Web code: WK011
CHILLERS HEAT PUMPS AIR-cooled AXIAL fans

WinPACK SE

TCAEY-THAEY 2110÷4340
Cooling capacity 97,6÷328,6 kW
Heating capacity 109,5÷354,6 kW

Water chillers and packaged reversible air-cooled heat pumps with axial fans. Range with scroll hermetic compressors and R410A refrigerant.

Features

Key features


High performance range with extended working limits

Wide range of accessories

Compact version B for replacement markets

Multi-purpose for systems with 2 pipes + DHW (with optional RC100)

Built-in MASTER/SLAVE control


WinPACK SE

Description

Construction features

• Compressor: scroll type, rotary, hermetic complete with thermal protection and casing heater.
• 2, 3 or 4 capacity steps with high efficiency at partial loads.
Water side heat exchanger: with stainless steel plates, complete with closed cell polyurethane foam rubber insulation and water flow differential pressure switch.
• Air side heat exchanger: featuring micro-channels or finned coil with copper pipes and aluminium fins depending on models/sizes.
• Fan: external rotor axial type electric fans with internal thermal protection, accident protection grilles. The electric fans, based on the models, are fitted with a proportional electronic device for continuous regulation of the rotation speed of the fans.
• Control: microprocessor electronic control with Adaptive Function Plus logic.
• Structure: load-bearing structure made of galvanised and painted steel plate with polyester powder coating.
• The unit is also complete with:
- fan and compressor circuit breaker switches;
- display of cooling circuit high and low pressure;
- Master/Slave control up to 4 units in parallel;
- clock board;
- control of Variable Primary Flow (VPF_R).

Versions

• B -Standard version (TCAEBY-THAEBY).
• S - Silenced version complete with compressor technical compartment soundproofing, reduced speed fans (TCAESY-THAESY).

Models

• TCAEBY: standard unit designed for cooling only.
• TCAESY: silenced unit designed for cooling only.
• THAEBY: heat pump unit.
• THAESY: silenced heat pump unit

Factory fitted accessories

• Shell and tube evaporator.
• PUMP with single or double electric pump, one of which automatic in standby. The electric pumps are available in the low or high head versions.
• TANK&PUMP with integrated buffer tank from 300 to 700 litres (depending on models) and single or double electric pump, complete with expansion tank, air vent valves, safety valve, and water side pressure gauge.
• Inverter pump control for unit start-up.
• Desuperheater.
• 100% heat recovery unit.
• Freecooling module management.
• Electronic expansion valve.
• Condensing control (standard in models TCAEBY, TCAESY, THAESY).
• Condensing control with fans with EC motor.
• Condensing control with over-pressure fans.
• Power factor correction capacitors (cosφ > 0.94).
• Forced limit of power consumption.
• Forced noise limit.
• Energy parameter measuring device.
• Optimised energy efficiency.
• Soft starter.
• Soundproofed compressor box or technical compartment soundproofing.
• Compressor soundproof enclosures.
• Cooling circuit outlet and inlet valves.
• Refrigerant leak detector.
• Cooling circuit high and low pressure gauges.
• Double safety valves.
• Metal filters or coil protection nets.
• Microchannel coils with E-coating treatment, copper/copper and pre-painted copper/aluminium depending on the versions.
• Control of min/max power supply voltage.
• Digital input for double set-point.
• 4-20 mA analogue signal for shifting set-point.
• Evaporator antifreeze heater, electrical panel, buffer tank, electric pumps and heat exchangers for heat recovery, if applicable.
• Buffer tank integrative heaters.
• Low temperature water production.
• Interfaces for serial communication with other devices.
• Anti-vibration mounts.

Separately supplied accessories

• Remote keypad with display.
• Thermostat with display.
• Rhoss supervisors for unit monitoring and remote management.
• Rhoss sequencer for integrated management of multiple chillers.

Technical data

TCAEBY-TCAESY MODEL 2110 2120 2140 2150 2170 2200 2220 4150 4170 4200 4220 4240 4270 4310 4340
Nominal cooling capacity kW 106,5 114,4 127,4 147,3 165,2 188,1 212,1 146,3 166,4 189,2 213,2 229,2 256 299,9 328,7
Nominal cooling capacity kW 102,5 110,4 122,4 142,3 159,2 183,2 205,1 142,3 161,4 182,3 207,2 224,2 250 291 319,7
E.E.R. 2,81 2,79 2,8 2,81 2,81 2,8 2,8 2,99 2,9 2,83 2,92 2,8 2,8 2,81 2,76
E.E.R. 2,72 2,67 2,65 2,71 2,7 2,66 2,7 2,93 2,82 2,67 2,82 2,68 2,66 2,68 2,61
Absorbed power kW 37,9 41 45,5 52,4 58,8 67,2 75,8 48,9 57,4 66,9 73 81,9 91,4 106,7 119,1
Absorbed power kW 37,7 41,3 46,2 52,5 59 68,9 76 48,6 57,2 68,3 73,5 83,7 94 108,6 122,5
THAEBY-THAESY MODEL 2110 2120 2140 2150 2170 2200 2220 4150 4170 4200 4220 4240 4270 4310 4340
Nominal heating capacity kW 112,6 123,7 139,7 158,8 176,9 198 229,1 152,7 172,6 197,8 225,9 249 281,3 319,3 354,6
Nominal heating capacity kW 109,5 121,7 135,7 155,8 173,9 195,9 226 147,7 167,6 192,8 219,9 245 278,3 315,2 345,5
C.O.P. 3,05 3,08 3,08 3,04 3,06 3,07 3,07 3,09 3,14 3,04 3,04 3,03 3,01 3,01 2,98
C.O.P. 3,1 3,13 3,1 3,13 3,1 3,09 3,13 3,1 3,12 3,09 3,09 3,09 3,05 3,07 3,03
Nominal cooling capacity kW 99,5 110,4 123,4 142,3 159,3 182,2 206,1 141,3 163,4 186,2 209,1 227,1 253,9 295,9 324,7
Nominal cooling capacity kW 97,6 106,5 117,5 136,4 152,3 175,3 199,2 136,4 156,4 180,3 200,2 220,2 248 286,1 313,8
Absorbed power kW 36,9 40,2 45,4 52,2 57,8 64,5 74,6 49,4 55 65,1 74,3 82,2 93,5 106,1 119
Absorbed power kW 35,3 38,9 43,8 49,8 56,1 63,4 72,2 47,6 53,7 62,4 71,2 79,3 91,2 102,7 114
TCAEBY-TCAESY-THAEBY-THAESY MODEL 2110 2120 2140 2150 2170 2200 2220 4150 4170 4200 4220 4240 4270 4310 4340
TCAEBY sound pressure dB(A) 55 56 56 57 58 58 59 57 57 57 58 60 60 60 61
THAEBY sound pressure dB(A) 53 54 54 55 56 56 57 54 54 56 56 58 60 60 61
TCAESY sound pressure dB(A) 49 50 50 51 52 52 53 51 51 51 52 54 54 56 57
THAESY sound pressure dB(A) 49 50 50 51 52 52 53 50 50 52 52 54 55 56 57
TCAEBY sound power dB(A) 87 88 88 89 90 90 91 89 89 89 90 92 92 92 93
THAEBY sound power dB(A) 85 86 86 87 88 88 89 86 86 88 88 90 92 92 93
TCAESY sound power dB(A) 81 82 82 83 84 84 85 83 83 83 84 86 86 88 89
THAESY sound power dB(A) 81 82 82 83 84 84 85 82 82 84 84 86 87 88 89
Scroll compressors/steps n. 2/3 2/3 2/2 2/3 2/2 2/3 2/2 4/4 4/4 4/4 4/4 4/4 4/4 4/4 4/4
Circuits n. 1 1 1 1 1 1 1 2 2 2 2 2 2 2 2
Electrical supply V-ph-Hz 400-3-50 400-3-50 400-3-50 400-3-50 400-3-50 400-3-50 400-3-50 400-3-50 400-3-50 400-3-50 400-3-50 400-3-50 400-3-50 400-3-50 400-3-50
DIMENSIONS AND WEIGHT 2110 2120 2140 2150 2170 2200 2220 4150 4170 4200 4220 4240 4270 4310 4340
W – TCAEBY-TCAESY width mm 2650 2650 2650 3600 3600 3600 4550 3600 3600 3600 4550 4550 4550 4800 4800
W – THAEBY-THAESY width mm 2650 2650 2650 3600 3600 3600 4550 3450 3450 3700 3700 4800 4800 4800 4800
H – TCAEBY-TCAESY height mm 2440 2440 2440 2440 2440 2440 2440 2440 2440 2440 2440 2440 2440 2030 2030
H – THAEBY-THAESY height mm 2440 2440 2440 2440 2440 2440 2440 2000 2000 2030 2030 2030 2030 2030 2030
D – TCAEBY-TCAESY depth mm 1350 1350 1350 1350 1350 1350 1350 1350 1350 1350 1350 1350 1350 2090 2090
D – THAEBY-THAESY depth mm 1350 1350 1350 1350 1350 1350 1350 1520 1520 2090 2090 2090 2090 2090 2090
TCAEBY weight kg 990 1000 1010 1160 1180 1180 1340 1165 1185 1190 1335 1670 1690 2400 2410
TCAESY weight kg 1110 1120 1130 1280 1300 1300 1460 1300 1320 1325 1470 1830 1850 2440 2450
THAEBY weight kg 1250 1310 1320 1470 1480 1565 1730 1450 1525 1725 1800 2375 2460 2580 2595
THAESY weight kg 1250 1310 1320 1470 1480 1565 1730 1475 1550 1765 1840 2415 2500 2620 2635
SEASONAL ENERGY PERFORMANCE 2110 2120 2140 2150 2170 2200 2220 4150 4170 4200 4220 4240 4270 4310 4340
TCAEBY MODEL SEASONAL PERFORMANCE IN COOLING MODE
Pdesignc (EN 14825) kW 106,5 114,4 127,4 147,3 165,2 188,1 212,1 146,3 166,4 189,2 213,2 229,2 256 299,9 328,6
SEER  (EN 14825) 4,16 4,15 4,13 4,17 4,14 4,27 4,13 4,3 4,26 4,3 4,33 4,26 4,32 4,26 4,25
ηs,c % 164 163 162 164 163 168 162 169 167 169 170 168 170 167 167
TCAESY MODEL SEASONAL PERFORMANCE IN COOLING MODE
Pdesignc (EN 14825) kW 102,5 110,4 122,4 142,3 159,2 183,2 205,1 142,3 161,4 182,3 207,2 224,2 250 291 319,7
SEER  (EN 14825) 4,19 4,18 4,11 4,23 4,15 4,22 4,16 4,35 4,28 4,19 4,33 4,24 4,25 4,26 4,21
ηs,c % 164 164 161 166 163 166 163 171 168 165 170 167 167 167 165
THAEBY MODEL SEASONAL PERFORMANCE IN HEATING MODE
Pdesignh (EN 14825) kW 95 104 119 134 149 170 200 129 145 168 192 211 240 271 301
SCOP (EN 14825) 3,38 3,4 3,67 3,36 3,64 3,35 3,53 3,41 3,47 3,33 3,33 3,35 3,33 3,34 3,32
ηs % 132 133 144 131 142 131 138 133 136 130 130 131 130 131 130
THAESY MODEL SEASONAL PERFORMANCE IN HEATING MODE
Pdesignh (EN 14825) kW 92 102 115 131 146 167 197 125 140 164 187 207 238 267 292
SCOP (EN 14825) 3,47 3,49 3,71 3,5 3,73 3,39 3,62 3,41 3,45 3,4 3,4 3,44 3,39 3,41 3,37
ηs % 136 136 145 137 146 133 142 134 135 133 133 135 132 133 132
  • Data at the following conditions:
  • Air: 35°C – Water: 12/7°C.
  • Air: 7°C, D.B. 6°C W.B.- Water: 40/45°C.
  • In open field (Q = 2) at 10 m from the unit.
  • Total sound power level in dB(A) based on measurements carried out in accordance with regulation UNI EN-ISO 9614.
  • Weight referred to the unit without load and not accessorised.
  • TCAESY-THAESY silenced versions.
  • Performance according to EN 14511.
  • Low temperature application (7°C)
  • Seasonal energy efficiency: low temperature cooling (EU Regulation 2016/2281)
  • In Average climatic conditions, low temperature application (35°C)
  • Seasonal energy efficiency: low temperature heating in Average climate (EU Regulations No.811/2013 and No.813/2013)

Manuals

To view all the documents, log in to the reserved area

Technical notes

To view all the documents, log in to the reserved area

Documents

To view all the documents, log in to the reserved area

Images

Format: tif
Request information about this product









    Find an agent or a reseller.

    Find a reseller in your area for a customized offer on Rhoss air conditioning solutions.