low pressure;
- Master/Slave control up to 4 units in parallel;
- clock board.

Version

T - High efficiency.

Models

TCAITY: unit designed for cooling only.
THAITY: heat pump unit.

PUMP set-up

• Pump unit complete with: EC circulator with 3 speed selector or continuous speed regulation or electric pump, membrane expansion tank, manual air vent valve, safety valve and pressure gauge.

TANK&PUMP set up
• Pump unit complete with: inertial buffer tank, circulator or electric circulation pump, membrane expansion tank, manual air vent valve, safety valve, and pressure gauge.

Factory fitted accessories

• Forced Download. Compressor partialisation or switch-off to limit power and current consumption (digital input).
• Condensing control with fans with EC motor.
• Silenced set up.
• Antifreeze heater on the tank.
• Circulator/electric pump antifreeze heater.
• Pre-painted copper/coils or copper/copper coils.
• Digital input for double set-point.
• 4-20 mA analogue signal for shifting set-point.
• Low water set-point temperature.

Separately supplied accessories

• 3-way valve for the production of domestic hot water, managed by regulation.
• Additional electrical resistance for heat pump, managed by regulation.
• Remotable outdoor air temperature probe for compensation of the set-point.
• Water filter.
• Rubber anti-vibration mounts.
• Remote keypad with display.
• Interfaces for serial communication with other devices.
• RS485/USB serial converter.
• Rhoss supervisors for unit monitoring and remote management.

Technical data

TCAITY MODEL 120 125 130
Cooling capacity kW 18,8 25,2 29,3
Absorbed power kW 6,53 8,72 10,17
E.E.R. 2,88 2,89 2,88
THAITY MODEL 120 125 130
Heating capacity kW 20 25,6 30,4
Absorbed power kW 6,15 7,83 9,5
C.O.P. NOM 3,25 3,27 3,2
Heating capacity kW 21,1 26,1 30,7
Absorbed power kW 5,2 6,41 7,62
C.O.P. 4,06 4,07 4,03
Heating capacity kW 14,8 18,1 21,3
Absorbed power kW 4,92 6,51 7,61
C.O.P. 3,01 2,78 2,8
Cooling capacity kW 18,5 24,1 28,3
E.E.R. 2,7 2,75 2,71
TCAITY-THAITY MODEL 120 125 130
Sound pressure dB(A) 47 50 51
P0 circulator available head kPa 77 80 67
Buffer tank water content l 110 110 110
Electrical supply V-ph-Hz 400-3+N-50 400-3+N-50 400-3+N-50
DIMENSIONS AND WEIGHT 120 125 130
L – PUMP width mm 1522 1522 1522
L – TANK&PUMP width mm 1625 1625 1625
H – PUMP height mm 1280 1280 1280
H – TANK&PUMP height mm 1590 1590 1590
P – PUMP Depth mm 600 600 600
P – TANK&PUMP Depth mm 600 600 600
PUMP Weight kg 245 265 275
TANK&PUMP Weight kg 345 365 375
SEASONAL ENERGY PERFORMANCE 120 125 130
TCAITY MODEL SEASONAL PERFORMANCE IN COOLING MODE
Pdesignc (EN 14825) kW 18,8 25,2 29,3
SEER  (EN 14825) 4,31 4,36 4,32
ηs,c % 169 171 170
THAITY MODEL SEASONAL PERFORMANCE IN HEATING MODE – Low temperature application 35°C
Pdesignh (EN 14825) kW 21 26 30
SCOP (EN 14825) 4,17 3,63 3,88
ηs % 164 142 152
Energy class A++ A+ A++
THAITY MODEL SEASONAL PERFORMANCE IN HEATING MODE – Medium temperature application 55°C
Pdesignh (EN 14825) kW 19 - -
SCOP (EN 14825) 3,41 - -
ηs % 133 - -
Energy class A++ - -
  • Data at the following conditions:
  • Air: 35°C D.B. – Water: 12/7°C.
  • Air: 7°C D.B. – 6°C W.B. – Water: 40/45°C.
  • Air: 7°C D.B. – 6°C W.B. – Water: 30/35°C.
  • Air: -7°C D.B. – Water: 30/35°C.
  • In open field (Q = 2) at 5 m from the unit.
  • Weight refers to the most complete setup.
  • Performance according to EN 14511. P0 setup.
  • Low temperature application (7°C)
  • Seasonal energy efficiency: low temperature cooling (EU Regulation 2016/2281)
  • In Average climatic conditions.
  • Seasonal energy efficiency: ambient heating in Average climate (EU Regulations No.811/2013 and No.813/2013)

Manuals

To view all the documents, log in to the reserved area

Technical notes

To view all the documents, log in to the reserved area

Documents

To view all the documents, log in to the reserved area

Images

Format: tif
Request information about this product









    Find an agent or a reseller.

    Find a reseller in your area for a customized offer on Rhoss air conditioning solutions.