Web code: WK021
CHILLERS HEAT PUMPS AIR-cooled AXIAL fans

WinPACK-R SE

TCAEBY-TCAESY 4225÷4345
Cooling capacity 214,2÷345,7 kW

Packaged air-cooled water chillers with axial fans. Range with scroll hermetic compressors and R410A refrigerant.

Features

Key features


Compact chillers also for replacement markets

High performance range with extended operating limits

Simplified installation thanks to pumping unit accessories

Integrated MASTER/SLAVE control


WinPACK-R SE

Description

Construction features

• Compressor: scroll type, rotary, hermetic complete with thermal protection and casing heater.
• 4 capacity steps with high efficiency at partial loads.
Water side heat exchanger: with stainless steel plates, complete with closed cell polyurethane foam rubber insulation and water flow differential pressure switch.
• Air side heat exchanger: with micro-channels.
• Fan: external rotor axial type electric fans with internal thermal protection, accident protection grilles.
• Control: microprocessor electronic control with Adaptive Function Plus logic.
• Structure: load-bearing structure made of galvanised and painted steel plate with polyester powder coating.
• The unit is also complete with:
- fan and compressor circuit breaker switches;
- display of cooling circuit high and low pressure;
- Master/Slave control up to 4 units in parallel;
- clock board;
- control of Variable Primary Flow (VPF_R).

Versions

• B - Standard version.
• S - Silenced version complete with compressor technical compartment soundproofing and reduced speed fans.

Models

• TCAEBY: standard unit designed for cooling only.
• TCAESY: silenced unit designed for cooling only.

Factory fitted accessories

• Shell and tube evaporator.
• PUMP with single or double electric pump, one of which automatic in standby. The electric pumps are available in the low or high head versions.
• TANK&PUMP with 500 - 700 litre integrated buffer tank (depending on models) and single or double electric pump, complete with expansion tank, air vent valves, safety valve and water side pressure gauge.
• Inverter pump control for unit start-up.
• Desuperheater.
• 100% heat recovery unit.
• Freecooling module management.
• Electronic expansion valve.
• Condensing control (standard in S versions).
• Condensing control with fans with EC motor.
• Condensing control with over-pressure fans.
• Power factor correction capacitors (cosφ > 0.94).
• Forced limit of power consumption.
• Forced noise limit.
• Energy parameter measuring device.
• Optimised energy efficiency.
• Soft starter.
• Soundproofed compressor box.
• Compressor soundproof enclosures.
• Cooling circuit outlet and inlet valves.
• Refrigerant leak detector.
• Cooling circuit high and low pressure gauges.
• Double safety valves.
• Coil protection nets.
• Micro-channel coils with E-coating treatment.
• Control of min/max power supply voltage.
• Digital input for double set-point.
• 4-20 mA analogue signal for shifting set-point.
• Evaporator antifreeze heater, electrical panel, buffer tank, electric pumps and heat exchangers for heat recovery, if applicable.
• Low temperature water production.
• Interfaces for serial communication with other devices.
• Anti-vibration mounts.

Separately supplied accessories

• Remote keypad with display.
• Thermostat with display.
• Rhoss supervisors for unit monitoring and remote management.
• Rhoss sequencer for integrated management of multiple chillers.

Technical data

TCAEBY-TCAESY MODEL 4225 4245 4265 4315 4345
Nominal cooling capacity kW 220,2 241,2 264 313,9 345,7
Nominal cooling capacity kW 214,2 234,2 252,1 305 333,8
E.E.R. 3 2,81 2,61 2,88 2,81
E.E.R. 2,9 2,67 2,4 2,76 2,66
Absorbed power kW 73,4 85,8 101,1 108,9 123
Absorbed power kW 73,9 87,7 105 110,5 125,5
TCAEBY-TCAESY MODEL 4225 4245 4265 4315 4345
Sound pressure dB(A) 58 59 60 61 62
Sound pressure dB(A) 52 53 54 56 57
Sound power dB(A) 90 91 92 93 94
Sound power dB(A) 84 85 86 88 89
Scroll compressors/steps n. 4/4 4/4 4/4 4/4 4/4
Circuits n. 2 2 2 2 2
Electrical supply V-ph-Hz 400-3-50 400-3-50 400-3-50 400-3-50 400-3-50
DIMENSIONS AND WEIGHTS 4225 4245 4265 4315 4345
L – Width mm 2550 2550 2550 3650 3650
H – Height mm 2450 2450 2450 2450 2450
P – Depth mm 2260 2260 2260 2260 2260
TCAEBY weight kg 1300 1500 1650 1985 2000
TCAESY weight kg 1460 1660 1810 2215 2230
SEASONAL ENERGY PERFORMANCE 4225 4245 4265 4315 4345
TCAEBY MODEL SEASONAL PERFORMANCE IN COOLING MODE
Pdesignc (EN 14825) kW 220,2 241,2 264 313,9 345,7
SEER  (EN 14825) 4,31 4,31 4,3 4,34 4,34
ηs,c % 169 169 169 170 171
TCAESY MODEL SEASONAL PERFORMANCE IN COOLING MODE
Pdesignc (EN 14825) kW 214,2 234,2 252,1 305 333,8
SEER  (EN 14825) 4,28 4,27 4,26 4,3 4,3
ηs,c % 168 168 167 169 169
  • Data at the following conditions:
  • Air: 35°C – Water: 12/7°C.
  • In open field (Q = 2) at 10 m from the unit.
  • Total sound power level in dB(A) based on measurements carried out in accordance with regulation UNI EN-ISO 9614.
  • Weight referred to the unit without load and not accessorised.
  • TCAESY silenced versions
  • Performance according to EN 14511.
  • Low temperature application (7°C)
  • Seasonal energy efficiency: low temperature cooling (EU Regulation 2016/2281)

Manuals

To view all the documents, log in to the reserved area

Technical notes

To view all the documents, log in to the reserved area

Documents

To view all the documents, log in to the reserved area

Images

Format: tif
Request information about this product









    Find an agent or a reseller.

    Find a reseller in your area for a customized offer on Rhoss air conditioning solutions.