Wall mounted fan coils with EC motor
IDROWALL-I IDROWALL-I/V3Wall mounted fan coils.
Key features
Consumption reduced by 50% compared to the traditional motor
New version without on board valve
V3 version with 3-way ON/OFF valve on board
Integrated master/slave function and serial interface
Remote control included
Description
Construction features
• Heat exchanger: finned coil.
• Fan: tangential with Inverter Brushless EC motor with continuous speed adjustment.
• Baffle: motorised with different positions.
• Structure: made of heat-resistant ABS polymer, RAL 9003 colour, complete with a regenerable polypropylene filter, adjustable fins and a natural condensate drain pan.
• Control: microprocessor electronic control.
Adjustment functions: full auto (Idrowall-I/V3), cool, dry, fan, autofan, heat.
Comfort functions: orienting, swing, timer, sleep, hot start, memory.
Remote control supplied as standard.
Resident RS485 serial interface.
>IDROWALL-I - Unit complete with backlit temperature display; digital output for mandatory ON/OFF valve control (not supplied) to be installed upstream of the unit; master-slave management of up to 10 units in total, with KPI panel.
>IDROWALL-I/V3 - Unit fitted with 3-way ON/OFF diverter valve, fitted on board; master-slave management of up to 64 units in total; centralised management with KWPCI panel of up to 64 units in total; SYS-TO compatible.
Separately supplied accessories
• KVAM - Wall mounted recessed box.
>IDROWALL-I/V3
• KV2V - 2-way ON/OFF valve accessory. Assembled on board by the installer.
• K2TF - Accessory for valve use externally to the unit. Assembled by the installer.
Controls supplied separately
>IDROWALL-I
• KPI - Electronic panel flush with display semi-recessed in the wall.
>IDROWALL-I/V3
• KWPI - Electronic panel for wall mounting installation.
• KWPCI - Centralised electronic panel for wall mounting installation Power supply V230-1-50.
Technical data
IDROWALL-I | IDROWALL-I | IDROWALL-I | IDROWALL-I | IDROWALL-I/V3 | IDROWALL-I/V3 | IDROWALL-I/V3 | |||||
20 | 25 | 35 | 45 | 21 | 31 | 41 | |||||
❶ | Total cooling capacity [EN1397] | MAX | kW | E | 2,20 | 2,70 | 3,60 | 4,30 | 1,99 | 2,95 | 3,5 |
MED | kW | E | 1,55 | 1,90 | 2,50 | 3,00 | 1,63 | 2,14 | 2,45 | ||
MIN | kW | E | 1,25 | 1,35 | 1,90 | 2,30 | 1,32 | 1,89 | 1,89 | ||
❷ | Heating capacity (45°C) [EN1397] | MAX | kW | E | 2,4 | 2,9 | 3,9 | 4,7 | 2,68 | 4,2 | 4,45 |
MED | kW | E | 1,7 | 2,2 | 2,7 | 3,4 | 2,02 | 3,04 | 3,63 | ||
MIN | kW | E | 1,4 | 1,55 | 2 | 2,5 | 1,45 | 2,61 | 2,61 | ||
❸ | Heating capacity (50°C) | MAX | kW | E | 2,86 | 3,48 | 4,77 | 5,82 | 3,05 | 4,78 | 5,14 |
MED | kW | E | 1,93 | 2,38 | 3,14 | 3,99 | 2,34 | 3,46 | 4,11 | ||
MIN | kW | E | 1,68 | 1,65 | 2,23 | 2,79 | 1,72 | 2,98 | 2,98 | ||
Air flow speed | MAX | m³/h | 340 | 510 | 680 | 850 | 556 | 722 | 814 | ||
MED | m³/h | 255 | 382 | 510 | 637 | 413 | 473 | 581 | |||
MIN | m³/h | 170 | 255 | 340 | 425 | 295 | 396 | 396 | |||
Sound power | MAX | dB(A) | E | 48 | 52 | 59 | 62 | 52 | 55 | 59 | |
MED | dB(A) | E | 39 | 44 | 51 | 53 | 43 | 46 | 51 | ||
MIN | dB(A) | E | 37 | 38 | 43 | 45 | 34 | 42 | 42 | ||
❹ | Sound pressure | MAX | dB(A) | 39 | 43 | 50 | 53 | 43 | 46 | 50 | |
MED | dB(A) | 30 | 35 | 42 | 44 | 34 | 37 | 42 | |||
MIN | dB(A) | 28 | 29 | 34 | 36 | 25 | 33 | 33 | |||
Absorbed power | MAX | W | E | 12 | 18 | 29 | 43 | 22 | 27 | 38 | |
MED | W | E | 9 | 11 | 16 | 20 | 14 | 15 | 19 | ||
MIN | W | E | 8 | 8 | 11 | 12 | 11 | 12 | 12 | ||
Electrical supply | V-ph-Hz | 230-1-50 | 230-1-50 | 230-1-50 | 230-1-50 | 230-1-50 | 230-1-50 | 230-1-50 | |||
DIMENSIONS AND WEIGHTS | 20 | 25 | 35 | 45 | 21 | 31 | 41 | ||||
L – Width | mm | 845 | 845 | 845 | 970 | 795 | 990 | 990 | |||
H – Height | mm | 289 | 289 | 289 | 300 | 290 | 290 | 290 | |||
P – Depth | mm | 209 | 209 | 209 | 224 | 230 | 230 | 230 | |||
Weight | kg | 10,5 | 10,5 | 10,5 | 12,5 | 9,3 | 11,6 | 11,6 | |||
- Data at the following conditions:
- ❶ Air: 27°C D.B.; 19°C W.B. – Water: 7/12°C.
- ❷ Air: 20°C – Water: 45/40°C.
- ❸ Air: 20°C – Water: 50°C, flow rate as in cooling.
- ❹ For room volume equal to 100 m³ and reverberation time = 0.5 sec.
- E Eurovent certificate performance.
- ❹ Air: 20°C – Water: 70/60°C.
- ❺ For room volume equal to 100 m³ and reverberation time = 0.5 sec.
- E Eurovent certificate performance.
Manuals
To view all the documents, log in to the reserved area
Technical notes
To view all the documents, log in to the reserved area
Documents
To view all the documents, log in to the reserved area
Request information about this product
Find a reseller in your area for a customized offer on Rhoss air conditioning solutions.