Web code: YARV3 - YARI3 Web code accessories: ACMEC Web code controls: ACREG
FAN COILS

Fan coils

COVER for YARDY
Cooling capacity 1,8÷4,8 kW
Heating capacity 2,3÷5,8 kW

Installation solutions with formwork and covering panels on the wall or on the ceiling

Features

Key features

Concealed fan coil installation
Wall-flush aesthetic cover panel in white RAL 9003
Recessed wall or false ceiling installation

Fan coils

Description

Yardy EV3 and Yardy-I EV3 - Versions

• IVP - Recessed vertical unit equipped with lower air inlet and upper delivery for wall mounting installation.
• IXP - Horizontal/vertical unit equipped with lower air inlet and upper delivery for false ceiling or recessed wall installation.
Yardy-ID2 and YardyDUCT2 - Version
• CXP - Ducted recessed unit for horizontal or vertical installation (with lower return and upper delivery).

Models

Yardy-I EV3: 20, 24, 30, 34, 45, 48
Yardy EV3: 20, 24, 25, 30, 34, 40, 45, 48
Yardy-ID2: 40, 48
YardyDUCT2: 40, 48

Construction set-ups

Type of unit
2T - Single main coil.
4T - Double main coil and additional.

ACCESSORIES for Yardy COVER

➔ Formwork for recessed wall or false ceiling installation
➔ Aesthetic panel for wall mounted formwork, colour matt white RAL 9003, with air delivery and return grille for wall mounting installation (IVP and IXP version only).
➔ Aesthetic panel for formwork, colour matt white RAL 9003, with air inlet grille for wall mounting or ceiling installation
➔ Delivery nozzle made of aluminium, with a double row of adjustable fins

CONTROLS for Yardy COVER

STANDARD controls
For wall mounting installation
➔ Panel with speed and summer/winter switch.
➔ Panel with room thermostat, summer/winter switch, speed switch, ON/OFF valve control and electrical resistance.
➔ Minimum temperature thermostat (for installation on machine).
➔ Electronic panel with automatic summer/winter switching for 2-pipe systems.
➔ Electronic panel with automatic summer/winter switching and automatic speed adjustment for 2-pipe systems with electrical resistance or 4-pipe systems.
➔ Electronic panel with display and RS485 serial interface, semi-recessed in wall.

Advanced LIT-TOUCH controls

➔ Flush LIT-Touch control panel in glossy black or pearl white for wall mounting installation.
➔ Wall mounted LIT-Touch remote control and receiver with air temperature probe and operation LED.
For on board installation
➔❖ LIT-Touch electronic control for 2-pipe systems, with 2 pipes with electrical resistance or 4 pipes, complete with minimum water temperature probe, ON/OFF valve control and integrated master/slave function up to a total of 15 units.
➔❖ Additional board with 2 digital outputs that can be configured.
➔❖ On board air temperature probe.
➔❖ RS485 serial board for serial communication with other devices (Modbus RTU protocol).

Technical data

YARDY-I EV3 IVP-IXP 20 24 30 34 45 48
Total cooling capacity [EN1397] MAX kW E 1,86 2,24 2,97 3,37 4,11 4,6
MED kW E 1,44 1,68 2,33 2,75 3,05 3,49
MIN kW E 0,75 0,8 1,08 1,34 1,53 1,73
Heating capacity (45°C) [EN1397] MAX kW E 2,1 2,18 3,27 3,41 4,47 4,65
MED kW E 1,48 1,57 2,52 2,6 3,13 3,27
MIN kW E 0,77 0,81 1,2 1,26 1,5 1,57
Heating capacity (50°C) MAX kW E 2,47 2,6 3,87 4,07 5,3 5,54
MED kW E 1,77 1,88 2,99 3,14 3,74 3,93
MIN kW E 0,92 0,97 1,42 1,52 1,81 1,9
Heating capacity (70°C) [EN1397] MAX kW 4,2 4,36 6,56 6,85 8,96 9,31
MED kW 2,98 3,14 5,06 5,26 6,28 6,56
MIN kW 1,56 1,64 2,44 2,56 3,06 3,19
Heating capacity of additional coil (65°C) [EN1397] MAX kW E 1,95 2,08 2,94 2,8 3,36 3,2
MED kW E 1,66 1,6 2,34 2,22 2,84 2,7
MIN kW E 0,87 0,83 1,3 1,23 1,53 1,46
Heating capacity of additional coil (70°C) [EN1397] MAX kW E 2,21 2,36 3,33 3,17 3,83 3,64
MED kW E 1,92 1,84 2,65 2,52 3,3 3,15
MIN kW E 1,01 0,96 1,48 1,41 1,79 1,7
Air flow speed MAX m³/h 331 331 523 523 645 645
MED m³/h 230 230 400 400 450 450
MIN m³/h 97 97 167 167 198 198
Sound power MAX dB(A) E 48 48 50 50 51 51
MED dB(A) E 40 40 43 43 42 42
MIN dB(A) E 29 29 29 29 29 29
Sound pressure MAX dB(A) 39 39 41 41 42 42
MED dB(A) 31 31 34 34 33 33
MIN dB(A) 20 20 20 20 20 20
Absorbed power MAX W E 23 25 26 28 39 42
MED W E 13 14 15 16 14 15
MIN W E 6 6 6 6 7 8
Electrical supply V-ph-Hz 230-1-50 230-1-50 230-1-50 230-1-50 230-1-50 230-1-50
DIMENSIONS AND WEIGHT 20 24 30 34 45 48
L – IVP-IXP Width mm 550 550 750 750 950 950
H – IVP-IXP Height mm 545 545 545 545 545 545
P – IVP-IXP Depth mm 212 212 212 212 212 212
IVP-IXP Weight kg 16,5 17 20,5 21,5 25,5 27
COVER for Yardy-I 20 24 30 34 45 48
KCASE formwork WxHxD mm 920x790x225 920x790x225 1125x790x225 1125x790x225 1325x790x225 1325x790x225
KCASE formwork Weight kg 13 13 15 15 17 17
KPVCASE – KPXCASE panel WxHxD mm 975x820x10 975x820x10 1175x820x10 1175x820x10 1375x820x10 1375x820x10
KPVCASE – KPXCASE panel Weight kg 9 9 10 10 11 11
KGMD delivery nozzle WxHxD mm 555x205x6 555x205x6 755x205x6 755x205x6 955x205x6 955x205x6
YARDY EV3 IVP-IXP 20 24 25 30 34 40 45 48
Total cooling capacity [EN1397] VI kW 1,98 2,2 •E 2,5 •E 3,21 3,28 •E 3,72 4,26 •E 4,76 •E
V kW 1,76 •E 2,1 2,24 2,8 •E 3,05 3,36 •E 3,84 4,46
IV kW 1,54 1,87 •E 2,02 •E 2,57 2,81 •E 2,84 3,31 •E 3,57 •E
III kW 1,37 •E 1,68 1,69 2,46 •E 2,55 2,63 •E 2,99 3,35
II kW 1,18 1,45 •E 1,62 •E 2,07 2,25 •E 2,47 2,81 3,11
I kW 1,13 •E 1,35 1,38 1,78 •E 1,98 2,06 •E 2,49 •E 2,85 •E
Heating capacity (45°C) [EN1397] VI kW 2,26 2,36 •E 2,97 •E 3,59 3,77 •E 4,37 4,68 •E 4,89 •E
V kW 1,97 •E 2,04 2,68 3,29 •E 3,45 3,79 •E 4,27 4,45
IV kW 1,62 1,73 •E 2,3 •E 2,85 2,98 •E 3,22 3,47 •E 3,64 •E
III kW 1,47 •E 1,52 1,94 2,66 •E 2,79 2,98 •E 3,21 3,34
II kW 1,26 1,44 •E 1,85 •E 2,26 2,35 •E 2,77 2,81 2,93
I kW 1,24 •E 1,27 1,57 2,02 •E 2,2 2,52 •E 2,59 •E 2,69 •E
Heating capacity (50°C) VI kW 2,65 2,78 •E 3,47 •E 4,21 4,42 •E 5,11 5,51 •E 5,79 •E
V kW 2,31 •E 2,43 3,14 3,85 •E 4,04 4,45 •E 5,03 5,28
IV kW 1,91 2,06 •E 2,71 •E 3,36 3,53 •E 3,79 4,11 •E 4,32 •E
III kW 1,74 •E 1,83 2,28 3,14 •E 3,3 3,5 •E 3,79 3,98
II kW 1,49 1,72 •E 2,18 •E 2,67 2,8 •E 3,26 3,35 3,52
I kW 1,46 •E 1,53 1,84 2,37 •E 2,59 2,93 •E 3,08 •E 3,23 •E
Heating capacity (70°C) [EN1397] VI kW 4,52 4,71 5,94 7,17 7,54 8,75 9,34 9,77
V kW 3,93 4,08 5,37 6,58 6,88 7,59 8,53 8,88
IV kW 3,23 3,45 4,61 5,71 5,97 6,46 6,93 7,27
III kW 2,95 3,06 3,88 5,32 5,61 5,96 6,4 6,69
II kW 2,54 2,89 3,71 4,53 4,76 5,57 5,63 5,89
I kW 2,5 2,57 3,15 4,06 4,44 5,05 5,19 5,42
Heating capacity of additional coil (65°C) [EN1397] VI kW 2,09 1,78 •E 2,7 •E 3,2 3,05 •E 3,68 3,5 •E 3,34 •E
V kW 1,92 •E 1,69 2,61 2,69 •E 2,56 2,94 •E 3,38 3,22
IV kW 1,81 1,46 •E 2,28 •E 2,61 2,48 •E 2,9 2,96 •E 2,82 •E
III kW 1,51 •E 1,33 2 2,28 •E 2,17 2,81 •E 2,79 2,65
II kW 1,4 1,2 •E 1,84 •E 2,15 2,04 •E 2,76 2,74 2,6
I kW 1,29 •E 1,16 1,69 1,93 •E 1,83 2,62 •E 2,21 •E 2,15 •E
Heating capacity of additional coil (70°C) [EN1397] VI kW 2,37 2,01 •E 3,06 •E 3,62 3,45 •E 4,18 3,98 •E 3,79 •E
V kW 2,2 •E 1,93 2,95 3,04 •E 2,9 3,46 •E 3,84 3,66
IV kW 2,09 1,7 •E 2,59 •E 2,95 2,8 •E 3,36 3,46 •E 3,27 •E
III kW 1,75 •E 1,56 2,27 2,58 •E 2,46 3,33 •E 3,25 3,07
II kW 1,63 1,4 •E 2,12 •E 2,43 2,31 •E 3,26 3,2 3,02
I kW 1,5 •E 1,34 1,92 2,19 •E 2,06 3,07 •E 2,59 •E 2,53 •E
Air flow speed VI m³/h 339 339 484 547 547 676 681 681
V m³/h 288 288 405 483 483 587 627 627
IV m³/h 238 238 339 434 434 472 474 474
III m³/h 207 207 281 383 383 419 431 431
II m³/h 177 177 252 329 321 390 392 392
I m³/h 155 155 217 281 281 365 338 338
Sound power VI dB(A) 48 48 •E 48 •E 50 50 •E 51 52 •E 52 •E
V dB(A) 44 •E 44 42 46 •E 47 48 •E 50 50
IV dB(A) 41 40 •E 38 •E 43 43 •E 43 43 •E 43 •E
III dB(A) 38 •E 35 33 40 •E 40 40 •E 41 41
II dB(A) 34 32 •E 30 •E 36 36 •E 38 38 38
I dB(A) 30 •E 31 26 35 •E 34 35 •E 35 •E 35 •E
Sound pressure VI dB(A) 39 39 39 41 41 42 43 43
V dB(A) 35 35 33 37 38 39 41 41
IV dB(A) 32 31 29 34 34 34 34 34
III dB(A) 29 26 24 31 31 31 32 32
II dB(A) 25 23 21 27 27 29 29 29
I dB(A) 21 22 17 26 25 26 26 26
Absorbed power VI W 40 41 •E 56 •E 60 65 •E 72 70 •E 76 •E
V W 36 •E 32 42 54 •E 58 58 •E 61 66
IV W 25 25 •E 32 •E 36 39 •E 42 41 •E 44 •E
III W 23 •E 21 27 31 •E 33 34 •E 36 39
II W 17 16 •E 21 •E 27 27 •E 33 31 33
I W 15 •E 14 20 25 •E 25 28 •E 28 •E 30 •E
Electrical supply V-ph-Hz 230-1-50 230-1-50 230-1-50 230-1-50 230-1-50 230-1-50 230-1-50 230-1-50
DIMENSIONS AND WEIGHT 20 24 25 30 34 40 45 48
L – IVP-IXP Width mm 550 550 750 750 750 950 950 950
H – IVP-IXP Height mm 545 545 545 545 545 545 545 545
P – IVP-IXP Depth mm 212 212 212 212 212 212 212 212
IVP-IXP Weight kg 16,5 17 20,5 20,5 21,5 24 25,5 27
COVER for Yardy 20 24 25 30 34 40 45 48
KCASE formwork WxHxD mm 920x790x225 920x790x225 1125x790x225 1125x790x225 1125x790x225 1325x790x225 1325x790x225 1325x790x225
KCASE formwork Weight kg 13 13 15 15 15 17 17 17
KPVCASE – KPXCASE panel WxHxD mm 975x820x10 975x820x10 1175x820x10 1175x820x10 1175x820x10 1375x820x10 1375x820x10 1375x820x10
KPVCASE – KPXCASE panel Weight kg 9 9 10 10 10 11 11 11
KGMD delivery nozzle WxHxD mm 555x205x6 555x205x6 755x205x6 755x205x6 755x205x6 955x205x6 955x205x6 955x205x6
  • Data at the following conditions:
  • Air: 27°C D.B.; 19°C W.B. – Water: 7/12°C.
  • Air: 20°C – Water: 45/40°C.
  • Air: 20°C – Water: 50°C, flow rate as in cooling.
  • Air: 20°C – Water: 70/60°C.
  • Air: 20°C – Water: 65/55°C.
  • For room volume equal to 100 m³ and reverberation time = 0.5 sec.
  • E Eurovent certified performance.
  • Performance refers to the motor’s input signal: 10V – 6V – 1V at MAX – MED – MIN speed.
  • YARDY-I EV3 24 – 34 – 48 – 74 – 88 with oversized 4-row coil.
  • Data at the following conditions:
  • Air: 27°C D.B.; 19°C W.B. – Water: 7/12°C.
  • Air: 20°C – Water: 45/40°C.
  • Air: 20°C – Water: 50°C, flow rate as in cooling.
  • Air: 20°C – Water: 70/60°C.
  • Air: 20°C – Water: 65/55°C.
  • For room volume equal to 100 m³ and reverberation time = 0.5 sec.
  • Wired speed in terminal block.
  • E Eurovent certified performance.
  • Yardy EV3 24 – 34 – 48 – 74 – 88 with oversized 4-row coil.
  • For the selection with Air’Suite filter, refer to the UP-TO-DATE selection Software.

Manuals

To view all the documents, log in to the reserved area

Technical notes

To view all the documents, log in to the reserved area

Documents

To view all the documents, log in to the reserved area

Images

Format: tif
Format: tif
Format: tif
Format: tif
Format: tif
Format: tif
Request information about this product









    Find an agent or a reseller.

    Find a reseller in your area for a customized offer on Rhoss air conditioning solutions.