WinPACK SE
TCAEY-THAEY 2110÷4340Water chillers and packaged reversible air-cooled heat pumps with axial fans. Range with scroll hermetic compressors and R410A refrigerant.
Key features
High performance range with extended working limits
Wide range of accessories
Compact version B for replacement markets
Multi-purpose for systems with 2 pipes + DHW (with optional RC100)
Built-in MASTER/SLAVE control
Description
Construction features
• Compressor: scroll type, rotary, hermetic complete with thermal protection and casing heater.
• 2, 3 or 4 capacity steps with high efficiency at partial loads.
Water side heat exchanger: with stainless steel plates, complete with closed cell polyurethane foam rubber insulation and water flow differential pressure switch.
• Air side heat exchanger: featuring micro-channels or finned coil with copper pipes and aluminium fins depending on models/sizes.
• Fan: external rotor axial type electric fans with internal thermal protection, accident protection grilles. The electric fans, based on the models, are fitted with a proportional electronic device for continuous regulation of the rotation speed of the fans.
• Control: microprocessor electronic control with Adaptive Function Plus logic.
• Structure: load-bearing structure made of galvanised and painted steel plate with polyester powder coating.
• The unit is also complete with:
- fan and compressor circuit breaker switches;
- display of cooling circuit high and low pressure;
- Master/Slave control up to 4 units in parallel;
- clock board;
- control of Variable Primary Flow (VPF_R).
Versions
• B -Standard version (TCAEBY-THAEBY).
• S - Silenced version complete with compressor technical compartment soundproofing, reduced speed fans (TCAESY-THAESY).
Models
• TCAEBY: standard unit designed for cooling only.
• TCAESY: silenced unit designed for cooling only.
• THAEBY: heat pump unit.
• THAESY: silenced heat pump unit
Factory fitted accessories
• Shell and tube evaporator.
• PUMP with single or double electric pump, one of which automatic in standby. The electric pumps are available in the low or high head versions.
• TANK&PUMP with integrated buffer tank from 300 to 700 litres (depending on models) and single or double electric pump, complete with expansion tank, air vent valves, safety valve, and water side pressure gauge.
• Inverter pump control for unit start-up.
• Desuperheater.
• 100% heat recovery unit.
• Freecooling module management.
• Electronic expansion valve.
• Condensing control (standard in models TCAEBY, TCAESY, THAESY).
• Condensing control with fans with EC motor.
• Condensing control with over-pressure fans.
• Power factor correction capacitors (cosφ > 0.94).
• Forced limit of power consumption.
• Forced noise limit.
• Energy parameter measuring device.
• Optimised energy efficiency.
• Soft starter.
• Soundproofed compressor box or technical compartment soundproofing.
• Compressor soundproof enclosures.
• Cooling circuit outlet and inlet valves.
• Refrigerant leak detector.
• Cooling circuit high and low pressure gauges.
• Double safety valves.
• Metal filters or coil protection nets.
• Microchannel coils with E-coating treatment, copper/copper and pre-painted copper/aluminium depending on the versions.
• Control of min/max power supply voltage.
• Digital input for double set-point.
• 4-20 mA analogue signal for shifting set-point.
• Evaporator antifreeze heater, electrical panel, buffer tank, electric pumps and heat exchangers for heat recovery, if applicable.
• Buffer tank integrative heaters.
• Low temperature water production.
• Interfaces for serial communication with other devices.
• Anti-vibration mounts.
Separately supplied accessories
• Remote keypad with display.
• Thermostat with display.
• Rhoss supervisors for unit monitoring and remote management.
• Rhoss sequencer for integrated management of multiple chillers.
Technical data
TCAEBY-TCAESY MODEL | 2110 | 2120 | 2140 | 2150 | 2170 | 2200 | 2220 | 4150 | 4170 | 4200 | 4220 | 4240 | 4270 | 4310 | 4340 | ||||
❶ | Nominal cooling capacity | kW | 106,5 | 114,4 | 127,4 | 147,3 | 165,2 | 188,1 | 212,1 | 146,3 | 166,4 | 189,2 | 213,2 | 229,2 | 256 | 299,9 | 328,7 | ||
❶ | Nominal cooling capacity | kW | 102,5 | 110,4 | 122,4 | 142,3 | 159,2 | 183,2 | 205,1 | 142,3 | 161,4 | 182,3 | 207,2 | 224,2 | 250 | 291 | 319,7 | ||
❶ | E.E.R. | 2,81 | 2,79 | 2,8 | 2,81 | 2,81 | 2,8 | 2,8 | 2,99 | 2,9 | 2,83 | 2,92 | 2,8 | 2,8 | 2,81 | 2,76 | |||
❶ | E.E.R. | 2,72 | 2,67 | 2,65 | 2,71 | 2,7 | 2,66 | 2,7 | 2,93 | 2,82 | 2,67 | 2,82 | 2,68 | 2,66 | 2,68 | 2,61 | |||
❶ | Absorbed power | kW | 37,9 | 41 | 45,5 | 52,4 | 58,8 | 67,2 | 75,8 | 48,9 | 57,4 | 66,9 | 73 | 81,9 | 91,4 | 106,7 | 119,1 | ||
❶ | Absorbed power | kW | 37,7 | 41,3 | 46,2 | 52,5 | 59 | 68,9 | 76 | 48,6 | 57,2 | 68,3 | 73,5 | 83,7 | 94 | 108,6 | 122,5 | ||
THAEBY-THAESY MODEL | 2110 | 2120 | 2140 | 2150 | 2170 | 2200 | 2220 | 4150 | 4170 | 4200 | 4220 | 4240 | 4270 | 4310 | 4340 | ||||
❷ | Nominal heating capacity | kW | 112,6 | 123,7 | 139,7 | 158,8 | 176,9 | 198 | 229,1 | 152,7 | 172,6 | 197,8 | 225,9 | 249 | 281,3 | 319,3 | 354,6 | ||
❷ | Nominal heating capacity | kW | 109,5 | 121,7 | 135,7 | 155,8 | 173,9 | 195,9 | 226 | 147,7 | 167,6 | 192,8 | 219,9 | 245 | 278,3 | 315,2 | 345,5 | ||
❷ | C.O.P. | 3,05 | 3,08 | 3,08 | 3,04 | 3,06 | 3,07 | 3,07 | 3,09 | 3,14 | 3,04 | 3,04 | 3,03 | 3,01 | 3,01 | 2,98 | |||
❷ | C.O.P. | 3,1 | 3,13 | 3,1 | 3,13 | 3,1 | 3,09 | 3,13 | 3,1 | 3,12 | 3,09 | 3,09 | 3,09 | 3,05 | 3,07 | 3,03 | |||
❶ | Nominal cooling capacity | kW | 99,5 | 110,4 | 123,4 | 142,3 | 159,3 | 182,2 | 206,1 | 141,3 | 163,4 | 186,2 | 209,1 | 227,1 | 253,9 | 295,9 | 324,7 | ||
❶ | Nominal cooling capacity | kW | 97,6 | 106,5 | 117,5 | 136,4 | 152,3 | 175,3 | 199,2 | 136,4 | 156,4 | 180,3 | 200,2 | 220,2 | 248 | 286,1 | 313,8 | ||
❷ | Absorbed power | kW | 36,9 | 40,2 | 45,4 | 52,2 | 57,8 | 64,5 | 74,6 | 49,4 | 55 | 65,1 | 74,3 | 82,2 | 93,5 | 106,1 | 119 | ||
❷ | Absorbed power | kW | 35,3 | 38,9 | 43,8 | 49,8 | 56,1 | 63,4 | 72,2 | 47,6 | 53,7 | 62,4 | 71,2 | 79,3 | 91,2 | 102,7 | 114 | ||
TCAEBY-TCAESY-THAEBY-THAESY MODEL | 2110 | 2120 | 2140 | 2150 | 2170 | 2200 | 2220 | 4150 | 4170 | 4200 | 4220 | 4240 | 4270 | 4310 | 4340 | ||||
❸ | TCAEBY sound pressure | dB(A) | 55 | 56 | 56 | 57 | 58 | 58 | 59 | 57 | 57 | 57 | 58 | 60 | 60 | 60 | 61 | ||
❸ | THAEBY sound pressure | dB(A) | 53 | 54 | 54 | 55 | 56 | 56 | 57 | 54 | 54 | 56 | 56 | 58 | 60 | 60 | 61 | ||
❸ | TCAESY sound pressure | dB(A) | 49 | 50 | 50 | 51 | 52 | 52 | 53 | 51 | 51 | 51 | 52 | 54 | 54 | 56 | 57 | ||
❸ | THAESY sound pressure | dB(A) | 49 | 50 | 50 | 51 | 52 | 52 | 53 | 50 | 50 | 52 | 52 | 54 | 55 | 56 | 57 | ||
❹ | TCAEBY sound power | dB(A) | 87 | 88 | 88 | 89 | 90 | 90 | 91 | 89 | 89 | 89 | 90 | 92 | 92 | 92 | 93 | ||
❹ | THAEBY sound power | dB(A) | 85 | 86 | 86 | 87 | 88 | 88 | 89 | 86 | 86 | 88 | 88 | 90 | 92 | 92 | 93 | ||
❹ | TCAESY sound power | dB(A) | 81 | 82 | 82 | 83 | 84 | 84 | 85 | 83 | 83 | 83 | 84 | 86 | 86 | 88 | 89 | ||
❹ | THAESY sound power | dB(A) | 81 | 82 | 82 | 83 | 84 | 84 | 85 | 82 | 82 | 84 | 84 | 86 | 87 | 88 | 89 | ||
Scroll compressors/steps | n. | 2/3 | 2/3 | 2/2 | 2/3 | 2/2 | 2/3 | 2/2 | 4/4 | 4/4 | 4/4 | 4/4 | 4/4 | 4/4 | 4/4 | 4/4 | |||
Circuits | n. | 1 | 1 | 1 | 1 | 1 | 1 | 1 | 2 | 2 | 2 | 2 | 2 | 2 | 2 | 2 | |||
Electrical supply | V-ph-Hz | 400-3-50 | 400-3-50 | 400-3-50 | 400-3-50 | 400-3-50 | 400-3-50 | 400-3-50 | 400-3-50 | 400-3-50 | 400-3-50 | 400-3-50 | 400-3-50 | 400-3-50 | 400-3-50 | 400-3-50 | |||
DIMENSIONS AND WEIGHT | 2110 | 2120 | 2140 | 2150 | 2170 | 2200 | 2220 | 4150 | 4170 | 4200 | 4220 | 4240 | 4270 | 4310 | 4340 | ||||
W – TCAEBY-TCAESY width | mm | 2650 | 2650 | 2650 | 3600 | 3600 | 3600 | 4550 | 3600 | 3600 | 3600 | 4550 | 4550 | 4550 | 4800 | 4800 | |||
W – THAEBY-THAESY width | mm | 2650 | 2650 | 2650 | 3600 | 3600 | 3600 | 4550 | 3450 | 3450 | 3700 | 3700 | 4800 | 4800 | 4800 | 4800 | |||
H – TCAEBY-TCAESY height | mm | 2440 | 2440 | 2440 | 2440 | 2440 | 2440 | 2440 | 2440 | 2440 | 2440 | 2440 | 2440 | 2440 | 2030 | 2030 | |||
H – THAEBY-THAESY height | mm | 2440 | 2440 | 2440 | 2440 | 2440 | 2440 | 2440 | 2000 | 2000 | 2030 | 2030 | 2030 | 2030 | 2030 | 2030 | |||
D – TCAEBY-TCAESY depth | mm | 1350 | 1350 | 1350 | 1350 | 1350 | 1350 | 1350 | 1350 | 1350 | 1350 | 1350 | 1350 | 1350 | 2090 | 2090 | |||
D – THAEBY-THAESY depth | mm | 1350 | 1350 | 1350 | 1350 | 1350 | 1350 | 1350 | 1520 | 1520 | 2090 | 2090 | 2090 | 2090 | 2090 | 2090 | |||
❺ | TCAEBY weight | kg | 990 | 1000 | 1010 | 1160 | 1180 | 1180 | 1340 | 1165 | 1185 | 1190 | 1335 | 1670 | 1690 | 2400 | 2410 | ||
❺ | TCAESY weight | kg | 1110 | 1120 | 1130 | 1280 | 1300 | 1300 | 1460 | 1300 | 1320 | 1325 | 1470 | 1830 | 1850 | 2440 | 2450 | ||
❺ | THAEBY weight | kg | 1250 | 1310 | 1320 | 1470 | 1480 | 1565 | 1730 | 1450 | 1525 | 1725 | 1800 | 2375 | 2460 | 2580 | 2595 | ||
❺ | THAESY weight | kg | 1250 | 1310 | 1320 | 1470 | 1480 | 1565 | 1730 | 1475 | 1550 | 1765 | 1840 | 2415 | 2500 | 2620 | 2635 | ||
SEASONAL ENERGY PERFORMANCE | 2110 | 2120 | 2140 | 2150 | 2170 | 2200 | 2220 | 4150 | 4170 | 4200 | 4220 | 4240 | 4270 | 4310 | 4340 | ||||
TCAEBY MODEL SEASONAL PERFORMANCE IN COOLING MODE | |||||||||||||||||||
① | Pdesignc (EN 14825) | kW | 106,5 | 114,4 | 127,4 | 147,3 | 165,2 | 188,1 | 212,1 | 146,3 | 166,4 | 189,2 | 213,2 | 229,2 | 256 | 299,9 | 328,6 | ||
① | SEER (EN 14825) | 4,16 | 4,15 | 4,13 | 4,17 | 4,14 | 4,27 | 4,13 | 4,3 | 4,26 | 4,3 | 4,33 | 4,26 | 4,32 | 4,26 | 4,25 | |||
② | ηs,c | % | 164 | 163 | 162 | 164 | 163 | 168 | 162 | 169 | 167 | 169 | 170 | 168 | 170 | 167 | 167 | ||
TCAESY MODEL SEASONAL PERFORMANCE IN COOLING MODE | |||||||||||||||||||
① | Pdesignc (EN 14825) | kW | 102,5 | 110,4 | 122,4 | 142,3 | 159,2 | 183,2 | 205,1 | 142,3 | 161,4 | 182,3 | 207,2 | 224,2 | 250 | 291 | 319,7 | ||
① | SEER (EN 14825) | 4,19 | 4,18 | 4,11 | 4,23 | 4,15 | 4,22 | 4,16 | 4,35 | 4,28 | 4,19 | 4,33 | 4,24 | 4,25 | 4,26 | 4,21 | |||
② | ηs,c | % | 164 | 164 | 161 | 166 | 163 | 166 | 163 | 171 | 168 | 165 | 170 | 167 | 167 | 167 | 165 | ||
THAEBY MODEL SEASONAL PERFORMANCE IN HEATING MODE | |||||||||||||||||||
③ | Pdesignh (EN 14825) | kW | 95 | 104 | 119 | 134 | 149 | 170 | 200 | 129 | 145 | 168 | 192 | 211 | 240 | 271 | 301 | ||
③ | SCOP (EN 14825) | 3,38 | 3,4 | 3,67 | 3,36 | 3,64 | 3,35 | 3,53 | 3,41 | 3,47 | 3,33 | 3,33 | 3,35 | 3,33 | 3,34 | 3,32 | |||
④ | ηs | % | 132 | 133 | 144 | 131 | 142 | 131 | 138 | 133 | 136 | 130 | 130 | 131 | 130 | 131 | 130 | ||
THAESY MODEL SEASONAL PERFORMANCE IN HEATING MODE | |||||||||||||||||||
③ | Pdesignh (EN 14825) | kW | 92 | 102 | 115 | 131 | 146 | 167 | 197 | 125 | 140 | 164 | 187 | 207 | 238 | 267 | 292 | ||
③ | SCOP (EN 14825) | 3,47 | 3,49 | 3,71 | 3,5 | 3,73 | 3,39 | 3,62 | 3,41 | 3,45 | 3,4 | 3,4 | 3,44 | 3,39 | 3,41 | 3,37 | |||
④ | ηs | % | 136 | 136 | 145 | 137 | 146 | 133 | 142 | 134 | 135 | 133 | 133 | 135 | 132 | 133 | 132 | ||
- Data at the following conditions:
- ❶ Air: 35°C – Water: 12/7°C.
- ❷ Air: 7°C, D.B. 6°C W.B.- Water: 40/45°C.
- ❸ In open field (Q = 2) at 10 m from the unit.
- ❹ Total sound power level in dB(A) based on measurements carried out in accordance with regulation UNI EN-ISO 9614.
- ❺ Weight referred to the unit without load and not accessorised.
- ■ TCAESY-THAESY silenced versions.
- Performance according to EN 14511.
- ① Low temperature application (7°C)
- ② Seasonal energy efficiency: low temperature cooling (EU Regulation 2016/2281)
- ③ In Average climatic conditions, low temperature application (35°C)
- ④ Seasonal energy efficiency: low temperature heating in Average climate (EU Regulations No.811/2013 and No.813/2013)
Manuals
To view all the documents, log in to the reserved area
Technical notes
To view all the documents, log in to the reserved area
Documents
To view all the documents, log in to the reserved area
Images
Request information about this product
Find a reseller in your area for a customized offer on Rhoss air conditioning solutions.