New
Web code (TCAITL, TCAIQL): FPV33 Web code (TCAITZ, TCAIQZ): FPV31
CHILLERS HEAT PUMPS AIR-cooled AXIAL fans

FullPOWER EVO VFD

TCAIT-TCAIQ 2565÷31865
Cooling capacity 550,4÷1864,1 kW

Packaged air-cooled water chillers with axial fans. Series with semi-hermetic screw compressors with variable Vi, inverter adjustment and R513A or R134a refrigerant gas

Features

Key features


Screw compressors with variable Vi, suitable for all applications

Continuous power adjustment from 8 to 100%

SEER up to 5,49 with FIEC accessory (EC fans)

R513A and R134a

Wide range of accessories

Integrated MASTER/SLAVE control


FullPOWER EVO VFD

Description

Construction features

• Compressor: high energy efficiency semi-hermetic screw compressor with variable Vi intrinsic compression ratio, star-delta limited start-up, inverter rotation adjustment (8-100%), complete with integral protection, casing heater, oil level sensor and refrigerant gas outlet piping shut-off valve.
• Water side heat exchanger: dry expansion shell and tube exchanger with counterflow heat exchange, complete with closed cell polyurethane foam rubber insulation, water flow differential pressure switch and Victaulic fittings.
• Air side heat exchanger: with micro-channels.
• Fan: external rotor axial type electric fans equipped with internal thermal protection, accident protection grilles and proportional electronic device for continuous fan rotation speed adjustment.
• Control: microprocessor electronic control.
• Structure: made of galvanised and painted steel plate with polyester powder coating.
• The unit is also complete with:
- display of cooling circuit high/low pressure;
- electronic expansion valve;
- oil level sensor;
- clock board;
- Master/Slave control up to 4 units in parallel;
- control of Variable Primary Flow (VPF_R).

Versions

• T - High efficiency version with oversized condensing section (TCAITL-TCAITZ).
• Q - Super-silenced version complete with compressor technical compartment soundproofing, reduced speed fans and oversized condensing section (TCAIQL-TCAIQZ).

Models

• TCAITL: high efficiency unit designed for cooling only with R513A gas.
• TCAIQL: super silenced unit designed for cooling only with R513A gas.
• TCAITZ: high efficiency unit designed for cooling only with R134a gas.
• TCAIQZ: super silenced unit designed for cooling only with R134a gas.

Factory fitted accessories

• PUMP with single or double electric pump, one of which automatic in standby. The electric pumps are available in the low or high head versions.
• Inverter pump control for unit start-up.
• Desuperheater.
• 100% heat recovery unit.
• Freecooling module management.
• Condensing control with fans with EC motor.
• Condensing control with over-pressure fans (T version only).
• Power factor correction capacitors (cosφ > 0.94).
• Compressor circuit breaker switches.
• Electro-mechanical flow switch.
• EMC anti-disturbance filters.
• Forced limit of power consumption.
• Forced noise limit.
• Energy parameter measuring device.
• Soundproofed compressor box.
• Cooling circuit intake valves.
• Refrigerant leak detector.
• Cooling circuit high and low pressure gauges.
• Double safety valves.
• Coil protection nets or buffer panels.
• Microchannel coils with E-coating treatment, copper/aluminium, copper/copper, pre-painted copper/aluminium.
• Control of min/max power supply voltage.
• Digital input for double set-point.
• 4-20 mA analogue signal for shifting set-point.
• Evaporator antifreeze heater, electrical panel, electric pumps and heat exchangers for heat recovery if applicable.
• Low temperature water production.
• Interfaces for serial communication with other devices.
• Colour touch user keypad (fitted on the machine or remotely) with 7” display.
• Spring anti-vibration mounts.
• Protective packaging.

Separately supplied accessories

• Remote keypad with display.
• Thermostat with display.
• Rhoss supervisors for unit monitoring and remote management.
• Rhoss sequencer for integrated management of multiple chillers.

Technical data

TCAITL-TCAIQL MODEL 2565 2615 2685 2775 2845 2945 21005 21195 21365 21495 21615 (*) 31715 (*) 31865 (*)
Nominal cooling capacity kW 568,4 616,5 686,4 779,4 852,3 951,3 1010,3 1190,2 1358,3 1497,1 1609,1 1703,2 1850,1
Nominal cooling capacity kW 550,4 601,5 670,4 756,4 829,3 923,4 985,3 1153,2 1315,3 1451,2 1554,1 1648,2 1782,1
E.E.R. 3,13 3,13 3,11 3,15 3,12 3,15 3,07 3,03 3,1 3,05 3,02 3,04 2,94
E.E.R. 2,92 3,01 2,9 2,95 2,86 2,94 2,89 2,8 2,88 2,88 2,83 2,84 2,72
Absorbed power kW 181,6 197 220,7 247,4 273,2 302 329,1 392,8 438,2 490,9 532,8 560,3 629,3
Absorbed power kW 188,5 199,8 231,2 256,4 290 314,1 340,9 411,9 456,7 503,9 549,2 580,4 655,2
TCAITL-TCAIQL MODEL 2565 2615 2685 2775 2845 2945 21005 21195 21365 21495 21615 31715 31865
Sound pressure dB(A) 69 70 70 71 71 72 72 72 73 73 74 75 75
Sound pressure dB(A) 61 61 61 62 63 63 64 64 65 65 67 68 68
Sound power dB(A) 102 103 103 104 104 105 105 105 106 106 107 108 108
Sound power dB(A) 94 94 94 95 96 96 97 97 98 98 100 101 101
Screw compressors n. 2 2 2 2 2 2 2 2 2 2 2 3 3
Circuits n. 2 2 2 2 2 2 2 2 2 2 2 3 3
Electrical supply V-ph-Hz 400-3-50 400-3-50 400-3-50 400-3-50 400-3-50 400-3-50 400-3-50 400-3-50 400-3-50 400-3-50 400-3-50 400-3-50 400-3-50
DIMENSIONS AND WEIGHTS 2565 2615 2685 2775 2845 2945 21005 21195 21365 21495 21615 31715 31865
L – Width mm 6090 7250 7250 8350 8350 10550 10550 10550 11650 12810 11650 12730 12730
H – Height mm 2480 2480 2480 2480 2480 2480 2480 2480 2480 2480 2580 2580 2580
P – Depth mm 2260 2260 2260 2260 2260 2260 2260 2260 2260 2260 2260 2260 2260
TCAITL weight kg 4144 4607 4707 5021 5141 5766 5876 6977 7763 8734 8036 9640 9687
TCAIQL weight kg 4524 5007 5107 5421 5541 6166 6276 7397 8183 9174 8476 10180 10227
SEASONAL ENERGY PERFORMANCE 2565 2615 2685 2775 2845 2945 21005 21195 21365 21495 21615 (*) 31715 (*) 31865 (*)
TCAITL MODEL SEASONAL PERFORMANCE IN COOLING MODE
Pdesignc (EN 14825) kW 568,4 616,5 686,4 779,4 852,3 951,3 1010,3 1190,2 1358,3 1497,1 1609,1 1703,2 1850,1
SEER  (EN 14825) 5,3 5,23 5,28 5,27 5,23 5,25 5,28 5,2 5,26 5,19 5,15 5,21 5,13
ηs,c % 209 206 208 208 206 207 208 205 208 204 203 205 202
TCAIQL MODEL SEASONAL PERFORMANCE IN COOLING MODE
Pdesignc (EN 14825) kW 550,4 601,5 670,4 756,4 829,3 923,4 985,3 1153,2 1315,3 1451,2 1554,1 1648,2 1782,1
SEER  (EN 14825) 5,19 5,12 5,17 5,17 5,13 5,16 5,17 5,1 5,19 5,13 5,06 5,11 5,03
ηs,c % 205 202 204 204 202 204 204 201 205 202 199 202 198
TCAITZ-TCAIQZ MODEL 2565 2615 2685 2775 2845 2945 21005 21195 21365 21495 21615 (*) 31715 (*) 31865 (*)
Nominal cooling capacity kW 570,4 619,5 689,4 782,4 856,3 955,3 1015,3 1195,2 1364,3 1504,1 1616,1 1715,2 1864,1
Nominal cooling capacity kW 552,4 604,5 673,4 759,4 833,3 927,4 989,3 1158,2 1321,3 1458,2 1567,1 1664,2 1808,1
E.E.R. 3,21 3,21 3,2 3,23 3,21 3,23 3,15 3,11 3,17 3,13 3,12 3,14 3,02
E.E.R. 3 3,09 2,98 3,02 2,94 3,02 2,96 2,87 2,95 2,95 2,92 2,93 2,82
Absorbed power kW 177,7 193 215,4 242,2 266,8 295,8 322,3 384,3 430,4 480,5 518,0 546,2 617,3
Absorbed power kW 184,1 195,6 226 251,5 283,4 307,1 334,2 403,6 447,9 494,3 536,7 568,0 641,2
TCAITZ-TCAIQZ MODEL 2565 2615 2685 2775 2845 2945 21005 21195 21365 21495 21615 31715 31865
Sound pressure dB(A) 69 70 70 71 71 72 72 72 73 73 74 75 75
Sound pressure dB(A) 61 61 61 62 63 63 64 64 65 65 67 68 68
Sound power dB(A) 102 103 103 104 104 105 105 105 106 106 107 108 108
Sound power dB(A) 94 94 94 95 96 96 97 97 98 98 100 101 101
Screw compressors/steps n. 2 2 2 2 2 2 2 2 2 2 2 3 3
Circuits n. 2 2 2 2 2 2 2 2 2 2 2 3 3
Electrical supply V-ph-Hz 400-3-50 400-3-50 400-3-50 400-3-50 400-3-50 400-3-50 400-3-50 400-3-50 400-3-50 400-3-50 400-3-50 400-3-50 400-3-50
DIMENSIONS AND WEIGHTS 2565 2615 2685 2775 2845 2945 21005 21195 21365 21495 21615 31715 31865
L – Width mm 6090 7250 7250 8350 8350 10550 10550 10550 11650 12810 11650 12730 12730
H – Height mm 2480 2480 2480 2480 2480 2480 2480 2480 2480 2480 2580 2580 2580
P – Depth mm 2260 2260 2260 2260 2260 2260 2260 2260 2260 2260 2260 2260 2260
TCAITZ weight kg 4144 4607 4707 5021 5141 5766 5876 6977 7763 8734 8036 9640 9687
TCAIQZ weight kg 4524 5007 5107 5421 5541 6166 6276 7397 8183 9174 8476 10180 10227
SEASONAL ENERGY PERFORMANCE 2565 2615 2685 2775 2845 2945 21005 21195 21365 21495 21615 (*) 31715 (*) 31865 (*)
TCAITZ MODEL SEASONAL PERFORMANCE IN COOLING MODE
Pdesignc (EN 14825) kW 570,4 619,5 689,4 782,4 856,3 955,3 1015,3 1195,2 1364,3 1504,1 1616,1 1715,2 1864,1
SEER  (EN 14825) 5,33 5,27 5,32 5,3 5,28 5,28 5,31 5,23 5,32 5,24 5,18 5,24 5,17
ηs,c % 210 208 210 209 208 208 210 206 210 207 204 206 204
TCAIQZ MODEL SEASONAL PERFORMANCE IN COOLING MODE
Pdesignc (EN 14825) kW 552,4 604,5 673,4 759,4 833,3 927,4 989,3 1158,2 1321,3 1458,2 1567,1 1664,2 1808,1
SEER  (EN 14825) 5,23 5,18 5,21 5,23 5,17 5,19 5,2 5,14 5,23 5,15 5,11 5,17 5,08
ηs,c % 206 204 205 206 204 205 205 203 206 203 201 204 200
  • Data at the following conditions:
  • Air: 35°C – Water: 12/7°C.
  • In open field (Q = 2) at 10 m from the unit.
  • Total sound power level in dB(A) based on measurements carried out in accordance with regulation UNI EN-ISO 9614.
  • Weight referred to the unit without load and not accessorised.
  • TCAIQL-TCAIQZ super-silenced versions.
  • Performance according to EN 14511.
  • (*) Unit not Eurovent certified
  • Low temperature application (7°C)
  • Seasonal energy efficiency: low temperature cooling (EU Regulation 2016/2281)

Manuals

To view all the documents, log in to the reserved area

Technical notes

To view all the documents, log in to the reserved area

Documents

To view all the documents, log in to the reserved area

Images

Format: TIF
Request information about this product









    Find an agent or a reseller.

    Find a reseller in your area for a customized offer on Rhoss air conditioning solutions.