FREECOOLING Modules
FFAM-FGAM 1÷11Packaged air-cooled water coolers in Freecooling mode (FFAM) and Freecooling NO-GLYCOL mode (FGAM) with axial fans.
Key features
NO GLYCOL version available
Compatible with many Rhoss product ranges
Dedicated pumping groups
Description
Construction features
• Heat exchanger (water-water) in Freecooling NO-GLYCOL: with stainless steel plates, complete with closed cell polyurethane foam rubber insulation and water flow differential pressure switch.
• Air side heat exchanger: featuring finned coil with copper pipes and aluminium fins.
• Fan: external rotor axial type electric fans equipped with internal thermal protection, accident protection grilles and proportional electronic device for continuous fan rotation speed regulation.
• Structure: load-bearing structure made of galvanised and painted steel plate with polyester powder coating.
• The unit is also complete with:
- fan circuit breaker switches;
- water side 3-way modulating valve.
Versions
• B - Standard compact version (FFAMB-FGAMB).
• T - High efficiency version (FFAMT-FGAMT).
• Q - Supersilenced version complete with reduced speed fans (FFAMQ-FGAMQ).
Models
• FFAMB: standard unit in Freecooling mode.
• FFAMT: high efficiency unit in Freecooling mode.
• FFAMQ: supersilenced unit in Freecooling mode.
• FGAMB: standard unit in NO-GLYCOL Freecooling mode.
• FGAMT: high efficiency unit in NO-GLYCOL Freecooling mode.
• FGAMQ: supersilenced unit in NO-GLYCOL Freecooling mode.
Factory fitted accessories
• PUMP with single or double electric pump, including an automatic actuation pump in standby. The electric pumps are available in the low or high head versions.
• TANK&PUMP with integrated 700 or 1000 litres buffer tank depending on models and single or double electric pump, complete with expansion tank, air vent valves and water side pressure gauge.
• Bottom compartment protection nets.
• Coil protection nets.
• Plate exchanger antifreeze heater (FGAM).
• Electrical panel heater.
• Control of min/max power supply voltage.
• Pre-painted copper/coils coils.
• Anti-vibration mounts.
Technical data
FFAMB MODEL | 1M | 2M | 3M | 4M | 5M | 6M | 7M | 8M | 9M | 10M | 11M | ||||
❶ | Nominal cooling capacity | kW | 123,5 | 247,1 | 370,8 | 494,1 | 617,2 | 738,7 | 860,4 | 981,5 | 1101,9 | 1221,6 | 1340,4 | ||
❶ | E.E.R. | 20,2 | 20,8 | 21,0 | 20,9 | 20,5 | 19,5 | 18,9 | 18,2 | 17,5 | 16,8 | 16,1 | |||
❶ | Absorbed power | kW | 6,1 | 11,9 | 17,6 | 23,7 | 30,0 | 37,9 | 45,5 | 53,9 | 62,9 | 72,6 | 83,2 | ||
FFAMT-FFAMQ MODEL | 1M | 2M | 3M | 4M | 5M | 6M | 7M | 8M | 9M | 10M | 11M | ||||
❶ | Nominal cooling capacity | kW | 108,1 | 216,4 | 324,6 | 432,6 | 540,5 | 647,3 | 754,2 | 860,7 | 966,7 | 1072,1 | 1177,0 | ||
❶ | Nominal cooling capacity | kW | 90,9 | 181,9 | 273,0 | 363,9 | 454,7 | 544,8 | 635,0 | 725,0 | 814,6 | 903,9 | 992,9 | ||
❶ | E.E.R. | 32,5 | 34,8 | 35,4 | 35,0 | 34,4 | 32,2 | 30,9 | 29,6 | 28,2 | 26,8 | 25,4 | |||
❶ | E.E.R. | 36,0 | 39,0 | 40,2 | 40,0 | 39,5 | 37,4 | 36,1 | 34,8 | 33,4 | 32,0 | 30,5 | |||
❶ | Absorbed power | kW | 3,3 | 6,2 | 9,2 | 12,4 | 15,7 | 20,1 | 24,4 | 29,1 | 34,3 | 40,1 | 46,4 | ||
❶ | Absorbed power | kW | 2,5 | 4,7 | 6,8 | 9,1 | 11,5 | 14,6 | 17,6 | 20,8 | 24,4 | 28,3 | 32,5 | ||
FFAMB-FFAMT-FFAMQ MODEL | 1M | 2M | 3M | 4M | 5M | 6M | 7M | 8M | 9M | 10M | 11M | ||||
❷ | Sound pressure FFAMB | dB(A) | 53 | 56 | 58 | 59 | 60 | 60 | 61 | 61 | 62 | 62 | 62 | ||
❷ | Sound pressure FFAMT | dB(A) | 50 | 53 | 55 | 56 | 57 | 57 | 58 | 58 | 59 | 59 | 59 | ||
❷ | Sound pressure FFAMQ | dB(A) | 44 | 47 | 49 | 50 | 51 | 51 | 52 | 52 | 53 | 53 | 53 | ||
❸ | Sound power FFAMB | dB(A) | 85 | 88 | 90 | 91 | 92 | 93 | 93,5 | 94 | 94,5 | 95 | 95,5 | ||
❸ | Sound power FFAMT | dB(A) | 82 | 85 | 87 | 88 | 89 | 90 | 90,5 | 91 | 91,5 | 92 | 92,5 | ||
❸ | Sound power FFAMQ | dB(A) | 76 | 79 | 81 | 82 | 83 | 84 | 84,5 | 85 | 85,5 | 86 | 86,5 | ||
Circuits | n. | 1 | 1 | 1 | 1 | 1 | 1 | 1 | 1 | 1 | 1 | 1 | |||
Electrical supply | V-ph-Hz | 400-3-50 | 400-3-50 | 400-3-50 | 400-3-50 | 400-3-50 | 400-3-50 | 400-3-50 | 400-3-50 | 400-3-50 | 400-3-50 | 400-3-50 | |||
DIMENSIONS AND WEIGHTS | 1M | 2M | 3M | 4M | 5M | 6M | 7M | 8M | 9M | 10M | 11M | ||||
L – Width | mm | 1.240 | 2.340 | 3.430 | 4.540 | 5.640 | 6.800 | 7.900 | 9000 | 10100 | 11200 | 12360 | |||
H – Height | mm | 2.480 | 2.480 | 2.480 | 2.480 | 2.480 | 2.480 | 2.480 | 2480 | 2480 | 2480 | 2480 | |||
P – Depth | mm | 2.260 | 2.260 | 2.260 | 2.260 | 2.260 | 2.260 | 2.260 | 2260 | 2260 | 2260 | 2260 | |||
❹ | FFAM Weight | kg | 670 | 1.255 | 1.720 | 2.130 | 2.590 | 3.375 | 3.820 | 4230 | 4660 | 5135 | 5690 | ||
❹ | FGAM Weight | kg | 825 | 1445 | 1985 | 2500 | 3000 | 3835 | 4320 | 4810 | 5315 | 6075 | 6710 | ||
- Data at the following conditions:
- ❶ Air: 0°C – Water: 15/10°C – Ethylene glycol 30%.
- ❷ In open field (Q = 2) at 10 m from the unit.
- ❸ Total sound power level in dB(A) based on measurements carried out in accordance with regulation UNI EN-ISO 9614.
- ❹ Weight referred to the unit without load and not accessorised.
- ■ FFAMQ super-silenced versions.
Manuals
To view all the documents, log in to the reserved area
Technical notes
To view all the documents, log in to the reserved area
Documents
To view all the documents, log in to the reserved area
Images
Request information about this product
Find a reseller in your area for a customized offer on Rhoss air conditioning solutions.