Fan coils with EC motor
BRIO-I SLIMFloor and ceiling fan coil units with cabinet for recessed wall or false ceiling installation.
Key features
Exclusive design with thin profile
Silent operation
Excellent room comfort with continuous regulation of the fan speed
Low consumption with standard EC motor
Versions with cabinet and recessed with front radiant function
Touch control
Description
Construction features
• Heat exchanger: finned coil with Eurokonus ¾” connections on the left; connections on the right with accessory supplied separately.
• Tangential fan with constant speed adjustment EC electronic motor and low-consumption micro-fans in the version with radiant function.
• Cabinet version structure: covering cabinet consisting of a painted sheet metal central panel and sides made of ABS polymer (or painted sheet metal for 4T units - 4-pipe systems), RAL9003 colour with matt finish, upper delivery grille in silver grey painted aluminium.
Complete unit with vertical condensate drain pan and an additional one with a natural drain, a regenerable filter and fixing brackets.
• Recessed version structure: in galvanised sheet steel, complete with a vertical condensate drain pan and an additional horizontal one with a natural drain, a regenerable filter and fixing brackets.
Versions
• MVP - Vertical unit with cabinet for wall mounting installation or with feet on the ground; ceiling installation with accessory supplied separately (KVXO)
• IXP - Recessed horizontal/vertical unit for wall or false ceiling installation.
• MVR - Vertical only unit with cabinet and front radiant function, for wall mounting installation or with feet on the ground (only unit 2T).
• IVR - Vertical only recessed unit with front radiant function, for wall formwork installation (only unit 2T).
Construction set-ups
Type of unit
2T - Single main coil.
4T - Double main coil and additional (MVP and IXP versions only).
ACCESSORIES
➔ Cable for water connections on the right side.
➔ Eurokonus / Gas connection straight fitting.
➔❖ 2 -way ON/OFF electrovalves for 2 and 4-pipe systems.
➔❖ 3 -way ON/OFF electrovalves for 2 and 4-pipe systems.
➔ Condensate drain pan for horizontal installation.
➔ Back in view.
➔ Aesthetic and floor support feet.
➔ Formwork for recessed installation (only 2-pipe systems)
➔ Wall aesthetic panel for formwork, colour matt white RAL 9003.
➔ Ceiling aesthetic panel for formwork, colour matt white RAL 9003.
➔ Straight or 90° inlet fitting.
➔ 90° delivery fitting, insulated.
➔ Telescopic delivery fitting, insulated.
➔ Wall inlet grille made of aluminium, with straight profile.
➔ Wall mounted delivery nozzle made of aluminium, with a double row of adjustable fins.
➔ Ceiling inlet grille made of aluminium, with curved profile.
➔ Ceiling delivery nozzle made of aluminium, with curved profile.
CONTROLS
STANDARD controls
For on board installation
➔ Electronic board in combination with 3-speed thermostats
➔ Electronic board in combination with thermostats with 0-10V analogue output
For wall mounting installation
➔ Panel with room thermostat, summer/winter switch, speed switch and ON/OFF valve control.
➔ Electronic panel with automatic summer/winter switching for 2-pipe systems.
ADVANCED controls
➔ Wall mounting slim-touch control panel in glossy black or pearl white, with RS485 Modbus RTU interface.
For installation on machine
➔❖ Touch control on board and electronic control with continuous speed modulation, with RS485 Modbus RTU interface.
➔❖ Touch control on board and 4-speed electronic control, only for 2-pipe systems.
➔❖ Electronic control with continuous speed modulation only when combined with a KPST panel, with master/slave control up to 31 controls.
Key: ❖ Factory fitted
➔ Supplied separately
Technical data
BRIO-I SLIM – MVP-MVR-IXP-IVR | 10 | 20 | 25 | 30 | 40 | ||||
❶ | Total cooling capacity [EN1397] | MAX | kW | E | 0,98 | 1,81 | 2,87 | 3,31 | 3,94 |
MED | kW | E | 0,75 | 1,35 | 2,16 | 2,43 | 2,9 | ||
MIN | kW | E | 0,38 | 0,73 | 1,14 | 1,27 | 1,46 | ||
❷ | Heating capacity (45°C) [EN1397] | MAX | kW | E | 1,13 | 2,03 | 3,19 | 3,75 | 4,46 |
MED | kW | E | 0,81 | 1,48 | 2,32 | 2,75 | 3,11 | ||
MIN | kW | E | 0,57 | 0,75 | 0,92 | 1,48 | 1,79 | ||
❸ | Heating capacity (50°C) | MAX | kW | E | 1,39 | 2,46 | 3,89 | 4,51 | 5,43 |
MED | kW | E | 1,0 | 1,75 | 2,78 | 3,23 | 3,73 | ||
MIN | kW | E | 0,7 | 0,84 | 1,04 | 1,56 | 1,87 | ||
❹ | Heating capacity (70°C) [EN1397] | MAX | kW | 2,27 | 4,08 | 6,41 | 7,54 | 9,17 | |
MED | kW | 1,63 | 2,98 | 4,67 | 5,52 | 6,42 | |||
MIN | kW | 1,16 | 1,54 | 1,84 | 2,97 | 3,7 | |||
❸ | Heating capacity only radiant function (50°C) MVR-IVR version | kW | 0,32 | 0,38 | 0,46 | 0,55 | 0,66 | ||
❹ | Heating capacity only radiant function (70°C) MVR-IVR version | kW | 0,54 | 0,67 | 0,78 | 0,92 | 1,08 | ||
❺ | Heating capacity of additional coil (65°C) [EN1397] | MAX | kW | E | 0,67 | 1,21 | 1,76 | 2,3 | 2,53 |
MED | kW | E | 0,56 | 0,97 | 1,27 | 1,81 | 2,05 | ||
MIN | kW | E | 0,33 | 0,69 | 0,95 | 1,31 | 1,29 | ||
❹ | Heating capacity of additional coil (70°C) [EN1397] | MAX | kW | E | 0,78 | 1,44 | 2,18 | 2,77 | 2,88 |
MED | kW | E | 0,64 | 1,16 | 1,56 | 2,2 | 2,35 | ||
MIN | kW | E | 0,37 | 0,81 | 1,13 | 1,59 | 1,48 | ||
Air flow speed | MAX | m³/h | 162 | 320 | 461 | 576 | 648 | ||
MED | m³/h | 113 | 252 | 367 | 453 | 494 | |||
MIN | m³/h | 55 | 155 | 248 | 370 | 426 | |||
Sound power | MAX | dB(A) | E | 50 | 51 | 52 | 54 | 54 | |
MED | dB(A) | E | 42 | 43 | 45 | 46 | 46 | ||
MIN | dB(A) | E | 32 | 33 | 34 | 35 | 36 | ||
❻ | Sound pressure | MAX | dB(A) | 41 | 42 | 43 | 45 | 45 | |
MED | dB(A) | 33 | 34 | 36 | 37 | 37 | |||
MIN | dB(A) | 23 | 24 | 25 | 26 | 27 | |||
Absorbed power | MAX | W | E | 11 | 19 | 20 | 28 | 35 | |
MED | W | E | 9 | 10 | 13 | 15 | 17 | ||
MIN | W | E | 7 | 7 | 7 | 8 | 8 | ||
Electrical supply | V-ph-Hz | 230-1-50 | 230-1-50 | 230-1-50 | 230-1-50 | 230-1-50 | |||
DIMENSIONS AND WEIGHTS | 10 | 20 | 25 | 30 | 40 | ||||
W – Width MVP-MVR | mm | 723 | 923 | 1123 | 1323 | 1523 | |||
W – Width IXP-IVR | mm | 525 | 725 | 925 | 1125 | 1325 | |||
H – Height MVP-MVR – 2T | mm | 579 | 579 | 579 | 579 | 579 | |||
H – Height IXP-IVR – 2T | mm | 590 | 590 | 590 | 590 | 590 | |||
H – Height MVP – 4T | mm | 639 | 639 | 639 | 639 | 639 | |||
H – Height IXP – 4T | mm | 650 | 650 | 650 | 650 | 650 | |||
Feet height /minimum height from floor | mm | 80 | 80 | 80 | 80 | 80 | |||
D – MVP-MVR depth | mm | 149 | 149 | 149 | 149 | 149 | |||
D – IXP-IVR depth | mm | 126 | 126 | 126 | 126 | 126 | |||
Weight MVP-MVR – 2T / MVP- 4T | kg | 17 / 18 | 20 / 21 | 23 / 25 | 26 / 28 | 29 / 32 | |||
Weight IXP-IVR – 2T / IXP – 4T | kg | 9 / 10 | 12 / 13 | 15 / 17 | 18 / 20 | 21 / 24 | |||
LxHxD – KCASE – 2T formwork | mm | 715x725x142 | 915x725x142 | 1115x725x142 | 1315x725x142 | 1515x725x142 | |||
- Data at the following conditions:
- ❶ Air: 27°C D.B.; 19°C W.B. – Water: 7/12°C.
- ❷ Air: 20°C – Water: 45/40°C.
- ❸ Air: 20°C – Water: 50°C, flow rate as in cooling.
- ❹ Air: 20°C – Water: 70/60°C.
- ❺ Air: 20°C – Water: 65/55°C.
- ❻ For room volume equal to 100 m³ and reverberation time = 0.5 sec.
- E Eurovent certified performance.
Manuals
To view all the documents, log in to the reserved area
Technical notes
To view all the documents, log in to the reserved area
Documents
To view all the documents, log in to the reserved area
Request information about this product
Find a reseller in your area for a customized offer on Rhoss air conditioning solutions.